Conduit Fill Calculator
Select conduit type and trade size, then enter up to three THHN/THWN conductor groups. The calculator checks the fill percentage against the NEC Chapter 9 limits: 53% for one conductor, 31% for two, and 40% for three or more.
Conductor groups
Conductor areas are reference values taken from NEC Chapter 9 Tables 4 and 5. The applicable edition of the NEC governs for code compliance.
Select a conduit size and at least one conductor group to see the fill result.
Free download
Get the printable wire size charts
NEC 310.16 ampacity for copper and aluminium at 60, 75 and 90 C, how far each size runs before voltage drop bites, standard breaker sizes and AWG to mm2. Three pages, made for the van door.
NEC Fill Percentage Limits
NEC Chapter 9, Table 1 specifies the maximum fill as a percentage of the conduit's internal cross-sectional area:
| Number of conductors | Maximum fill |
|---|---|
| 1 conductor | 53% |
| 2 conductors | 31% |
| 3 or more conductors | 40% |
Source: NEC Chapter 9, Table 1. Always verify against the edition having jurisdiction.
Conduit fill chart for same-size wires
If every wire is the same size you can skip the sum. The conduit fill chart lists the most THHN/THWN conductors, 14 AWG to 4/0, in each trade size of EMT and PVC Schedule 40, with the Chapter 9 areas and a print layout.
How It Works
The fill percentage formula
Conduit fill is the ratio of the total cross-sectional area of all conductors inside the conduit to the conduit's total internal area:
The conductor areas are taken from NEC Chapter 9, Table 5 (total area including insulation). The conduit areas come from Table 4 (100% fill column). The applicable fill limit from Table 1 is then compared to the calculated fill.
Worked example
Three 12 AWG THHN conductors in 1/2" EMT:
- Conduit internal area (1/2" EMT, Table 4): 196.1 mm²
- Conductor area (12 AWG THHN, Table 5): 8.581 mm² each
- Total wire area: 3 × 8.581 = 25.74 mm²
- Fill: 25.74 ÷ 196.1 × 100 = 13.1%
- Limit (3 conductors): 40%, so the result is a PASS
If the same conduit held 10 conductors at 12 AWG THHN (total area 85.81 mm²), the fill would be 43.8%, over the 40% limit: a FAIL that requires a larger conduit.
Frequently Asked Questions
What are the NEC conduit fill percentage limits?
The NEC (Chapter 9, Table 1) sets three limits: 53% of the conduit internal area for a single conductor, 31% for two conductors, and 40% for three or more conductors. The lower two-conductor limit exists because two round conductors wedge against each other less efficiently than three or more, which can rotate to pack more freely. When every conductor is the same size, Chapter 9 Note 7 lets you round the count up if the division leaves a decimal of 0.8 or more, so 22 conductors of 14 AWG THHN are allowed in 3/4 inch EMT even though the exact fill is 40.03%; mixed sizes are judged on the plain percentage.
How do I count conductors for conduit fill?
Count every current-carrying conductor plus the equipment grounding conductor (EGC) that runs inside the conduit. Neutral conductors are counted. Equipment bonding jumpers (EBJs) outside the conduit and conductors in separate raceways do not count. When conductors of different sizes are mixed, add each individual conductor's cross-sectional area (from NEC Table 5) and compare the total to the conduit's internal area.
What is THHN insulation and why is it common?
THHN stands for Thermoplastic High Heat-resistant Nylon-coated. It is the most widely used building wire in the US for conductors pulled through conduit, rated 90 degC dry and 75 degC wet (as THWN-2). Its thin, slippery nylon jacket makes it easy to pull and gives it a small cross-sectional area relative to its current rating, which helps conduit fill.
Why does conduit fill matter?
Exceeding the fill limit makes conductors difficult or impossible to pull without damaging the insulation, and it traps heat generated by current flow. Heat build-up reduces conductor ampacity, which is why the NEC ampacity tables already derate conductors in conduit. Staying within fill limits keeps pulling practical and prevents additional derating beyond what the tables already account for.
When should I choose EMT versus PVC conduit?
EMT (Electrical Metallic Tubing) is lightweight, easily bent, and is the standard choice for most interior exposed or concealed work in commercial and residential buildings. PVC Schedule 40 is used where corrosion or moisture is a concern, in underground runs, and where metal is prohibited. PVC has slightly different internal areas to EMT at some trade sizes, so always use the correct column in NEC Table 4 for your conduit type.
Related Calculators
Continue with these related electrical tools
Conduit Fill Chart
How many THHN wires fit in EMT and PVC conduit, from NEC Chapter 9
Wire Size Calculator
Smallest conductor that meets ampacity and the voltage-drop limit (AWG/mm2)
Wire Gauge Chart
AWG sizes 4/0 to 40 with diameter, area, resistance and copper amps
AWG Conversion Calculator
Convert AWG to mm2, circular mils, kcmil and diameter
Voltage Drop Calculator
Voltage drop over a run by length, current and conductor (AWG/mm2, 1ph/3ph/DC)
Embed This Calculator
Add this free calculator to your website. Copy the code below and paste it into your page.