What Size Breaker Do I Need? Chart and 125% Rule

Published 17 September 2026

The breaker sizing calculator takes a current and returns the next standard size. This page is the chart and the decision that come first: typical household pairings, which current to enter, when to apply 125%, and when a water heater or motor nameplate already tells you not to use that current at all.

The short version. Start from the equipment nameplate, not from the wattage on the box. If the load can run for three hours or more, multiply that current by 1.25 (NEC 210.20(A)). Then pick the smallest standard rating in NEC 240.6(A) that is at least that figure. The conductor has to be able to carry the breaker, not the other way around. Motors, air conditioners and EV chargers each have their own articles. This is a planning aid, not a design sign-off.

Circuit breaker size chart (typical copper, US dwelling)

These are the pairings people actually search for. The breaker still has to protect the conductor (240.4(D) caps 14/12/10 AWG at 15/20/30 A), and a continuous load still needs the 125% step below. Do not treat this as a substitute for the nameplate on the machine you are feeding.

Breaker Typical copper wire Typical use Continuous load ceiling (80%)
15 A14 AWGLighting, general outlets12 A
20 A12 AWGKitchen, bathroom, small water heater if non-continuous16 A
30 A10 AWGDryer, water heater on many 240 V listings24 A
40 A8 AWGCooktop, 32 A EVSE circuit rating32 A
50 A8 or 6 AWGRange, 32 A EVSE where next-size-up is used40 A
60 A6 AWG48 A EVSE, small sub-panel48 A

"What size breaker for a water heater" is the highest-volume phrasing of this question in US search. A typical 4,500 W, 240 V heater is 18.75 A. Many listings and AHJs put that on a 30 A two-pole breaker with 10 AWG. If your jurisdiction treats the heater as continuous (three hours), 18.75 × 1.25 = 23.4 A and the next standard size is 25 A, which is uncommon in dwelling panels, so 30 A is still what gets installed. Read the water-heater nameplate; some 5,500 W units are a 30 A circuit only because 5,500 ÷ 240 = 22.9 A, and 22.9 × 1.25 = 28.6 A.

Start from the nameplate, not from a wattage guess

A 4,500 W water heater on 240 V is 4,500 ÷ 240 = 18.75 A. That arithmetic is fine for a resistive heater, because the nameplate current and the wattage divided by voltage are the same number. It is the wrong starting point for a motor, a heat pump or a charger. Those plates carry a full-load current, a minimum circuit ampacity (MCA) and a maximum overcurrent protection (MOCP or MOP) that already include starting current, continuous-load factors and the manufacturer's listing. Using P ÷ V on those machines undersizes the circuit and oversizes the breaker in the same job.

Read the plate. If it gives amps, use amps. If it gives MCA and MOCP, those two numbers replace this entire guide for that piece of equipment: the branch-circuit conductor is sized to MCA, the breaker is at or below MOCP, and you do not apply 125% a second time. The motor nameplate guide covers the FLA / SF / LRA fields that trip people up.

Continuous load and the 125% rule

NEC 210.20(A) and 215.3 require the overcurrent device to be rated at not less than 125% of a continuous load. A continuous load is one expected to run for three hours or more: electric heating, water heaters on a timer that stay on, lighting in a commercial space, EV charging overnight. A kettle, a welder used in bursts, a garage door motor: not continuous.

The 80% rule people quote is the same rule written backwards. A 20 A breaker may carry 16 A continuously because 16 × 1.25 = 20. You can either multiply the load by 1.25 and pick a breaker, or multiply the breaker by 0.8 and check the load. Do not do both.

The 125% factor is a US NEC construction. BS 7671 sizes the protective device to the circuit current after cable derating (In ≤ Iz) and does not apply a blanket 1.25 to every long-running load. If you are working to UK or Australian rules, do not import this multiplier. The comparison is in the NEC vs BS 7671 vs AS/NZS 3008 guide.

Worked example: 16 A space heater, continuous

  • Nameplate current: 16 A on 240 V
  • Continuous: 16 × 1.25 = 20 A minimum device rating
  • Next standard size: 20 A
  • Conductor: 12 AWG copper at 60 °C (NEC 310.16, and 240.4(D) caps 12 AWG at 20 A)

Worked example: 4,500 W water heater, not treated as continuous in many dwellings

  • Current: 4,500 ÷ 240 = 18.75 A
  • If the AHJ treats it as non-continuous: next size is 20 A
  • If it is expected to run three hours: 18.75 × 1.25 = 23.4 A, next size 25 A
  • Either way the conductor follows the breaker, not the 18.75 A figure

That second case is why "what size breaker" is not a lookup table. The same heater is a 20 A circuit in one jurisdiction and a 25 A circuit in another. Use the breaker / fuse sizing calculator once you have decided whether the load is continuous.

Standard sizes, and the next-size-up permission

NEC 240.6(A) lists the standard ampere ratings. The ones that appear in housing and light commercial work are:

15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200

You pick the smallest of those that is at least the required rating. You do not invent a 22 A breaker.

NEC 240.4(B) then allows the next standard size above the conductor ampacity, for circuits of 800 A or less, where the conductor ampacity does not match a standard rating. That permission protects the conductor with a slightly larger breaker; it is not a licence to put 12 AWG on a 30 A breaker. 240.4(D) still caps 14, 12 and 10 AWG copper at 15, 20 and 30 A.

