Wire Ampacity Chart (NEC 310.16)

Allowable ampacity of insulated copper and aluminium conductors rated up to 2,000 V, for not more than three current-carrying conductors in a raceway, cable or earth, at an ambient temperature of 30°C. These are the figures every wire size answer on this site is built from. Print the page, or take the three-page PDF below.

How to read it

  1. Find the column for the lowest termination temperature rating in the circuit. NEC 110.14(C)(1) requires the 60°C column for circuits of 100 A or less unless every termination is listed higher, and the 75°C column above 100 A.
  2. Read down to the first size whose ampacity meets or exceeds your load.
  3. Check that size against the 240.4(D) caps below, which override the table for the smallest conductors.
  4. Then check voltage drop over your run length, which frequently calls for a larger conductor than ampacity alone.

Wire size for amps: breaker size to wire gauge

The smallest wire that carries the breaker's rating and may be protected by it, with the NEC 240.4(D) caps applied. Each row links to the page for that circuit.

Smallest copper and aluminium wire size for each breaker rating at 60 and 75 degrees C
Amps Copper Aluminium
60°C 75°C 60°C 75°C
15 A 14 AWG 14 AWG 12 AWG 12 AWG
20 A 12 AWG 12 AWG 10 AWG 10 AWG
25 A 10 AWG 10 AWG 10 AWG 10 AWG
30 A 10 AWG 10 AWG 8 AWG 8 AWG
35 A 8 AWG 8 AWG 8 AWG 8 AWG
40 A 8 AWG 8 AWG 6 AWG 8 AWG
45 A 6 AWG 8 AWG 4 AWG 6 AWG
50 A 6 AWG 8 AWG 4 AWG 6 AWG
60 A 4 AWG 6 AWG 3 AWG 4 AWG
70 A 4 AWG 4 AWG 2 AWG 3 AWG
80 A 3 AWG 4 AWG 1 AWG 2 AWG
90 A 2 AWG 3 AWG 1/0 AWG 2 AWG
100 A 1 AWG 3 AWG 1/0 AWG 1 AWG
110 A 1 AWG 2 AWG 2/0 AWG 1/0 AWG
125 A 1/0 AWG 1 AWG 3/0 AWG 2/0 AWG
150 A 3/0 AWG 1/0 AWG 4/0 AWG 3/0 AWG
175 A 4/0 AWG 2/0 AWG 300 kcmil 4/0 AWG
200 A 250 kcmil 3/0 AWG 350 kcmil 250 kcmil
225 A 300 kcmil 4/0 AWG 400 kcmil 300 kcmil
250 A 350 kcmil 250 kcmil 500 kcmil 350 kcmil
300 A 500 kcmil 350 kcmil 700 kcmil 500 kcmil
400 A 750 kcmil 600 kcmil 1250 kcmil 900 kcmil

Use the 60°C column for circuits of 100 A or less unless every termination is listed for 75°C, and the 75°C column above 100 A (NEC 110.14(C)(1)). Loads that run three hours or more need the wire sized to 125% of the load. "Parallel" means no single conductor in the table is large enough. This is wire size for ampacity only, so add voltage drop with the wire size calculator, and see the wire gauge chart for diameters and the conduit fill chart for conduit size.

Copper ampacity (NEC 310.16)

Amps, for not more than three current-carrying conductors at 30°C ambient. Cross-section and AC resistance are shown alongside so the same row answers a metric or a voltage-drop question.

Size mm² 60°C 75°C 90°C Ω/km
18 AWG 0.82 - - 14 -
16 AWG 1.31 - - 18 -
14 AWG 2.08 15 20 25 10.200
12 AWG 3.31 20 25 30 6.600
10 AWG 5.26 30 35 40 3.900
8 AWG 8.37 40 50 55 2.560
6 AWG 13.30 55 65 75 1.610
4 AWG 21.15 70 85 95 1.020
3 AWG 26.67 85 100 115 0.820
2 AWG 33.63 95 115 130 0.620
1 AWG 42.41 110 130 145 0.490
1/0 AWG 53.47 125 150 170 0.390
2/0 AWG 67.43 145 175 195 0.330
3/0 AWG 85.03 165 200 225 0.253
4/0 AWG 107.22 195 230 260 0.203
250 kcmil 126.68 215 255 290 0.171
300 kcmil 152.01 240 285 320 0.144
350 kcmil 177.35 260 310 350 0.125
400 kcmil 202.68 280 335 380 0.108
500 kcmil 253.35 320 380 430 0.089
600 kcmil 304.02 350 420 475 0.075
700 kcmil 354.69 385 460 520 -
750 kcmil 380.03 400 475 535 0.062
800 kcmil 405.36 410 490 555 -
900 kcmil 456.03 435 520 585 -
1000 kcmil 506.70 455 545 615 0.049
1250 kcmil 633.38 495 590 665 -
1500 kcmil 760.05 525 625 705 -
1750 kcmil 886.73 545 650 735 -
2000 kcmil 1,013.40 555 665 750 -

