Conduit Fill Chart (NEC Chapter 9)
A conduit fill chart shows how many wires of one size fit in each trade size of conduit. For three or more conductors the NEC limit is 40% of the conduit's internal area, so 1/2 inch EMT holds 9 THHN conductors of 12 AWG and 3/4 inch EMT holds 16. The charts below cover EMT and PVC Schedule 40, 14 AWG to 4/0.
Maximum number of THHN/THWN wires in conduit
All the wires in the conduit are the same size. A dash means one wire of that size does not fit within the Table 1 limit.
EMT (electrical metallic tubing)
| Wire size | 1/2 in | 3/4 in | 1 in | 1-1/4 in | 1-1/2 in | 2 in | 2-1/2 in | 3 in |
|---|---|---|---|---|---|---|---|---|
| 14 AWG | 12 | 22 | 35 | 61 | 84 | 138 | 241 | 364 |
| 12 AWG | 9 | 16 | 26 | 45 | 61 | 101 | 176 | 266 |
| 10 AWG | 5 | 10 | 16 | 28 | 38 | 63 | 111 | 167 |
| 8 AWG | 3 | 6 | 9 | 16 | 22 | 36 | 64 | 96 |
| 6 AWG | 1 | 4 | 7 | 12 | 16 | 26 | 46 | 69 |
| 4 AWG | 1 | 2 | 4 | 7 | 10 | 16 | 28 | 43 |
| 3 AWG | 1 | 1 | 3 | 6 | 8 | 13 | 24 | 36 |
| 2 AWG | 1 | 1 | 3 | 5 | 7 | 11 | 20 | 30 |
| 1 AWG | 1 | 1 | 1 | 4 | 5 | 8 | 15 | 22 |
| 1/0 AWG | - | 1 | 1 | 3 | 4 | 7 | 12 | 19 |
| 2/0 AWG | - | 1 | 1 | 2 | 3 | 6 | 10 | 16 |
| 3/0 AWG | - | 1 | 1 | 1 | 3 | 5 | 8 | 13 |
| 4/0 AWG | - | - | 1 | 1 | 1 | 4 | 7 | 11 |
PVC Schedule 40
| Wire size | 1/2 in | 3/4 in | 1 in | 1-1/4 in | 1-1/2 in | 2 in | 2-1/2 in | 3 in |
|---|---|---|---|---|---|---|---|---|
| 14 AWG | 11 | 21 | 34 | 60 | 82 | 135 | 193 | 299 |
| 12 AWG | 8 | 15 | 25 | 43 | 59 | 99 | 141 | 218 |
| 10 AWG | 5 | 9 | 15 | 27 | 37 | 62 | 89 | 137 |
| 8 AWG | 3 | 5 | 9 | 16 | 21 | 36 | 51 | 79 |
| 6 AWG | 1 | 4 | 6 | 11 | 15 | 26 | 37 | 57 |
| 4 AWG | 1 | 1 | 4 | 7 | 9 | 16 | 22 | 35 |
| 3 AWG | 1 | 1 | 3 | 6 | 8 | 13 | 19 | 30 |
| 2 AWG | 1 | 1 | 3 | 5 | 7 | 11 | 16 | 25 |
| 1 AWG | - | 1 | 1 | 3 | 5 | 8 | 12 | 18 |
| 1/0 AWG | - | 1 | 1 | 3 | 4 | 7 | 10 | 15 |
| 2/0 AWG | - | 1 | 1 | 2 | 3 | 6 | 8 | 13 |
| 3/0 AWG | - | 1 | 1 | 1 | 3 | 5 | 7 | 11 |
| 4/0 AWG | - | - | 1 | 1 | 1 | 4 | 6 | 9 |
Worked out from NEC Chapter 9 Tables 1, 4 and 5 for THHN/THWN-2 insulation. Annex C is the printed version of the same calculation and governs where a cell differs by one. These counts do not include any ampacity derating, which starts above three current-carrying conductors.
Conduit internal area and fill limits (Table 1 and Table 4)
The area in each limit column is what the conductors may add up to, in square inches. Add up the Table 5 areas of your wires and compare.
