Select conduit type and trade size, then enter up to three THHN/THWN conductor groups. The calculator checks the fill percentage against the NEC Chapter 9 limits: 53% for one conductor, 31% for two, and 40% for three or more.
Conductor groups
Conductor areas are reference values taken from NEC Chapter 9 Tables 4 and 5. The applicable edition of the NEC governs for code compliance.
Select a conduit size and at least one conductor group to see the fill result.
NEC Chapter 9, Table 1 specifies the maximum fill as a percentage of the conduit's internal cross-sectional area:
| Number of conductors | Maximum fill |
|---|---|
| 1 conductor | 53% |
| 2 conductors | 31% |
| 3 or more conductors | 40% |
Source: NEC Chapter 9, Table 1. Always verify against the edition having jurisdiction.
The maximum number of same-size THHN/THWN conductors permitted in each trade size of conduit. Counts are computed from NEC Chapter 9 Table 4 (conduit area) and Table 5 (conductor area) against the Table 1 fill limits, so a cell showing 1 or 2 conductors uses the 53% and 31% limits rather than 40%.
| Wire size | 1/2" | 3/4" | 1" | 1-1/4" | 1-1/2" | 2" | 2-1/2" | 3" |
|---|---|---|---|---|---|---|---|---|
| 14 AWG | 12 | 21 | 35 | 61 | 83 | 138 | 241 | 364 |
| 12 AWG | 9 | 16 | 25 | 44 | 61 | 100 | 176 | 266 |
| 10 AWG | 5 | 10 | 16 | 28 | 38 | 63 | 111 | 167 |
| 8 AWG | 3 | 5 | 9 | 16 | 22 | 36 | 64 | 96 |
| 6 AWG | 1 | 4 | 6 | 11 | 16 | 26 | 46 | 69 |
| 4 AWG | 1 | 2 | 4 | 7 | 9 | 16 | 28 | 42 |
| 3 AWG | 1 | 1 | 3 | 6 | 8 | 13 | 24 | 36 |
| 2 AWG | 1 | 1 | 2 | 5 | 7 | 11 | 20 | 30 |
| 1 AWG | 1 | 1 | 1 | 3 | 5 | 8 | 15 | 22 |
| 1/0 AWG | — | 1 | 1 | 3 | 4 | 7 | 12 | 19 |
| 2/0 AWG | — | 1 | 1 | 2 | 3 | 6 | 10 | 15 |
| 3/0 AWG | — | 1 | 1 | 1 | 3 | 5 | 8 | 13 |
| 4/0 AWG | — | — | 1 | 1 | 1 | 4 | 7 | 10 |
| Wire size | 1/2" | 3/4" | 1" | 1-1/4" | 1-1/2" | 2" | 2-1/2" | 3" |
|---|---|---|---|---|---|---|---|---|
| 14 AWG | 11 | 20 | 34 | 59 | 81 | 135 | 193 | 299 |
| 12 AWG | 8 | 15 | 25 | 43 | 59 | 98 | 141 | 218 |
| 10 AWG | 5 | 9 | 15 | 27 | 37 | 62 | 89 | 137 |
| 8 AWG | 3 | 5 | 9 | 15 | 21 | 35 | 51 | 79 |
| 6 AWG | 1 | 4 | 6 | 11 | 15 | 25 | 37 | 57 |
| 4 AWG | 1 | 1 | 4 | 7 | 9 | 15 | 22 | 35 |
| 3 AWG | 1 | 1 | 3 | 5 | 8 | 13 | 19 | 29 |
| 2 AWG | 1 | 1 | 2 | 5 | 6 | 11 | 16 | 25 |
| 1 AWG | — | 1 | 1 | 3 | 5 | 8 | 12 | 18 |
| 1/0 AWG | — | 1 | 1 | 3 | 4 | 7 | 10 | 15 |
| 2/0 AWG | — | 1 | 1 | 2 | 3 | 5 | 8 | 13 |
| 3/0 AWG | — | 1 | 1 | 1 | 2 | 4 | 7 | 10 |
| 4/0 AWG | — | — | 1 | 1 | 1 | 4 | 5 | 8 |
These counts are computed from the Chapter 9 areas rather than transcribed from NEC Annex C, so a cell may occasionally land one conductor either side of the Annex C figure where rounding differs. Annex C governs where a code official is counting. Counts assume all conductors are the same size and insulation type, with no nipple allowance (a raceway 24 inches or shorter may fill to 60% under NEC Chapter 9 Note 4). Mixed conductor sizes must be worked out by total area, which is what the calculator above does. Ampacity derating under NEC 310.15(C)(1) applies once more than three current-carrying conductors share a raceway, so the count that physically fits is often more than the count you should actually pull.
Conduit fill is the ratio of the total cross-sectional area of all conductors inside the conduit to the conduit's total internal area:
The conductor areas are taken from NEC Chapter 9, Table 5 (total area including insulation). The conduit areas come from Table 4 (100% fill column). The applicable fill limit from Table 1 is then compared to the calculated fill.
Three 12 AWG THHN conductors in 1/2" EMT:
If the same conduit held 10 conductors at 12 AWG (total area 116.8 mm²), the fill would be 59.6%, exceeding the 40% limit — a FAIL that requires a larger conduit.
The NEC (Chapter 9, Table 1) sets three limits: 53% of the conduit internal area for a single conductor, 31% for two conductors, and 40% for three or more conductors. The lower two-conductor limit exists because two round conductors wedge against each other less efficiently than three or more, which can rotate to pack more freely.
Count every current-carrying conductor plus the equipment grounding conductor (EGC) that runs inside the conduit. Neutral conductors are counted. Equipment bonding jumpers (EBJs) outside the conduit and conductors in separate raceways do not count. When conductors of different sizes are mixed, add each individual conductor's cross-sectional area (from NEC Table 5) and compare the total to the conduit's internal area.
THHN stands for Thermoplastic High Heat-resistant Nylon-coated. It is the most widely used building wire in the US for conductors pulled through conduit, rated 90 degC dry and 75 degC wet (as THWN-2). Its thin, slippery nylon jacket makes it easy to pull and gives it a small cross-sectional area relative to its current rating, which helps conduit fill.
Exceeding the fill limit makes conductors difficult or impossible to pull without damaging the insulation, and it traps heat generated by current flow. Heat build-up reduces conductor ampacity, which is why the NEC ampacity tables already derate conductors in conduit. Staying within fill limits keeps pulling practical and prevents additional derating beyond what the tables already account for.
EMT (Electrical Metallic Tubing) is lightweight, easily bent, and is the standard choice for most interior exposed or concealed work in commercial and residential buildings. PVC Schedule 40 is used where corrosion or moisture is a concern, in underground runs, and where metal is prohibited. PVC has slightly different internal areas to EMT at some trade sizes, so always use the correct column in NEC Table 4 for your conduit type.
Continue with these related electrical tools
Add this free calculator to your website. Copy the code below and paste it into your page.
Fast, free calculators for electricians and engineers
© 2026 Electrical Calculators. All rights reserved.