AWG Conversion Calculator
Convert American Wire Gauge to and from square millimetres, circular mils, kcmil and conductor diameter. Enter a value in any unit to see all the others, plus the nearest standard gauge.
For AWG, enter a gauge such as 10 or 4/0.
Free download
Get the printable wire size charts
NEC 310.16 ampacity for copper and aluminium at 60, 75 and 90 C, how far each size runs before voltage drop bites, standard breaker sizes and AWG to mm2. Three pages, made for the van door.
How It Works
The AWG formula
American Wire Gauge is geometric. The conductor diameter for gauge n is:
diameter (in) = 0.005 × 92(36 - n) / 39
Gauges 1/0 to 4/0 use n = 0, -1, -2, -3. The cross-sectional area in circular mils is the diameter in mils squared, and 1 circular mil is 5.067 × 10-4 mm².
Worked example
10 AWG: diameter = 0.005 × 9226/39 ≈ 0.1019 in (2.59 mm), which is 101.9² ≈ 10,380 circular mils, or about 5.26 mm².
AWG sizes at a glance: area and ampacity
Each AWG size with its metric area, circular mils, conductor diameter, and the allowable ampacity of copper and aluminium at 60, 75 and 90°C terminations.
| AWG | mm² | Circular mils | Diameter (mm) | Copper ampacity (A) | Aluminium ampacity (A) | ||||
|---|---|---|---|---|---|---|---|---|---|
| 60°C | 75°C | 90°C | 60°C | 75°C | 90°C | ||||
| 14 | 2.081 | 4,107 | 1.628 | 15 | 20 | 25 | - | - | - |
| 12 | 3.309 | 6,530 | 2.053 | 20 | 25 | 30 | 15 | 20 | 25 |
| 10 | 5.261 | 10,380 | 2.588 | 30 | 35 | 40 | 25 | 30 | 35 |
| 8 | 8.365 | 16,510 | 3.264 | 40 | 50 | 55 | 35 | 40 | 45 |
| 6 | 13.30 | 26,250 | 4.115 | 55 | 65 | 75 | 40 | 50 | 55 |
| 4 | 21.15 | 41,740 | 5.189 | 70 | 85 | 95 | 55 | 65 | 75 |
| 3 | 26.67 | 52,630 | 5.827 | 85 | 100 | 115 | 65 | 75 | 85 |
| 2 | 33.63 | 66,370 | 6.544 | 95 | 115 | 130 | 75 | 90 | 100 |
| 1 | 42.41 | 83,690 | 7.348 | 110 | 130 | 145 | 85 | 100 | 115 |
| 1/0 | 53.47 | 105,500 | 8.251 | 125 | 150 | 170 | 100 | 120 | 135 |
| 2/0 | 67.43 | 133,100 | 9.266 | 145 | 175 | 195 | 115 | 135 | 150 |
| 3/0 | 85.03 | 167,800 | 10.40 | 165 | 200 | 225 | 130 | 155 | 175 |
| 4/0 | 107.2 | 211,600 | 11.68 | 195 | 230 | 260 | 150 | 180 | 205 |
Ampacities are NEC 310.16 values for not more than three current-carrying conductors in a raceway at 30°C ambient, before any derating. The 14 AWG aluminium cells are blank because 2023 NEC 310.3(A) makes 12 AWG the smallest aluminium conductor. Areas are nominal solid-conductor values; stranded conductors of the same AWG have a slightly larger overall diameter. To size a conductor for a specific load, use the wire size calculator. For all 44 sizes from 4/0 to 40 AWG with resistance, see the wire gauge chart.
Frequently Asked Questions
How do I convert AWG to mm²?
Find the conductor diameter from the AWG formula, square it to get circular mils, then multiply by 0.0005067 to get mm². For example 10 AWG is about 5.26 mm².
What is a circular mil?
A circular mil is the area of a circle one mil (0.001 in) in diameter. The area of a round conductor in circular mils is simply its diameter in mils, squared.
What does 4/0 mean?
Sizes larger than 1 AWG are written 1/0, 2/0, 3/0 and 4/0 (spoken "one aught" to "four aught"). Above 4/0, conductors are sized in kcmil instead.
Why does a smaller AWG number mean a bigger wire?
AWG counts drawing steps: each step down in gauge number is a larger diameter. So 10 AWG is bigger than 14 AWG.
How is kcmil related to AWG?
kcmil is thousands of circular mils, used for conductors larger than 4/0. For example 250 kcmil is just larger than 4/0 (about 212 kcmil).