| Conduit | Trade size | Total area (in²) | Total area (mm²) | 53% (1 wire) | 31% (2 wires) | 40% (3 or more) |
|---|---|---|---|---|---|---|
| EMT | 1/2 in | 0.304 | 196.1 | 0.161 | 0.094 | 0.122 |
| EMT | 3/4 in | 0.533 | 343.9 | 0.283 | 0.165 | 0.213 |
| EMT | 1 in | 0.864 | 557.4 | 0.458 | 0.268 | 0.346 |
| EMT | 1-1/4 in | 1.496 | 965.2 | 0.793 | 0.464 | 0.598 |
| EMT | 1-1/2 in | 2.036 | 1,313.5 | 1.079 | 0.631 | 0.814 |
| EMT | 2 in | 3.356 | 2,165.2 | 1.779 | 1.040 | 1.342 |
| EMT | 2-1/2 in | 5.858 | 3,779.3 | 3.105 | 1.816 | 2.343 |
| EMT | 3 in | 8.846 | 5,707.1 | 4.688 | 2.742 | 3.538 |
| PVC Sch 40 | 1/2 in | 0.285 | 183.9 | 0.151 | 0.088 | 0.114 |
| PVC Sch 40 | 3/4 in | 0.508 | 327.7 | 0.269 | 0.157 | 0.203 |
| PVC Sch 40 | 1 in | 0.832 | 536.8 | 0.441 | 0.258 | 0.333 |
| PVC Sch 40 | 1-1/4 in | 1.453 | 937.4 | 0.770 | 0.450 | 0.581 |
| PVC Sch 40 | 1-1/2 in | 1.986 | 1,281.3 | 1.053 | 0.616 | 0.794 |
| PVC Sch 40 | 2 in | 3.291 | 2,123.2 | 1.744 | 1.020 | 1.316 |
| PVC Sch 40 | 2-1/2 in | 4.695 | 3,029.0 | 2.488 | 1.455 | 1.878 |
| PVC Sch 40 | 3 in | 7.268 | 4,689.0 | 3.852 | 2.253 | 2.907 |
THHN/THWN conductor area (Table 5)
Total area including insulation. These are the THHN/THWN figures, which are smaller than the TW and THW ones, so do not use them for those wires.
| Wire size | Area (in²) | Area (mm²) |
|---|---|---|
| 14 AWG | 0.0097 | 6.258 |
| 12 AWG | 0.0133 | 8.581 |
| 10 AWG | 0.0211 | 13.613 |
| 8 AWG | 0.0366 | 23.613 |
| 6 AWG | 0.0507 | 32.710 |
| 4 AWG | 0.0824 | 53.161 |
| 3 AWG | 0.0973 | 62.774 |
| 2 AWG | 0.1158 | 74.710 |
| 1 AWG | 0.1562 | 100.774 |
| 1/0 AWG | 0.1855 | 119.677 |
| 2/0 AWG | 0.2223 | 143.419 |
| 3/0 AWG | 0.2679 | 172.838 |
| 4/0 AWG | 0.3237 | 208.838 |
Free download
Get the printable wire size charts
NEC 310.16 ampacity for copper and aluminium at 60, 75 and 90 C, how far each size runs before voltage drop bites, standard breaker sizes and AWG to mm2. Three pages, made for the van door.
How to read the conduit fill chart
- Count every conductor that will share the conduit, including neutrals and the equipment grounding conductor.
- If all the wires are one size, read the count straight from the first two charts. If the sizes are mixed, add up their Table 5 areas.
- Compare that total with the limit column for your conduit: 53% for one wire, 31% for two, 40% for three or more.
- If the total is over the limit, go up a trade size or split the wires between two conduits.
Worked example: three 10 AWG and a 12 AWG ground in 1/2 inch EMT
- Wire area: 3 × 13.613 + 8.581 = 49.42 mm².
- Conduit area: 196.1 mm².
- Fill: 49.42 ÷ 196.1 = 25.2%. Four conductors are allowed 40%, so this passes.
The conduit fill calculator does the same sum for up to three groups of wires. For the wire itself, the wire gauge chart gives diameters and areas, and the wire size calculator picks the gauge for your load and run length.
What this chart leaves out
It covers EMT and PVC Schedule 40 from 1/2 to 3 inch and THHN/THWN from 14 AWG to 4/0. Rigid metal, IMC, PVC Schedule 80, flexible conduit, larger trade sizes and kcmil conductors have different Table 4 areas, so use Annex C for those.
Frequently Asked Questions
How many 12 AWG wires fit in 1/2 inch EMT?
9 THHN or THWN conductors of 12 AWG fit in 1/2 inch EMT at the 40% limit that applies to three or more conductors. In 3/4 inch EMT the figure is 16.
What is the maximum conduit fill percentage?
NEC Chapter 9, Table 1 allows 53% of the internal area for one conductor, 31% for two conductors and 40% for three or more. A nipple no longer than 24 inches may be filled to 60%.
Do I count the ground wire in conduit fill?
Yes. Count every conductor in the conduit, neutral and equipment grounding conductors included, and use the area of each one from Table 5. A bare grounding conductor is counted by its Table 8 area.
Why does the chart round some counts up?
When every conductor is the same size, the Chapter 9 notes to the tables say to go up to the next whole number if the division leaves a decimal of 0.8 or more. For 14 AWG THHN in 3/4 inch EMT the division gives 21.98, so the chart shows 22. The rule does not apply to mixed sizes.
Is the chart the same as NEC Annex C?
It is worked out from Chapter 9 Tables 1, 4 and 5 rather than copied from Annex C, so a cell can differ from Annex C by one conductor where the two round differently. Where they differ, Annex C and your local inspector decide.
Related Calculators
Continue with these related electrical tools
Conduit Fill Calculator
NEC conduit fill percentage by conductor size and count
Wire Gauge Chart
AWG sizes 4/0 to 40 with diameter, area, resistance and copper amps
Wire Size Calculator
Smallest conductor that meets ampacity and the voltage-drop limit (AWG/mm2)
Ampacity Chart
NEC 310.16 copper and aluminium ampacity at 60, 75 and 90 C, with AWG to mm2
Voltage Drop Calculator
Voltage drop over a run by length, current and conductor (AWG/mm2, 1ph/3ph/DC)