Wire Gauge Chart (AWG)

A wire gauge chart lists each American Wire Gauge (AWG) size with its diameter, cross-section and resistance. A smaller gauge number is a thicker wire: 10 AWG is 0.1019 in (2.588 mm) across with 5.261 mm² of copper, and 14 AWG is 0.06408 in with 2.081 mm².

AWG wire gauge chart: diameter, area and resistance

Solid copper wire, 4/0 AWG down to 40 AWG. Resistance is DC at 20°C.

AWG wire sizes with diameter, cross-sectional area and DC resistance
AWG Diameter (in) Diameter (mm) Area (mm²) Circular mils Ω per 1000 ft Ω per km
4/0 0.4600 11.68 107.2 211,600 0.04901 0.1608
3/0 0.4096 10.40 85.03 167,800 0.06180 0.2028
2/0 0.3648 9.266 67.43 133,100 0.07793 0.2557
1/0 0.3249 8.251 53.47 105,500 0.09827 0.3224
1 0.2893 7.348 42.41 83,690 0.1239 0.4066
2 0.2576 6.544 33.63 66,370 0.1563 0.5127
3 0.2294 5.827 26.67 52,630 0.1970 0.6464
4 0.2043 5.189 21.15 41,740 0.2485 0.8152
5 0.1819 4.621 16.77 33,100 0.3133 1.028
6 0.1620 4.115 13.30 26,250 0.3951 1.296
7 0.1443 3.665 10.55 20,820 0.4982 1.634
8 0.1285 3.264 8.365 16,510 0.6282 2.061
9 0.1144 2.906 6.634 13,090 0.7921 2.599
10 0.1019 2.588 5.261 10,380 0.9988 3.277
11 0.09074 2.305 4.172 8,234 1.260 4.132
12 0.08081 2.053 3.309 6,530 1.588 5.211
13 0.07196 1.828 2.624 5,178 2.003 6.571
14 0.06408 1.628 2.081 4,107 2.525 8.285
15 0.05707 1.450 1.650 3,257 3.184 10.45
16 0.05082 1.291 1.309 2,583 4.015 13.17
17 0.04526 1.150 1.038 2,048 5.063 16.61
18 0.04030 1.024 0.8230 1,624 6.385 20.95
19 0.03589 0.9116 0.6527 1,288 8.051 26.41
20 0.03196 0.8118 0.5176 1,022 10.15 33.31
21 0.02846 0.7229 0.4105 810.1 12.80 42.00
22 0.02535 0.6438 0.3255 642.4 16.14 52.96
23 0.02257 0.5733 0.2582 509.5 20.36 66.78
24 0.02010 0.5106 0.2047 404.0 25.67 84.21
25 0.01790 0.4547 0.1624 320.4 32.37 106.2
26 0.01594 0.4049 0.1288 254.1 40.81 133.9
27 0.01420 0.3606 0.1021 201.5 51.47 168.9
28 0.01264 0.3211 0.08097 159.8 64.90 212.9
29 0.01126 0.2859 0.06422 126.7 81.83 268.5
30 0.01003 0.2546 0.05093 100.5 103.2 338.6
31 0.008928 0.2268 0.04039 79.70 130.1 426.9
32 0.007950 0.2019 0.03203 63.21 164.1 538.3
33 0.007080 0.1798 0.02540 50.13 206.9 678.8
34 0.006305 0.1601 0.02014 39.75 260.9 856.0
35 0.005615 0.1426 0.01597 31.52 329.0 1,079
36 0.005000 0.1270 0.01267 25.00 414.8 1,361
37 0.004453 0.1131 0.01005 19.83 523.1 1,716
38 0.003965 0.1007 0.007967 15.72 659.6 2,164
39 0.003531 0.08969 0.006318 12.47 831.8 2,729
40 0.003145 0.07987 0.005010 9.888 1,049 3,441

Every value is worked out from the AWG formula (see below) to four significant figures. Charts that round the diameter first and then square it can differ from these in the last digit, for example 1/0 AWG at 105,600 circular mils against 105,500 here. Resistance uses 10.371 ohm-circular-mil per foot, the ASTM B258 figure for annealed copper at 20°C. The AC resistance the voltage drop calculator uses (NEC Chapter 9, Table 9) is larger.

