What Size Cable for 32 Amp? NEC vs BS 7671 vs AS/NZS 3008

Published 17 September 2026

A 32 A circuit is not a 32 A cable, and a 6 mm2 twin-and-earth is not "about 8 AWG". Under BS 7671 a 6 mm cable clipped direct is typically good for a 32 A radial; 4 mm is the next size down and is often too tight once it is in insulation. The same 32 A continuous load is a 40 A circuit on 8 AWG in the NEC. This page is why those answers diverge, with the 4 mm / 6 mm / 10 mm ratings people actually search.

The short version. NEC assumes 30 °C air and then applies 125% to continuous loads, so a 32 A continuous circuit is really a 40 A circuit on 8 AWG copper. BS 7671 does not apply that 125%; it derates the cable for grouping, insulation and method until Iz is at least In, so the same 32 A radial is often 6 mm2 twin-and-earth. AS/NZS 3008 commonly tables current at 40 °C, which is already a hotter starting point than NEC, so 4 mm2 that looks fine on a US chart is often not the Australian answer. Use the code that applies where the cable will be installed. This is a planning comparison, not a design sign-off.

4 mm, 6 mm and 10 mm amp ratings (UK, typical Method C)

These are the clipped-direct (Method C) ballpark figures for thermoplastic twin-and-earth that show up on every UK "6mm cable amp rating" chart. Buried in insulation, grouped, or run in a hot loft, they fall. 4 mm at about 37 A can cover a 32 A radial only while those derates stay friendly; 6 mm at about 47 A is the usual 32 A answer; 10 mm at about 64 A is what people reach for when the 32 A run is long or buried.

Cable Approx Iz, Method C Typical MCB US cousin (not equivalent)
2.5 mm227 A20 A ring / 16-20 A radialClose to 14 AWG area, used unlike 14 AWG
4 mm237 A32 A only if method and grouping allowBetween 12 and 10 AWG
6 mm247 A32 A radial, many cooker circuitsBetween 10 and 8 AWG
10 mm264 A40-50 A, long 32 A runsClose to 8 AWG area

Three documents, three jobs

People treat these as interchangeable ampacity tables. They are not even the same kind of document.

  • NEC (NFPA 70), Article 310 and 240. Allowable ampacity in Table 310.16 is for not more than three current-carrying conductors in raceway, cable or earth, at 30 °C ambient. Overcurrent protection is a separate article. Voltage drop is an informational note, not a mandatory limit.
  • BS 7671 (IET Wiring Regulations). Current-carrying capacity lives in Appendix 4, tabulated by installation method (clipped direct, in conduit, in insulation, buried). The protective device rating In must not exceed the derated cable rating Iz. Voltage drop in Appendix 4 is a design limit in ordinary use: 3% for lighting, 5% for other uses.
  • AS/NZS 3008.1. This is the cable selection standard, used with AS/NZS 3000 (the Wiring Rules). Tables are built around Australian installation methods and, in many columns, a 40 °C air temperature. Voltage drop is handled in AS/NZS 3000 and in 3008 as a design check, commonly 5% origin to load.

The wire size calculator on this site is NEC-based, with metric labels as a convenience. It will not spit out a BS 7671 or AS/NZS 3008 design current. That is deliberate: mixing the tables is how a 4 mm2 "equivalent" gets pulled into a 40 °C roof space.

Five reasons the answers diverge

1. Ambient temperature

NEC 310.16 is a 30 °C table. Walk into a US attic in July and you derate from there using 310.15(B). Many AS/NZS 3008 columns already start at 40 °C, which is closer to an Australian roof void on a normal summer day. A cable that carries 32 A at 30 °C may be below 32 A at 40 °C before anyone has bundled it. That single assumption is why an AWG-to-mm2 chart lies.

2. Continuous load

NEC 210.20(A) multiplies a three-hour load by 1.25 before you touch the ampacity table. A 32 A EV charger is therefore a 40 A circuit. BS 7671 has no equivalent blanket 125%. You size In to the design current and check that Iz, after all correction factors, is still at least In. AS/NZS practice follows the Wiring Rules and the equipment standard; it does not import NEC 210.20. Apply 125% on a UK radial and you will oversize the protective device relative to the cable you just selected.

The breaker decision itself is in what size breaker do I need.

3. Installation method, not insulation colour

NEC ampacity is mostly a function of conductor metal, size and termination temperature (60 / 75 / 90 °C columns), then derating for bundling and ambient. BS 7671 Appendix 4 is built the other way: Method A (in a wall), Method B (in conduit on a wall), Method C (clipped direct), Method D (buried), Method 100 and 103 (in insulation) each have their own current for the same 4 mm2 or 6 mm2 twin-and-earth. A 2.5 mm2 T&E that carries 27 A clipped direct is a 20 A or 16 A cable once it is buried in insulation. AS/NZS 3008 is similarly method-driven. You cannot read a current off a size without naming the method.

4. Voltage drop is mandatory in one place and a note in another

NEC informational notes to 210.19 and 215.2 recommend 3% on a feeder or branch and 5% overall. They are not enforceable by themselves. BS 7671 Appendix 4 treats 3% (lighting) and 5% (other) as the design target in normal conditions. AS/NZS 3000 typically works to 5% from the origin of the installation to the load, with tighter figures on extra-low voltage. On a long run the "code minimum" conductor is often too small in the UK and Australia even when it is legal for ampacity in the US. Check the number with the voltage drop calculator; the physics do not care which book you opened.

