Wire Size Calculator
Find the smallest copper or aluminium conductor that both carries the load current and keeps voltage drop within your limit. Pick a use-case preset or enter the circuit yourself. Sizes in AWG or mm2 for single-phase, three-phase and DC.
Free download
Get the printable wire size charts
NEC 310.16 ampacity for copper and aluminium at 60, 75 and 90 C, how far each size runs before voltage drop bites, standard breaker sizes and AWG to mm2. Three pages, made for the van door.
How It Works
Two limits, take the larger
A conductor must satisfy two independent requirements, and the correct size is the larger of the two:
- Ampacity: the conductor must be rated to carry the load current at the chosen termination temperature (60, 75 or 90°C).
- Voltage drop: over the run length, the drop must stay within your limit (commonly 3% on a branch circuit, 5% total).
On short, high-current runs ampacity usually wins. On long runs the voltage-drop limit forces a larger conductor than ampacity alone would need.
Continuous loads: the 125% step
A continuous load runs at its full current for three hours or more. NEC 210.19(A)(1) requires the conductor feeding one to carry 125% of that current, and NEC 625.42 treats EV charging as continuous by definition. Tick Continuous load, or pick the EV charger or solar preset, and the calculator sizes the conductor for 125% of the current you enter. It still works out voltage drop at the current you enter. For a solar PV circuit, enter the maximum circuit current from NEC 690.8(A), which for a PV source circuit is already 125% of the modules' short-circuit current; the Continuous load box then applies the second 125% that 690.8(B)(1) requires. Voltage drop uses that maximum current as well, which errs on the safe side.
Worked example
A 48 A EV charger at 240 V over 50 ft of copper. The charger is a continuous load, so the conductor has to carry 48 × 1.25 = 60 A, which is also the rating of the circuit it sits on. At the 75°C column, which the calculator opens on, 6 AWG carries 65 A and holds voltage drop under 1% at 48 A, so 6 AWG is the pick, set by ampacity. NM cable is held to the 60°C column, where 6 AWG carries only 55 A, so an NM cable run needs 4 AWG (70 A); the result shows that size as well. Sizing to the bare 48 A would return 8 AWG, which is too small for a 60 A circuit. The EV charger wire and breaker guide has every common charger size.
Ampacities are reference values for not more than three current-carrying conductors in a standard installation. They do not include ambient-temperature or conductor-bundling derating, and local wiring rules take precedence. Verify against the applicable standard.
The ampacities here are NEC Table 310.16. A UK or Australian cable is sized by installation method under BS 7671 Appendix 4 or AS/NZS 3008, and the answer can differ by a size or more: the NEC vs BS 7671 vs AS/NZS 3008 comparison works one 32 A circuit through all three.
Frequently Asked Questions
How do I choose a wire size?
Size for ampacity first (the conductor must carry the current), then check voltage drop over the run. Use whichever requirement calls for the larger conductor.
What does the termination rating mean?
Terminations are rated 60, 75 or 90°C. You generally size ampacity from the lowest-rated component in the circuit, most often the 75°C column.
Why does a long run need a bigger wire?
Voltage drop grows with length. On a long run the drop can exceed the limit even when the conductor easily carries the current, so a larger size is needed.
Copper or aluminium?
Aluminium has lower ampacity and higher resistance for a given size, so an aluminium conductor is usually one to two sizes larger than copper for the same job.
Does this include derating?
No. The ampacities are base values for a standard installation. Apply ambient-temperature and bundling derating factors separately, and follow your local wiring rules.
Wire size by breaker rating
Already know the circuit rating? These pages give the answer straight out, with the 60/75/90°C table and the maximum run length before voltage drop bites.
Wire size by appliance
Starting from what you are wiring rather than the breaker? These pages carry the typical circuit, the copper and aluminium answer, the run limits and the NEC articles that apply to that particular job.
Related Calculators
Continue with these related electrical tools
Voltage Drop Calculator
Voltage drop over a run by length, current and conductor (AWG/mm2, 1ph/3ph/DC)
Ampacity Chart
NEC 310.16 copper and aluminium ampacity at 60, 75 and 90 C, with AWG to mm2
Wire Gauge Chart
AWG sizes 4/0 to 40 with diameter, area, resistance and copper amps
Conduit Fill Chart
How many THHN wires fit in EMT and PVC conduit, from NEC Chapter 9
AWG Conversion Calculator
Convert AWG to mm2, circular mils, kcmil and diameter
Watts Amps Volts Calculator
Convert between watts, volts and amps (DC, 1-phase, 3-phase)
Ohm's Law Calculator
Solve voltage, current, resistance and power from any two
Embed This Calculator
Add this free calculator to your website. Copy the code below and paste it into your page.