Wire Gauge Chart (AWG)
A wire gauge chart lists each American Wire Gauge (AWG) size with its diameter, cross-section and resistance. A smaller gauge number is a thicker wire: 10 AWG is 0.1019 in (2.588 mm) across with 5.261 mm² of copper, and 14 AWG is 0.06408 in with 2.081 mm².
AWG wire gauge chart: diameter, area and resistance
Solid copper wire, 4/0 AWG down to 40 AWG. Resistance is DC at 20°C.
| AWG | Diameter (in) | Diameter (mm) | Area (mm²) | Circular mils | Ω per 1000 ft | Ω per km |
|---|---|---|---|---|---|---|
| 4/0 | 0.4600 | 11.68 | 107.2 | 211,600 | 0.04901 | 0.1608 |
| 3/0 | 0.4096 | 10.40 | 85.03 | 167,800 | 0.06180 | 0.2028 |
| 2/0 | 0.3648 | 9.266 | 67.43 | 133,100 | 0.07793 | 0.2557 |
| 1/0 | 0.3249 | 8.251 | 53.47 | 105,500 | 0.09827 | 0.3224 |
| 1 | 0.2893 | 7.348 | 42.41 | 83,690 | 0.1239 | 0.4066 |
| 2 | 0.2576 | 6.544 | 33.63 | 66,370 | 0.1563 | 0.5127 |
| 3 | 0.2294 | 5.827 | 26.67 | 52,630 | 0.1970 | 0.6464 |
| 4 | 0.2043 | 5.189 | 21.15 | 41,740 | 0.2485 | 0.8152 |
| 5 | 0.1819 | 4.621 | 16.77 | 33,100 | 0.3133 | 1.028 |
| 6 | 0.1620 | 4.115 | 13.30 | 26,250 | 0.3951 | 1.296 |
| 7 | 0.1443 | 3.665 | 10.55 | 20,820 | 0.4982 | 1.634 |
| 8 | 0.1285 | 3.264 | 8.365 | 16,510 | 0.6282 | 2.061 |
| 9 | 0.1144 | 2.906 | 6.634 | 13,090 | 0.7921 | 2.599 |
| 10 | 0.1019 | 2.588 | 5.261 | 10,380 | 0.9988 | 3.277 |
| 11 | 0.09074 | 2.305 | 4.172 | 8,234 | 1.260 | 4.132 |
| 12 | 0.08081 | 2.053 | 3.309 | 6,530 | 1.588 | 5.211 |
| 13 | 0.07196 | 1.828 | 2.624 | 5,178 | 2.003 | 6.571 |
| 14 | 0.06408 | 1.628 | 2.081 | 4,107 | 2.525 | 8.285 |
| 15 | 0.05707 | 1.450 | 1.650 | 3,257 | 3.184 | 10.45 |
| 16 | 0.05082 | 1.291 | 1.309 | 2,583 | 4.015 | 13.17 |
| 17 | 0.04526 | 1.150 | 1.038 | 2,048 | 5.063 | 16.61 |
| 18 | 0.04030 | 1.024 | 0.8230 | 1,624 | 6.385 | 20.95 |
| 19 | 0.03589 | 0.9116 | 0.6527 | 1,288 | 8.051 | 26.41 |
| 20 | 0.03196 | 0.8118 | 0.5176 | 1,022 | 10.15 | 33.31 |
| 21 | 0.02846 | 0.7229 | 0.4105 | 810.1 | 12.80 | 42.00 |
| 22 | 0.02535 | 0.6438 | 0.3255 | 642.4 | 16.14 | 52.96 |
| 23 | 0.02257 | 0.5733 | 0.2582 | 509.5 | 20.36 | 66.78 |
| 24 | 0.02010 | 0.5106 | 0.2047 | 404.0 | 25.67 | 84.21 |
| 25 | 0.01790 | 0.4547 | 0.1624 | 320.4 | 32.37 | 106.2 |
| 26 | 0.01594 | 0.4049 | 0.1288 | 254.1 | 40.81 | 133.9 |
| 27 | 0.01420 | 0.3606 | 0.1021 | 201.5 | 51.47 | 168.9 |
| 28 | 0.01264 | 0.3211 | 0.08097 | 159.8 | 64.90 | 212.9 |
| 29 | 0.01126 | 0.2859 | 0.06422 | 126.7 | 81.83 | 268.5 |
| 30 | 0.01003 | 0.2546 | 0.05093 | 100.5 | 103.2 | 338.6 |
| 31 | 0.008928 | 0.2268 | 0.04039 | 79.70 | 130.1 | 426.9 |
| 32 | 0.007950 | 0.2019 | 0.03203 | 63.21 | 164.1 | 538.3 |
| 33 | 0.007080 | 0.1798 | 0.02540 | 50.13 | 206.9 | 678.8 |
| 34 | 0.006305 | 0.1601 | 0.02014 | 39.75 | 260.9 | 856.0 |
| 35 | 0.005615 | 0.1426 | 0.01597 | 31.52 | 329.0 | 1,079 |
| 36 | 0.005000 | 0.1270 | 0.01267 | 25.00 | 414.8 | 1,361 |
| 37 | 0.004453 | 0.1131 | 0.01005 | 19.83 | 523.1 | 1,716 |
| 38 | 0.003965 | 0.1007 | 0.007967 | 15.72 | 659.6 | 2,164 |
| 39 | 0.003531 | 0.08969 | 0.006318 | 12.47 | 831.8 | 2,729 |
| 40 | 0.003145 | 0.07987 | 0.005010 | 9.888 | 1,049 | 3,441 |
Every value is worked out from the AWG formula (see below) to four significant figures. Charts that round the diameter first and then square it can differ from these in the last digit, for example 1/0 AWG at 105,600 circular mils against 105,500 here. Resistance uses 10.371 ohm-circular-mil per foot, the ASTM B258 figure for annealed copper at 20°C. The AC resistance the voltage drop calculator uses (NEC Chapter 9, Table 9) is larger.