5. You cannot buy the equivalent size

8 AWG copper is 8.37 mm2. The next metric sizes on a reel in the UK or Australia are 6 mm2 and 10 mm2. There is no 8.37 mm2 T&E. The AWG conversion calculator is useful for identifying a conductor; it is not a permission to install 6 mm2 because it is "close to 8 AWG". After conversion you still have to pass the local table.

Worked example: 32 A, 20 m, copper, single-phase

Same load, same one-way length, three rulebooks. Figures below are the typical textbook answers for a simple two-core circuit in a 30 to 40 °C space with no grouping. Real work still needs the correction factors for that job.

Rulebook What 32 A becomes Typical copper size Why
NEC 2023, continuous 40 A circuit (32 × 1.25) 8 AWG THHN at 75 °C, or 8 AWG NM-B at 60 °C 310.16 plus 210.20(A). 8 AWG is not caught by 240.4(D).
NEC 2023, not continuous 32 A, next breaker 35 A 8 AWG at 60 °C (40 A), sometimes 10 AWG at 75 °C if every termination is 75 °C 10 AWG is capped at 30 A by 240.4(D), so a 35 A breaker still wants 8 AWG.
BS 7671, Method C clipped direct 32 A radial, In = 32 A 6 mm2 twin-and-earth (Iz about 47 A) 4 mm2 Method C is about 37 A and can work if grouping and insulation stay friendly; 6 mm2 is the usual conservative pick. 2.5 mm2 is 27 A and fails.
BS 7671, in insulation 32 A radial 10 mm2 is often the one that still has Iz ≥ 32 A Method, not millimetres, is doing the work.
AS/NZS 3008, 40 °C air 32 A 6 mm2 two-core is the common answer; 4 mm2 is often at or under 32 A once method and ambient are applied Hotter table, metric sizes, 5% voltage-drop check on the 20 m run.

Voltage drop on 20 m at 32 A is modest on 6 mm2 or 8 AWG at 230 to 240 V (around 2%). Stretch the same circuit to 40 m and drop, not ampacity, starts to pick 10 mm2 in metric countries and 6 AWG in the US. That is the same physics in all three books; only the pass mark changes.

What to do with a drawing from another country

  1. Do not convert the conductor size and install it. Convert only so you know what you are looking at.
  2. Re-establish the design current under the local load rules (125% or not).
  3. Pick a manufactured size that exists where you are buying cable.
  4. Run ampacity for the local method and ambient, then voltage drop, then the protective device.
  5. If the original drawing used MCA / MOCP from UL-listed plant, those numbers are still listing numbers; they do not become BS 7671 Iz.

The what size wire do I need guide is the walkthrough of ampacity plus drop on one circuit. This page is only the reason the three tables disagree.

Table currents here are typical published values for simple cases, rounded for comparison. They are not a substitute for the current edition of NEC, BS 7671 Appendix 4 or AS/NZS 3008.1, or for the correction factors that apply to the installation. A qualified person in the country of install signs the design off.

Frequently Asked Questions

Is 8 AWG the same as 10 mm2?

No. 8 AWG is about 8.4 mm2. 10 mm2 is the next common metric size up; 6 mm2 is the next one down. Neither is a substitute for 8 AWG without running the local table. The conversion calculator gives area, not permission.

Why is Australian cable often a size larger than a US chart suggests?

Because many AS/NZS 3008 columns already assume 40 °C, while NEC 310.16 assumes 30 °C. A hotter starting point plus metric manufactured sizes plus a 5% voltage-drop check is enough to push a 32 A circuit from "4 mm2 looks close to 12 AWG" to 6 mm2.

Does the UK use the NEC 125% continuous-load rule?

No. BS 7671 requires the protective device rating In to be no greater than the derated cable rating Iz. Long-running loads are handled by diversity, design current and those correction factors, not by multiplying every three-hour load by 1.25.

Can I use the wire size calculator on this site for a UK or Australian job?

Use it to understand voltage drop and to see the NEC answer. Do not take its AWG pick, convert it, and install that mm2 size. Re-run the circuit in Appendix 4 or AS/NZS 3008 with the installation method you actually have.

What size cable for a 32 amp circuit?

Under the NEC, a continuous 32 A load is a 40 A circuit and typically 8 AWG copper. Under BS 7671 Method C, 6 mm2 twin-and-earth is the usual radial. Under AS/NZS 3008 at 40 °C, 6 mm2 is the common answer and 4 mm2 is often too tight. Method, ambient and length can all move those up a size.

What is the amp rating of 6mm cable?

About 47 A clipped direct (Method C) for thermoplastic twin-and-earth. That is why 6 mm is the default 32 A radial. In insulation, grouped, or in a hot loft the same cable can drop below 32 A, which is when you go to 10 mm2.

Recommended gear

Links are Amazon affiliate links (tag: sispn-20). Prices and availability are set by the retailer. Buy cable to the local standard, not to an Amazon search term from another country.

1

8 AWG THHN copper (US)

The size the NEC example above actually lands on for a 40 A continuous circuit.

View on Amazon.com
2

Wire gauge / mm2 chart

A pocket chart is fine for identification. It is not a substitute for the local ampacity table.

View on Amazon.com
3

Insulation resistance tester

After the cable is in, the test is the same in every country even if the table was not.