How to Read a Motor Nameplate (NEMA and IEC)

Published 17 September 2026

The motor FLA calculator estimates full-load current from horsepower when the motor is still on a datasheet. Once the machine is in front of you, the NEMA or IEC nameplate is the document. NEC Article 430 then tells you which field is for the conductors and which is for the overload. Using the wrong one is how a starter trips on a cold morning or a conductor is sized to a current the windings never see.

The short version. Conductors and the branch-circuit breaker are sized from the NEC table FLA (430.247 to 430.250), not from the nameplate, even when the plate reads lower (430.6(A)(1)). Overload protection is sized from the nameplate FLA (430.32). Service factor amps are not a licence to run hotter on a smaller circuit. Locked-rotor amps (or the code letter) size the starter and tell you whether the breaker will ride through a start. This is a planning aid, not a design sign-off.

The fields that actually change the circuit

HP or kW

Shaft output, not electrical input. 1 HP is 746 W of mechanical power. Electrical input is higher by the inverse of efficiency: a 10 HP motor at 90% efficiency draws about 8.3 kW from the supply, not 7.46 kW. IEC plates in kW (7.5 kW is the common 10 HP cousin) are the same idea in metric.

Volts, and the dual-voltage slash

A plate that reads 230/460 V is one motor with two windings. At 230 V the windings are in parallel and the current is twice the 460 V figure. Connecting a dual-voltage motor on the low voltage without doubling the expected FLA is a classic undersize. Frequency matters too: a 60 Hz motor on 50 Hz, or the reverse, is not the same machine. The plate is only valid on the system it names.

FLA, FLC, A

Full-load amperes at rated voltage, rated frequency, rated horsepower. This is the current at which the motor delivers its nameplate power without using the service factor. It is the number for overloads. It is not, under the NEC, the number for the branch-circuit conductors or the short-circuit device. Those come from the tables, which are deliberately a little conservative so a replacement motor of the same HP still fits the circuit.

If the plate is missing or painted over, the motor FLA calculator will reconstruct a current from HP, volts, phase, power factor and efficiency. Treat that as a check, then confirm against Table 430.248 or 430.250 before you buy cable.

SF and SF amps

Service factor is how much above rated horsepower the motor can run without immediate damage, typically 1.15 or 1.25 on NEMA machines, 1.0 on many IEC machines. SF amps are the current at that overload. They are a thermal rating of the motor, not a new FLA for the circuit. You do not size the conductor to SF amps, and you do not set the overload to SF amps unless the motor is actually applied at the service factor and the manufacturer says so. A 1.15 SF is margin for a dirty filter and a hot day, not a 15% free upgrade.

LRA and the code letter

Locked-rotor amps are the current with the shaft held still, which is the first cycle of every start. If the plate omits LRA it will give a NEMA code letter (A through V). Code letter times HP gives locked-rotor kVA; divide by (kV × √3) for three-phase amps. A Code G 10 HP motor at 460 V has a much gentler start than a Code K. That number sizes the starter, sets whether a 250% breaker in 430.52 will hold, and is why a "correct" 20 A breaker on a small motor still trips when the load is stuck.

Phase, RPM, design letter, duty

Phase tells you which FLA table to open (430.247 DC, 430.248 single-phase, 430.250 three-phase). RPM plus poles tells you whether you are looking at a 2-pole 3,000 / 3,600 rpm machine or a 4-pole 1,500 / 1,800 rpm one; starting current and inertia differ. NEMA design letter (A, B, C, D) is the torque-speed curve: Design B is the default, Design C and D are high-starting-torque machines that draw differently. Duty (S1 continuous, S3 intermittent, and the rest of the IEC cycle) tells you whether 430's continuous assumptions even apply.

Efficiency, PF, insulation class, frame, enclosure

Efficiency and power factor are what the FLA calculator needs if you are reconstructing current from HP. Insulation class (B, F, H) is the winding temperature limit; a Class F motor on a Class B rise is how manufacturers build thermal margin. Frame (NEMA 56, 184T, IEC 90L) is the mechanical swap, not an electrical one. Enclosure (TEFC, ODP, TENV) changes cooling and therefore how much service factor you actually have in a hot plant room. None of these replace FLA for the circuit, but they tell you whether the motor you are about to hang on an existing starter is the same animal.

NEC 430.6: table for the circuit, plate for the overload

This is the rule that feels backwards until a motor is swapped. NEC 430.6(A)(1) says conductors and short-circuit / ground-fault protection are sized from Tables 430.247 to 430.250, using the HP and voltage, not from the nameplate current. 430.32 says overload protection is sized from the nameplate FLA. Two currents, printed two inches apart, for two devices on the same motor.