Wire gauge to amps: copper, 14 AWG to 4/0

Allowable ampacity from NEC Table 310.16 for not more than three current-carrying conductors at 30°C ambient. Use the column for the lowest temperature rating of any termination in the circuit. The ampacity chart has aluminium and the larger kcmil sizes.

Copper ampacity by AWG size at 60, 75 and 90 degrees C
AWG Area (mm²) 60°C 75°C 90°C
4/0 107.2 195 230 260
3/0 85.03 165 200 225
2/0 67.43 145 175 195
1/0 53.47 125 150 170
1 42.41 110 130 145
2 33.63 95 115 130
3 26.67 85 100 115
4 21.15 70 85 95
6 13.30 55 65 75
8 8.365 40 50 55
10 5.261 30 35 40
12 3.309 20 25 30
14 2.081 15 20 25

NEC 240.4(D) caps the breaker on the smallest wires whatever the table says: 14 AWG copper at 15 A, 12 AWG at 20 A and 10 AWG at 30 A. Ampacity is before any derating for heat or bundling.

Free download

Get the printable wire size charts

NEC 310.16 ampacity for copper and aluminium at 60, 75 and 90 C, how far each size runs before voltage drop bites, standard breaker sizes and AWG to mm2. Three pages, made for the van door.

We store your email with EmailOctopus to send the charts and occasional wiring and calculator tips, nothing else. Unsubscribe any time. Privacy policy.

How the AWG number sets the size

AWG is geometric. The diameter of gauge n, in inches, is:

diameter (in) = 0.005 × 92(36 − n) / 39

The sizes 1/0 to 4/0 use n = 0, −1, −2 and −3. The area in circular mils is the diameter in thousandths of an inch, squared, and one circular mil is 0.0005067 mm². Each step down in gauge number multiplies the diameter by 1.1229, so six steps double it and three steps double the area.

Worked example: 10 AWG

  • Diameter: 0.005 × 9226/39 = 0.1019 in, or 2.588 mm.
  • Area: (101.9 mils)² = 10,380 circular mils, which is 5.261 mm².
  • Resistance: 10.371 × 1000 ÷ 10,380 = 0.9988 Ω per 1000 ft.

Choosing a gauge for a circuit

For ordinary copper circuits protected by a breaker, the smallest gauge on the 60°C column is 14 AWG for 15 A, 12 AWG for 20 A and 10 AWG for 30 A. The wire size for amps table carries every breaker size up to 400 A, and the wire size calculator adds voltage drop for your run length, which on a long run calls for a thicker wire than the amps alone.

Once you have the gauge, the conduit fill chart shows how many of those wires fit in each size of conduit.

Frequently Asked Questions

What size is 12 AWG wire in mm and inches?

12 AWG solid copper is 2.053 mm (0.08081 in) across, with a cross-section of 3.309 mm2 or 6,530 circular mils.

Why does a smaller AWG number mean a thicker wire?

The number counts the drawing steps a wire has been through. Each pass through a die makes the wire thinner, so a higher number is a thinner wire. Going from 10 AWG to 11 AWG cuts the diameter by about 11%, and every 6 gauge numbers the diameter halves.

What gauge wire do I need for 20 amps?

12 AWG copper is the smallest wire for a 20 A breaker. Its 60°C ampacity in NEC 310.16 is 20 A, and NEC 240.4(D) limits it to a 20 A breaker. Long runs may need a larger wire to keep voltage drop down.

Is stranded wire the same size as solid wire of the same gauge?

The copper cross-section is about the same, so the gauge is the same, but stranded wire is a little thicker overall because of the gaps between strands. Its resistance is slightly higher than the solid-wire figures in this chart.

How do I convert AWG to mm2?

Read the mm2 column in the chart, or use the formula: diameter in inches is 0.005 x 92^((36 - n) / 39), and the area in mm2 is the diameter in mils squared times 0.0005067. For 10 AWG that gives 5.261 mm2.