The conductor has to carry the breaker

A breaker is there to protect the wire. Sizing the breaker to the load and then leaving 14 AWG on a 20 A device is how insulation cooks. After you have a breaker rating, check the conductor against NEC 310.16 at the termination temperature that actually applies (110.14(C): 60 °C for most circuits 100 A or less unless every termination is listed 75 °C). The wire size calculator and the wire size guide are the other half of this decision.

Voltage drop is a third constraint. A 20 A breaker on 12 AWG is code-legal and still the wrong circuit if the run is 40 m to a shed and the tools at the far end sag. Check it with the voltage drop calculator before you buy the cable.

When 125% is the wrong rule

Motors (NEC 430)

Branch-circuit short-circuit and ground-fault protection for a motor is not 125% of FLA. NEC 430.52 allows an inverse-time breaker up to 250% of the motor's full-load current from Tables 430.247 to 430.250, so the breaker can ride through starting current. Overload protection (heaters, or the electronic overload in a starter) is a separate, tighter device sized from the nameplate FLA under 430.32, typically 115% or 125% depending on the motor. Using one number for both jobs either trips on start or fails to protect the windings.

Worked: a 10 HP, 230 V, single-phase motor. Table 430.248 gives 50 A. An inverse-time breaker may be 50 × 2.5 = 125 A. The overload is set from the nameplate FLA, which might be 46 A, not from the table. Put 50 A through the motor FLA calculator only as a check against a missing plate; the table still wins for the conductor and the breaker.

Air conditioners and heat pumps (NEC 440)

Do not calculate a breaker from compressor RLA. The nameplate MCA and MOCP already include the 125% on the compressor plus the other loads on that circuit. A 30 A MOCP on a unit whose RLA looks like 18 A is not a "big" breaker; it is the listed maximum. Going above MOCP voids the listing.

EV chargers (NEC 625)

A Level 2 EVSE is a continuous load. A 32 A charger needs a 40 A circuit rating (32 × 1.25) and, because 40 A is a standard size, a 40 A breaker if the EVSE is listed for it, or 50 A where the next-size-up rule and the manufacturer's instructions both allow it. The EV-specific walkthrough, including wire gauges, is the EV charger wire and breaker size guide.

A decision sequence that does not loop

  1. Read the nameplate. If it has MCA and MOCP, stop: those are the circuit and the breaker.
  2. If it has FLA only, decide whether the load is continuous (three hours).
  3. Required rating = FLA, or FLA × 1.25 if continuous, unless Article 430 or 440 applies.
  4. Pick the smallest 240.6(A) size that meets that rating.
  5. Size the conductor to the breaker at the correct termination column, then check voltage drop.
  6. Confirm the panel has a spare slot of the right pole count and that a load calculation still fits the service.

If the sequence ever says "fit a bigger breaker because the wire is already there", turn it around. Change the wire, or reduce the load. The breaker follows the conductor's ability to survive a fault, not the other way around.

These calculators and guides are planning aids. They are not a substitute for the adopted code in your jurisdiction, the equipment listing, or a design signed off by a qualified person. Local amendments and the AHJ win.

Frequently Asked Questions

What size breaker for a water heater?

A 4,500 W 240 V heater is 18.75 A and usually lands on a 30 A two-pole breaker with 10 AWG copper. A 3,500 W 240 V unit is 14.6 A and often fits 20 A if it is not treated as continuous. Always follow the nameplate MCA/MOCP when they are printed.

What size breaker do I need for a 20 amp load?

If the load is not continuous, a 20 A breaker. If it is continuous, 20 × 1.25 = 25 A, so a 25 A breaker, and the conductor must be rated for 25 A (typically 10 AWG copper at 60 °C, not 12 AWG). That is why a 16 A continuous load fits a 20 A breaker and a 20 A continuous load does not.

Is a 15 amp breaker OK on 14 AWG wire?

Yes, that pairing is the NEC 240.4(D) small-conductor rule: 14 AWG copper is capped at 15 A, 12 AWG at 20 A, 10 AWG at 30 A, regardless of the higher ampacity in the 90 °C column of 310.16. You may not put a 20 A breaker on 14 AWG even if the insulation is THHN.

Can I use a 30 amp breaker on 12 AWG wire?

No. 12 AWG copper is limited to 20 A by 240.4(D). A 30 A breaker on 12 AWG is a classic overload of the conductor. The next-size-up permission in 240.4(B) does not override the small-conductor caps.

Do I multiply motor FLA by 125% to size the breaker?

Not for the branch-circuit breaker. NEC 430.52 sizes that device up to 250% of table FLA so the motor can start. The 115% or 125% figure belongs on the overload relay, and that one is taken from the nameplate FLA, not from the table. Two devices, two numbers, two code articles.

What size breaker for a Level 2 EV charger?

A 32 A EVSE is a continuous load: 32 × 1.25 = 40 A, so a 40 A two-pole breaker on a 240 V circuit if the unit is listed for it. Larger 48 A units land on 60 A. Follow the EVSE instructions; some units require a specific breaker type. The long-form sizes are in the EV charger guide.

Recommended gear

Links are Amazon affiliate links (tag: sispn-20). Prices and availability are set by the retailer.

1

20 A single-pole circuit breaker

The most common branch-circuit size in a US dwelling. Match the brand to the panel.

View on Amazon.com
2

50 A two-pole breaker

Typical of a 32 A Level 2 EVSE circuit once the 125% rule is applied.

View on Amazon.com
3

Clamp meter

Confirm running current against the nameplate before you change a breaker.

View on Amazon.com