The table is usually a little higher than a modern high-efficiency plate. That is the point. The circuit has to accept a replacement motor of the same HP whose FLA might be worse. The overload has to protect this winding, so it follows the plate.

Worked example: 10 HP, 460 V, three-phase

Plate: 10 HP, 460 V, 3 ph, 60 Hz, FLA 12.4 A, SF 1.15, SF amps 14.2 A, Code G, Design B, Nom. Eff. 91.7%, PF 0.84, TEFC.

  • Table 430.250 FLA for 10 HP at 460 V: 14 A (use this, not 12.4 A, for the conductors and the breaker)
  • Conductors: 14 A × 125% (430.22) = 17.5 A → 12 AWG copper is typical once termination temperature is checked
  • Inverse-time breaker (430.52): 14 A × 250% = 35 A → 35 A standard size
  • Overload (430.32, service factor 1.15): 12.4 A × 125% = 15.5 A heaters, not 14.2 A SF amps
  • Calculator check: 10 × 746 / (√3 × 460 × 0.84 × 0.917) ≈ 12.1 A, which matches the plate and is still not the table value

If you had sized the breaker to 12.4 × 1.25 = 15.5 A you would have a 20 A breaker that nuisance-trips on start. If you had sized the overload to table 14 A you would have allowed more current than the winding is listed for. Both mistakes come from using one number twice. The breaker guide covers the 250% path; this page is why the 12.4 A and the 14 A both appear.

On a pump, shaft power is not on the motor plate until someone has chosen the motor. Start from flow and head on the pump power calculator, then come back here with a HP, then confirm FLA.

Star / delta, 50 Hz plates, and other traps

A six-terminal IEC motor marked 230/400 V is star on 400 V three-phase and delta on 230 V three-phase. The FLA on the plate is usually given for both. Connecting delta on a 400 V supply puts twice the intended voltage on each winding.

A motor rated 380 V 50 Hz will draw more current and run hotter on 480 V 60 Hz than the plate suggests, and the speed will be 20% high. Do not treat "it spun" as a successful install.

VFD-rated plates add a turndown, a PWM voltage class and sometimes a separate FLA for inverter duty. The branch circuit is still sized from Article 430 (or 430.122 for the VFD input), not from the motor FLA alone. The VFD nameplate current is the one that sizes the line-side conductors.

NEC table values in the example are the familiar published figures for that HP and voltage; always check the edition adopted in your jurisdiction. Nameplate fields vary by manufacturer. When the plate and the table disagree, Article 430.6 already tells you which one wins for which device.

Frequently Asked Questions

Is nameplate FLA the number I put in the FLA calculator?

No. The calculator estimates FLA from HP when you do not have a plate. When you do have a plate, read it. For NEC conductor and breaker sizing, then go to Tables 430.247 to 430.250 using HP and voltage, which may be higher than both the plate and the calculator.

What is the difference between FLA and SF amps?

FLA is current at rated horsepower. SF amps is current at the service-factor overload. Overloads are set from FLA (430.32). SF amps tell you the motor can survive a short period above rating; they do not enlarge the circuit.

Why is table FLA higher than my high-efficiency motor's plate?

Because 430.6 wants the circuit to accept a replacement motor of the same horsepower. The table is a conservative HP-to-current conversion, not a measurement of your windings. The overload, not the breaker, tracks the efficient plate.

How do I find locked-rotor amps from the code letter?

NEC Table 430.7(B) gives kVA per horsepower for each code letter. Locked-rotor kVA = kVA/HP × HP. For three-phase, LRA = (kVA × 1,000) / (V × √3). Code G is a moderate start; letters later in the alphabet are harsher.

Can I use the 230 V FLA on a 208 V supply?

Not without checking. A 230 V motor on 208 V draws more current for the same shaft power, runs hotter, and may not develop rated torque. Some plates list 208 V FLA separately (it will be higher). If they do not, you need the manufacturer, not a 230/208 ratio on the back of an envelope.

Recommended gear

Links are Amazon affiliate links (tag: sispn-20). Prices and availability are set by the retailer.

1

Clamp meter with inrush

Compare running current to FLA and capture LRA on start, which a plain average-sensing meter will miss.

View on Amazon.com
2

Motor overload relay / heater pack

Sized to nameplate FLA, not to table FLA. Match the starter series.

View on Amazon.com
3

Nameplate photo, before you paint

A phone camera is the cheapest insurance on a motor whose plate will be covered in paint next shutdown. No affiliate link; take the picture.