Wire gauge to amps: copper, 14 AWG to 4/0
Allowable ampacity from NEC Table 310.16 for not more than three current-carrying conductors at 30°C ambient. Use the column for the lowest temperature rating of any termination in the circuit. The ampacity chart has aluminium and the larger kcmil sizes.
| AWG | Area (mm²) | 60°C | 75°C | 90°C |
|---|---|---|---|---|
| 4/0 | 107.2 | 195 | 230 | 260 |
| 3/0 | 85.03 | 165 | 200 | 225 |
| 2/0 | 67.43 | 145 | 175 | 195 |
| 1/0 | 53.47 | 125 | 150 | 170 |
| 1 | 42.41 | 110 | 130 | 145 |
| 2 | 33.63 | 95 | 115 | 130 |
| 3 | 26.67 | 85 | 100 | 115 |
| 4 | 21.15 | 70 | 85 | 95 |
| 6 | 13.30 | 55 | 65 | 75 |
| 8 | 8.365 | 40 | 50 | 55 |
| 10 | 5.261 | 30 | 35 | 40 |
| 12 | 3.309 | 20 | 25 | 30 |
| 14 | 2.081 | 15 | 20 | 25 |
NEC 240.4(D) caps the breaker on the smallest wires whatever the table says: 14 AWG copper at 15 A, 12 AWG at 20 A and 10 AWG at 30 A. Ampacity is before any derating for heat or bundling.
Free download
Get the printable wire size charts
NEC 310.16 ampacity for copper and aluminium at 60, 75 and 90 C, how far each size runs before voltage drop bites, standard breaker sizes and AWG to mm2. Three pages, made for the van door.
How the AWG number sets the size
AWG is geometric. The diameter of gauge n, in inches, is:
The sizes 1/0 to 4/0 use n = 0, −1, −2 and −3. The area in circular mils is the diameter in thousandths of an inch, squared, and one circular mil is 0.0005067 mm². Each step down in gauge number multiplies the diameter by 1.1229, so six steps double it and three steps double the area.
Worked example: 10 AWG
- Diameter: 0.005 × 9226/39 = 0.1019 in, or 2.588 mm.
- Area: (101.9 mils)² = 10,380 circular mils, which is 5.261 mm².
- Resistance: 10.371 × 1000 ÷ 10,380 = 0.9988 Ω per 1000 ft.
Choosing a gauge for a circuit
For ordinary copper circuits protected by a breaker, the smallest gauge on the 60°C column is 14 AWG for 15 A, 12 AWG for 20 A and 10 AWG for 30 A. The wire size for amps table carries every breaker size up to 400 A, and the wire size calculator adds voltage drop for your run length, which on a long run calls for a thicker wire than the amps alone.
Once you have the gauge, the conduit fill chart shows how many of those wires fit in each size of conduit.
Frequently Asked Questions
What size is 12 AWG wire in mm and inches?
12 AWG solid copper is 2.053 mm (0.08081 in) across, with a cross-section of 3.309 mm2 or 6,530 circular mils.
Why does a smaller AWG number mean a thicker wire?
The number counts the drawing steps a wire has been through. Each pass through a die makes the wire thinner, so a higher number is a thinner wire. Going from 10 AWG to 11 AWG cuts the diameter by about 11%, and every 6 gauge numbers the diameter halves.
What gauge wire do I need for 20 amps?
12 AWG copper is the smallest wire for a 20 A breaker. Its 60°C ampacity in NEC 310.16 is 20 A, and NEC 240.4(D) limits it to a 20 A breaker. Long runs may need a larger wire to keep voltage drop down.
Is stranded wire the same size as solid wire of the same gauge?
The copper cross-section is about the same, so the gauge is the same, but stranded wire is a little thicker overall because of the gaps between strands. Its resistance is slightly higher than the solid-wire figures in this chart.
How do I convert AWG to mm2?
Read the mm2 column in the chart, or use the formula: diameter in inches is 0.005 x 92^((36 - n) / 39), and the area in mm2 is the diameter in mils squared times 0.0005067. For 10 AWG that gives 5.261 mm2.
Related Calculators
Continue with these related electrical tools
Wire Size Calculator
Smallest conductor that meets ampacity and the voltage-drop limit (AWG/mm2)
AWG Conversion Calculator
Convert AWG to mm2, circular mils, kcmil and diameter
Ampacity Chart
NEC 310.16 copper and aluminium ampacity at 60, 75 and 90 C, with AWG to mm2
Conduit Fill Chart
How many THHN wires fit in EMT and PVC conduit, from NEC Chapter 9
Voltage Drop Calculator
Voltage drop over a run by length, current and conductor (AWG/mm2, 1ph/3ph/DC)