Conduit Fill Chart (NEC Chapter 9)

A conduit fill chart shows how many wires of one size fit in each trade size of conduit. For three or more conductors the NEC limit is 40% of the conduit's internal area, so 1/2 inch EMT holds 9 THHN conductors of 12 AWG and 3/4 inch EMT holds 16. The charts below cover EMT and PVC Schedule 40, 14 AWG to 4/0.

Maximum number of THHN/THWN wires in conduit

All the wires in the conduit are the same size. A dash means one wire of that size does not fit within the Table 1 limit.

EMT (electrical metallic tubing)

Maximum number of THHN or THWN conductors in EMT conduit by trade size and wire gauge
Wire size 1/2 in 3/4 in 1 in 1-1/4 in 1-1/2 in 2 in 2-1/2 in 3 in
14 AWG 12 22 35 61 84 138 241 364
12 AWG 9 16 26 45 61 101 176 266
10 AWG 5 10 16 28 38 63 111 167
8 AWG 3 6 9 16 22 36 64 96
6 AWG 1 4 7 12 16 26 46 69
4 AWG 1 2 4 7 10 16 28 43
3 AWG 1 1 3 6 8 13 24 36
2 AWG 1 1 3 5 7 11 20 30
1 AWG 1 1 1 4 5 8 15 22
1/0 AWG - 1 1 3 4 7 12 19
2/0 AWG - 1 1 2 3 6 10 16
3/0 AWG - 1 1 1 3 5 8 13
4/0 AWG - - 1 1 1 4 7 11

PVC Schedule 40

Maximum number of THHN or THWN conductors in PVC conduit by trade size and wire gauge
Wire size 1/2 in 3/4 in 1 in 1-1/4 in 1-1/2 in 2 in 2-1/2 in 3 in
14 AWG 11 21 34 60 82 135 193 299
12 AWG 8 15 25 43 59 99 141 218
10 AWG 5 9 15 27 37 62 89 137
8 AWG 3 5 9 16 21 36 51 79
6 AWG 1 4 6 11 15 26 37 57
4 AWG 1 1 4 7 9 16 22 35
3 AWG 1 1 3 6 8 13 19 30
2 AWG 1 1 3 5 7 11 16 25
1 AWG - 1 1 3 5 8 12 18
1/0 AWG - 1 1 3 4 7 10 15
2/0 AWG - 1 1 2 3 6 8 13
3/0 AWG - 1 1 1 3 5 7 11
4/0 AWG - - 1 1 1 4 6 9

Worked out from NEC Chapter 9 Tables 1, 4 and 5 for THHN/THWN-2 insulation. Annex C is the printed version of the same calculation and governs where a cell differs by one. These counts do not include any ampacity derating, which starts above three current-carrying conductors.

Conduit internal area and fill limits (Table 1 and Table 4)

The area in each limit column is what the conductors may add up to, in square inches. Add up the Table 5 areas of your wires and compare.

Conduit internal area and the usable area at 53, 31 and 40 percent fill
Conduit Trade size Total area (in²) Total area (mm²) 53% (1 wire) 31% (2 wires) 40% (3 or more)
EMT 1/2 in 0.304 196.1 0.161 0.094 0.122
EMT 3/4 in 0.533 343.9 0.283 0.165 0.213
EMT 1 in 0.864 557.4 0.458 0.268 0.346
EMT 1-1/4 in 1.496 965.2 0.793 0.464 0.598
EMT 1-1/2 in 2.036 1,313.5 1.079 0.631 0.814
EMT 2 in 3.356 2,165.2 1.779 1.040 1.342
EMT 2-1/2 in 5.858 3,779.3 3.105 1.816 2.343
EMT 3 in 8.846 5,707.1 4.688 2.742 3.538
PVC Sch 40 1/2 in 0.285 183.9 0.151 0.088 0.114
PVC Sch 40 3/4 in 0.508 327.7 0.269 0.157 0.203
PVC Sch 40 1 in 0.832 536.8 0.441 0.258 0.333
PVC Sch 40 1-1/4 in 1.453 937.4 0.770 0.450 0.581
PVC Sch 40 1-1/2 in 1.986 1,281.3 1.053 0.616 0.794
PVC Sch 40 2 in 3.291 2,123.2 1.744 1.020 1.316
PVC Sch 40 2-1/2 in 4.695 3,029.0 2.488 1.455 1.878
PVC Sch 40 3 in 7.268 4,689.0 3.852 2.253 2.907

THHN/THWN conductor area (Table 5)

Total area including insulation. These are the THHN/THWN figures, which are smaller than the TW and THW ones, so do not use them for those wires.