Table 310.16 gives 18 and 16 AWG copper a 90°C figure only. Under 2023 NEC 310.3(A), 14 AWG is the smallest copper conductor for general wiring, so those two rows are for reference: other articles permit them for uses such as fixture wires (Article 402). AC resistance is NEC Chapter 9 Table 9, 60 Hz in PVC conduit. Table 9 runs from 14 AWG to 1,000 kcmil and does not list 700, 800 or 900 kcmil, hence the gaps.

Aluminium and copper-clad aluminium ampacity (NEC 310.16)

Amps, for not more than three current-carrying conductors at 30°C ambient. Cross-section and AC resistance are shown alongside so the same row answers a metric or a voltage-drop question.

Size mm² 60°C 75°C 90°C Ω/km
12 AWG 3.31 15 20 25 10.500
10 AWG 5.26 25 30 35 6.600
8 AWG 8.37 35 40 45 4.300
6 AWG 13.30 40 50 55 2.660
4 AWG 21.15 55 65 75 1.670
3 AWG 26.67 65 75 85 1.310
2 AWG 33.63 75 90 100 1.050
1 AWG 42.41 85 100 115 0.820
1/0 AWG 53.47 100 120 135 0.660
2/0 AWG 67.43 115 135 150 0.520
3/0 AWG 85.03 130 155 175 0.430
4/0 AWG 107.22 150 180 205 0.330
250 kcmil 126.68 170 205 230 0.279
300 kcmil 152.01 195 230 260 0.233
350 kcmil 177.35 210 250 280 0.200
400 kcmil 202.68 225 270 305 0.177
500 kcmil 253.35 260 310 350 0.141
600 kcmil 304.02 285 340 385 0.118
700 kcmil 354.69 315 375 425 -
750 kcmil 380.03 320 385 435 0.095
800 kcmil 405.36 330 395 445 -
900 kcmil 456.03 355 425 480 -
1000 kcmil 506.70 375 445 500 0.075
1250 kcmil 633.38 405 485 545 -
1500 kcmil 760.05 435 520 585 -
1750 kcmil 886.73 455 545 615 -
2000 kcmil 1,013.40 470 560 630 -

Under 2023 NEC 310.3(A), 12 AWG is the smallest aluminium conductor, which is why the table starts there. Every terminal an aluminium conductor lands on must be identified for aluminium (NEC 110.14): AL/CU on breakers and lugs, CO/ALR on receptacles and switches of 20 A or less that the aluminium connects to directly. Aluminium is typically one to two sizes larger than copper for the same load. Table 9 resistance stops at 1,000 kcmil and does not list 700, 800 or 900 kcmil.

Small-conductor caps (NEC 240.4(D))

These override the table above. Whatever the 75 or 90°C column allows, the overcurrent device on these conductors may not exceed the figure here for general circuits. NEC 240.4(G) exempts motor circuits (Article 430) and air-conditioning equipment (Article 440), which are sized from the nameplate instead.

Conductor Max overcurrent device 75°C ampacity it would otherwise allow
18 AWG copper 7 A -
16 AWG copper 10 A -
14 AWG copper 15 A 20 A
12 AWG copper 20 A 25 A
10 AWG copper 30 A 35 A
12 AWG aluminium 15 A 20 A
10 AWG aluminium 25 A 30 A

The 18 and 16 AWG copper limits apply only where continuous loads stay at or below 5.6 A and 8 A respectively, and the breaker or fuse is one of the types 240.4(D)(1) and (2) list. Aluminium here includes copper-clad aluminium.

AWG to mm² and kcmil

Cross-section, diameter and area for every size in the ampacity tables. Derived from the AWG formula, so it agrees with the AWG conversion calculator to the same precision.

