Motor FLA Calculator
Find the full-load amps (FLA) of an electric motor from its horsepower rating, supply voltage, phase, power factor and efficiency. Works for DC, single-phase and three-phase AC motors.
Free download
Get the printable wire size charts
NEC 310.16 ampacity for copper and aluminium at 60, 75 and 90 C, how far each size runs before voltage drop bites, standard breaker sizes and AWG to mm2. Three pages, made for the van door.
How It Works
The formula
Motor shaft power in watts is horsepower multiplied by 746. Full-load current is then the input electrical power divided by voltage, phase factor, power factor and efficiency:
- Shaft power: W = HP × 746
- DC: FLA = W / (V × Eff)
- Single-phase AC: FLA = W / (V × PF × Eff)
- Three-phase AC: FLA = W / (√3 × V × PF × Eff)
The √3 factor (approximately 1.732) accounts for the relationship between line and phase quantities in a balanced three-phase system. Power factor (PF) is the ratio of real to apparent power; efficiency (Eff) is the ratio of shaft output to electrical input.
If you are sizing the supply for a pump and do not yet have a shaft power figure, work it out from head and flow rate on the pump power calculator, then bring the kW result back here to get the full-load amps.
Once the motor is in front of you, the plate is the document, and NEC 430.6 tells you which field is for the conductors and which is for the overload. That is the motor nameplate guide.
Worked examples
A 10 HP three-phase motor running at 460 V with a power factor of 0.85 and efficiency of 90%:
- Shaft power = 10 × 746 = 7,460 W
- FLA = 7,460 / (1.732 × 460 × 0.85 × 0.90) ≈ 12.2 A
A 5 HP single-phase motor at 230 V, sized the way NEC Article 430 requires:
- Calculated FLA at PF 0.85 and 90% = 3,730 / (230 × 0.85 × 0.90) ≈ 21.2 A
- Table 430.248 full-load current: 28 A. This is the figure for the circuit, not the calculated one (430.6(A)(1)).
- Conductor at 125% (430.22): 28 × 1.25 = 35.0 A, so 8 AWG copper at the 60°C column
- Inverse-time breaker at up to 250% (430.52): 28 × 2.5 = 70.0 A, so a 70 A breaker
A 25 HP three-phase motor at 460 V:
- Calculated FLA = 18,650 / (1.732 × 460 × 0.85 × 0.90) ≈ 30.6 A
- Table 430.250 full-load current: 34 A
- Conductor: 34 × 1.25 = 42.5 A, so 6 AWG copper at 60°C
- Breaker: 34 × 2.5 = 85.0 A is not a standard size, so 430.52(C)(1) Exception No. 1 allows the next one up: 90 A
NEC 430.6 note: For conductor and overcurrent device sizing, NEC Article 430 requires using the full-load current (FLC) values from Tables 430.247 to 430.250 rather than the nameplate FLA or a calculated value. Use this calculator for estimation and reference; consult the NEC tables for code-compliant sizing.
NEC Table 430.248: single-phase motor full-load current
Full-load current in amps for single-phase AC motors running at usual speeds with normal torque. The listed voltages are rated motor voltages; the currents apply to systems of 110 to 120 V and 220 to 240 V. NEC 430.6(A)(1) makes these figures, not the nameplate, the basis for the conductors, the disconnect and the branch-circuit breaker.
| HP | 115 V | 200 V | 208 V | 230 V |
|---|---|---|---|---|
| 1/6 hp (0.17) | 4.4 | 2.5 | 2.4 | 2.2 |
| 1/4 hp (0.25) | 5.8 | 3.3 | 3.2 | 2.9 |
| 1/3 hp (0.33) | 7.2 | 4.1 | 4.0 | 3.6 |
| 1/2 hp (0.5) | 9.8 | 5.6 | 5.4 | 4.9 |
| 3/4 hp (0.75) | 13.8 | 7.9 | 7.6 | 6.9 |
| 1 hp | 16 | 9.2 | 8.8 | 8.0 |
| 1-1/2 hp (1.5) | 20 | 11.5 | 11 | 10 |
| 2 hp | 24 | 13.8 | 13.2 | 12 |
| 3 hp | 34 | 19.6 | 18.7 | 17 |
| 5 hp | 56 | 32.2 | 30.8 | 28 |
| 7-1/2 hp (7.5) | 80 | 46 | 44 | 40 |
| 10 hp | 100 | 57.5 | 55 | 50 |
NEC Table 430.250: three-phase motor full-load current
Full-load current in amps for three-phase induction motors (squirrel cage and wound rotor) at usual speeds and normal torque. The currents apply to systems of 110 to 120, 220 to 240, 440 to 480 and 550 to 600 V. The 2300 V column is not shown. NEC 430.6(A)(1) makes these figures, not the nameplate, the basis for the conductors, the disconnect and the branch-circuit breaker.