THHN and THWN conductor cross-sectional area by AWG size
Wire size Area (in²) Area (mm²)
14 AWG 0.0097 6.258
12 AWG 0.0133 8.581
10 AWG 0.0211 13.613
8 AWG 0.0366 23.613
6 AWG 0.0507 32.710
4 AWG 0.0824 53.161
3 AWG 0.0973 62.774
2 AWG 0.1158 74.710
1 AWG 0.1562 100.774
1/0 AWG 0.1855 119.677
2/0 AWG 0.2223 143.419
3/0 AWG 0.2679 172.838
4/0 AWG 0.3237 208.838

Free download

Get the printable wire size charts

NEC 310.16 ampacity for copper and aluminium at 60, 75 and 90 C, how far each size runs before voltage drop bites, standard breaker sizes and AWG to mm2. Three pages, made for the van door.

We store your email with EmailOctopus to send the charts and occasional wiring and calculator tips, nothing else. Unsubscribe any time. Privacy policy.

How to read the conduit fill chart

  1. Count every conductor that will share the conduit, including neutrals and the equipment grounding conductor.
  2. If all the wires are one size, read the count straight from the first two charts. If the sizes are mixed, add up their Table 5 areas.
  3. Compare that total with the limit column for your conduit: 53% for one wire, 31% for two, 40% for three or more.
  4. If the total is over the limit, go up a trade size or split the wires between two conduits.

Worked example: three 10 AWG and a 12 AWG ground in 1/2 inch EMT

  • Wire area: 3 × 13.613 + 8.581 = 49.42 mm².
  • Conduit area: 196.1 mm².
  • Fill: 49.42 ÷ 196.1 = 25.2%. Four conductors are allowed 40%, so this passes.

The conduit fill calculator does the same sum for up to three groups of wires. For the wire itself, the wire gauge chart gives diameters and areas, and the wire size calculator picks the gauge for your load and run length.

What this chart leaves out

It covers EMT and PVC Schedule 40 from 1/2 to 3 inch and THHN/THWN from 14 AWG to 4/0. Rigid metal, IMC, PVC Schedule 80, flexible conduit, larger trade sizes and kcmil conductors have different Table 4 areas, so use Annex C for those.

Frequently Asked Questions

How many 12 AWG wires fit in 1/2 inch EMT?

9 THHN or THWN conductors of 12 AWG fit in 1/2 inch EMT at the 40% limit that applies to three or more conductors. In 3/4 inch EMT the figure is 16.

What is the maximum conduit fill percentage?

NEC Chapter 9, Table 1 allows 53% of the internal area for one conductor, 31% for two conductors and 40% for three or more. A nipple no longer than 24 inches may be filled to 60%.

Do I count the ground wire in conduit fill?

Yes. Count every conductor in the conduit, neutral and equipment grounding conductors included, and use the area of each one from Table 5. A bare grounding conductor is counted by its Table 8 area.

Why does the chart round some counts up?

When every conductor is the same size, the Chapter 9 notes to the tables say to go up to the next whole number if the division leaves a decimal of 0.8 or more. For 14 AWG THHN in 3/4 inch EMT the division gives 21.98, so the chart shows 22. The rule does not apply to mixed sizes.

Is the chart the same as NEC Annex C?

It is worked out from Chapter 9 Tables 1, 4 and 5 rather than copied from Annex C, so a cell can differ from Annex C by one conductor where the two round differently. Where they differ, Annex C and your local inspector decide.