Size mm² kcmil Diameter (in) Diameter (mm)
18 AWG 0.82 1.6 0.0403 1.02
16 AWG 1.31 2.6 0.0508 1.29
14 AWG 2.08 4.1 0.0641 1.63
12 AWG 3.31 6.5 0.0808 2.05
10 AWG 5.26 10.4 0.1019 2.59
8 AWG 8.37 16.5 0.1285 3.26
6 AWG 13.30 26.3 0.1620 4.12
4 AWG 21.15 41.7 0.2043 5.19
3 AWG 26.67 52.6 0.2294 5.83
2 AWG 33.63 66.4 0.2576 6.54
1 AWG 42.41 83.7 0.2893 7.35
1/0 AWG 53.47 105.5 0.3249 8.25
2/0 AWG 67.43 133.1 0.3648 9.27
3/0 AWG 85.03 167.8 0.4096 10.40
4/0 AWG 107.22 211.6 0.4600 11.68
250 kcmil 126.68 250.0 0.5000 12.70
300 kcmil 152.01 300.0 0.5477 13.91
350 kcmil 177.35 350.0 0.5916 15.03
400 kcmil 202.68 400.0 0.6325 16.06
500 kcmil 253.35 500.0 0.7071 17.96
600 kcmil 304.02 600.0 0.7746 19.67
700 kcmil 354.69 700.0 0.8367 21.25
750 kcmil 380.03 750.0 0.8660 22.00
800 kcmil 405.36 800.0 0.8944 22.72
900 kcmil 456.03 900.0 0.9487 24.10
1000 kcmil 506.70 1,000.0 1.0000 25.40
1250 kcmil 633.38 1,250.0 1.1180 28.40
1500 kcmil 760.05 1,500.0 1.2247 31.11
1750 kcmil 886.73 1,750.0 1.3229 33.60
2000 kcmil 1,013.40 2,000.0 1.4142 35.92

Free download

Get the printable wire size charts

NEC 310.16 ampacity for copper and aluminium at 60, 75 and 90 C, how far each size runs before voltage drop bites, standard breaker sizes and AWG to mm2. Three pages, made for the van door.

We store your email with EmailOctopus to send the charts and occasional wiring and calculator tips, nothing else. Unsubscribe any time. Privacy policy.

What the chart does not include

The figures above are base ampacities for a defined set of conditions. Three adjustments are applied on top of them, and all three make the required conductor larger, never smaller:

  • Ambient temperature. The table assumes 30°C. NEC Table 310.15(B)(1) gives correction factors for hotter surroundings, and a conduit in direct sun or a hot attic is well above 30°C.
  • Conductor bundling. More than three current-carrying conductors in a raceway or cable triggers the adjustment factors in NEC 310.15(C)(1): 80% for four to six, 70% for seven to nine, and lower again beyond that.
  • Continuous loads. A load running three hours or more requires the circuit to be rated at 125% of it under NEC 210.19 and 215.2.

Derating starts from the ampacity of the conductor's own insulation rating, which is why a 90°C conductor is useful even though its 90°C column is rarely the final answer: you derate from the 90°C figure and then check the result against the termination column.

Frequently Asked Questions

What is ampacity?

The maximum current a conductor can carry continuously without exceeding its temperature rating. It is a property of the conductor in its installed conditions, not of the wire alone: the same conductor has a lower ampacity in a hot attic, or bundled with others, than it does in the table.

Which column should I use, 60, 75 or 90°C?

The one matching the lowest termination rating in the circuit. NEC 110.14(C)(1) requires the 60°C column for circuits of 100 A or less unless every termination is listed for a higher temperature, and the 75°C column above 100 A. Most modern breakers and lugs are listed 75°C. The 90°C column is normally a starting point for derating rather than a final answer, and NM cable is fixed at the 60°C column by NEC 334.80 regardless of the terminations.

Why can 12 AWG copper only take a 20 A breaker when the chart says 25 A?

NEC 240.4(D) caps the overcurrent device on the smallest conductors regardless of their ampacity, to allow for the damage a small conductor suffers from repeated overload. 14 AWG copper is capped at 15 A, 12 AWG at 20 A and 10 AWG at 30 A; in aluminium, 12 AWG is capped at 15 A and 10 AWG at 25 A. The cap does not apply to motor or air-conditioning circuits, which follow Articles 430 and 440 instead.

Is this table the same as NEC Table 310.15(B)(16)?

Yes, renumbered. The allowable ampacity table was Table 310.16 in older editions, became Table 310.15(B)(16) in the 2011 through 2017 cycles, and returned to Table 310.16 in the 2020 edition. The values are the ones in current use; older references to 310.15(B)(16) point at the same data.

Does a bigger conductor always fix a voltage drop problem?

It is the usual fix, because drop is proportional to resistance and resistance falls as cross-section rises. Going one size up typically buys around 25% more distance at the same current. Raising the system voltage is more effective where it is an option, since drop as a percentage falls with the square of the voltage for a given power.