| HP | 115 V | 200 V | 208 V | 230 V | 460 V | 575 V |
|---|---|---|---|---|---|---|
| 1/2 hp (0.5) | 4.4 | 2.5 | 2.4 | 2.2 | 1.1 | 0.9 |
| 3/4 hp (0.75) | 6.4 | 3.7 | 3.5 | 3.2 | 1.6 | 1.3 |
| 1 hp | 8.4 | 4.8 | 4.6 | 4.2 | 2.1 | 1.7 |
| 1-1/2 hp (1.5) | 12 | 6.9 | 6.6 | 6.0 | 3.0 | 2.4 |
| 2 hp | 13.6 | 7.8 | 7.5 | 6.8 | 3.4 | 2.7 |
| 3 hp | - | 11 | 10.6 | 9.6 | 4.8 | 3.9 |
| 5 hp | - | 17.5 | 16.7 | 15.2 | 7.6 | 6.1 |
| 7-1/2 hp (7.5) | - | 25.3 | 24.2 | 22 | 11 | 9.0 |
| 10 hp | - | 32.2 | 30.8 | 28 | 14 | 11 |
| 15 hp | - | 48.3 | 46.2 | 42 | 21 | 17 |
| 20 hp | - | 62.1 | 59.4 | 54 | 27 | 22 |
| 25 hp | - | 78.2 | 74.8 | 68 | 34 | 27 |
| 30 hp | - | 92 | 88 | 80 | 40 | 32 |
| 40 hp | - | 120 | 114 | 104 | 52 | 41 |
| 50 hp | - | 150 | 143 | 130 | 65 | 52 |
| 60 hp | - | 177 | 169 | 154 | 77 | 62 |
| 75 hp | - | 221 | 211 | 192 | 96 | 77 |
| 100 hp | - | 285 | 273 | 248 | 124 | 99 |
| 125 hp | - | 359 | 343 | 312 | 156 | 125 |
| 150 hp | - | 414 | 396 | 360 | 180 | 144 |
| 200 hp | - | 552 | 528 | 480 | 240 | 192 |
| 250 hp | - | - | - | - | 302 | 242 |
| 300 hp | - | - | - | - | 361 | 289 |
| 350 hp | - | - | - | - | 414 | 336 |
| 400 hp | - | - | - | - | 477 | 382 |
| 450 hp | - | - | - | - | 515 | 412 |
| 500 hp | - | - | - | - | 590 | 472 |
Motor wire and breaker size from the table current
Copper conductor at 125% of the table full-load current (430.22), from the 60°C column where that is 100 A or less and the 75°C column above it, and the largest inverse-time breaker 430.52 allows, 250% of the same current rounded up to a standard size. Single motor, not more than three current-carrying conductors, 30°C ambient, no voltage drop allowance. Motors marked NEMA design B, C or D may use the 75°C column below 100 A as well (110.14(C)(1)(a)(4)), which can save a size. Overload protection is separate and is set from the nameplate, not this table (430.32).
| Motor | Table FLC (A) | 125% (A) | Copper wire | Max breaker (A) |
|---|---|---|---|---|
| 1 HP, 230 V 1-phase | 8.0 | 10.0 | 14 AWG | 20 |
| 2 HP, 230 V 1-phase | 12 | 15.0 | 14 AWG | 30 |
| 3 HP, 230 V 1-phase | 17 | 21.3 | 10 AWG | 45 |
| 5 HP, 230 V 1-phase | 28 | 35.0 | 8 AWG | 70 |
| 7-1/2 HP, 230 V 1-phase | 40 | 50.0 | 6 AWG | 100 |
| 10 HP, 230 V 1-phase | 50 | 62.5 | 4 AWG | 125 |
| 3 HP, 208 V 3-phase | 10.6 | 13.3 | 14 AWG | 30 |
| 5 HP, 208 V 3-phase | 16.7 | 20.9 | 10 AWG | 45 |
| 7-1/2 HP, 208 V 3-phase | 24.2 | 30.3 | 8 AWG | 70 |
| 10 HP, 208 V 3-phase | 30.8 | 38.5 | 8 AWG | 80 |
| 15 HP, 208 V 3-phase | 46.2 | 57.8 | 4 AWG | 125 |
| 20 HP, 208 V 3-phase | 59.4 | 74.3 | 3 AWG | 150 |
| 5 HP, 460 V 3-phase | 7.6 | 9.5 | 14 AWG | 20 |
| 10 HP, 460 V 3-phase | 14 | 17.5 | 12 AWG | 35 |
| 15 HP, 460 V 3-phase | 21 | 26.3 | 10 AWG | 60 |
| 20 HP, 460 V 3-phase | 27 | 33.8 | 8 AWG | 70 |
| 25 HP, 460 V 3-phase | 34 | 42.5 | 6 AWG | 90 |
| 30 HP, 460 V 3-phase | 40 | 50.0 | 6 AWG | 100 |
| 40 HP, 460 V 3-phase | 52 | 65.0 | 4 AWG | 150 |
| 50 HP, 460 V 3-phase | 65 | 81.3 | 3 AWG | 175 |
| 75 HP, 460 V 3-phase | 96 | 120.0 | 1 AWG | 250 |
| 100 HP, 460 V 3-phase | 124 | 155.0 | 2/0 AWG | 350 |
A planning aid, not a design sign-off. Long runs need a voltage drop check: take the 125% current to the voltage drop calculator.
Frequently Asked Questions
How do you calculate motor full-load amps?
Multiply the horsepower by 746 to get shaft power in watts. For single-phase AC, divide by (voltage times power factor times efficiency). For three-phase AC, divide by (root-3 times voltage times power factor times efficiency). For DC motors, divide simply by (voltage times efficiency).
How do I convert HP to amps?
You need the supply voltage, phase, power factor and efficiency as well as the horsepower. One horsepower equals 746 W of mechanical output. For a 5 HP single-phase 230 V motor at PF 0.85 and 90% efficiency, FLA = (5 × 746) / (230 × 0.85 × 0.9) ≈ 21.2 A. NEC Table 430.248 lists 28 A for the same motor, and that is the figure the circuit is sized from.
Why do power factor and efficiency matter for motor current?
Power factor represents how much of the apparent current in an AC circuit does useful work. A lower power factor means more current is drawn for the same shaft output. Efficiency is the ratio of mechanical power out to electrical power in; a 90% efficient motor draws more current than an ideal 100% efficient one. Both factors increase the real current drawn from the supply compared to a simple watts-to-amps calculation.
Should I use this calculated FLA or the NEC table value for breaker and wire sizing?
For code-compliant conductor and overcurrent device sizing, NEC Article 430.6 requires using the full-load current (FLC) values from NEC Tables 430.247 to 430.250, not the nameplate or a calculated value. The calculated FLA is useful for estimation, load studies and comparing motors, but the NEC table value must be used for protective device and wiring selection on US installations.
What is the difference between single-phase and three-phase motor current?
For the same horsepower and voltage, a three-phase motor draws approximately 1/√3 (about 58%) of the line current of an equivalent single-phase motor. This is why three-phase motors are preferred for larger loads: they draw less current per phase, allowing smaller conductors and lower losses. A 10 HP motor at 230 V works out at roughly 42 A single-phase but about 24 A per line three-phase, and the NEC tables give 50 A and 28 A.
Related Calculators
Continue with these related electrical tools
Breaker / Fuse Sizing Calculator
Next standard breaker or fuse size for a load (NEC 240.6)
Wire Size Calculator
Smallest conductor that meets ampacity and the voltage-drop limit (AWG/mm2)
Three-Phase Power Calculator
Three-phase power triangle: line current, kW, kVA, kVAR
Ampacity Chart
NEC 310.16 copper and aluminium ampacity at 60, 75 and 90 C, with AWG to mm2
Conduit Fill Chart
How many THHN wires fit in EMT and PVC conduit, from NEC Chapter 9
Embed This Calculator
Add this free calculator to your website. Copy the code below and paste it into your page.