Wire Ampacity Chart (NEC 310.16)
Allowable ampacity of insulated copper and aluminium conductors rated up to 2,000 V, for not more than three current-carrying conductors in a raceway, cable or earth, at an ambient temperature of 30°C. These are the figures every wire size answer on this site is built from. Print the page, or take the three-page PDF below.
How to read it
- Find the column for the lowest termination temperature rating in the circuit. NEC 110.14(C)(1) requires the 60°C column for circuits of 100 A or less unless every termination is listed higher, and the 75°C column above 100 A.
- Read down to the first size whose ampacity meets or exceeds your load.
- Check that size against the 240.4(D) caps below, which override the table for the smallest conductors.
- Then check voltage drop over your run length, which frequently calls for a larger conductor than ampacity alone.
Wire size for amps: breaker size to wire gauge
The smallest wire that carries the breaker's rating and may be protected by it, with the NEC 240.4(D) caps applied. Each row links to the page for that circuit.
| Amps | Copper | Aluminium | ||
|---|---|---|---|---|
| 60°C | 75°C | 60°C | 75°C | |
| 15 A | 14 AWG | 14 AWG | 12 AWG | 12 AWG |
| 20 A | 12 AWG | 12 AWG | 10 AWG | 10 AWG |
| 25 A | 10 AWG | 10 AWG | 10 AWG | 10 AWG |
| 30 A | 10 AWG | 10 AWG | 8 AWG | 8 AWG |
| 35 A | 8 AWG | 8 AWG | 8 AWG | 8 AWG |
| 40 A | 8 AWG | 8 AWG | 6 AWG | 8 AWG |
| 45 A | 6 AWG | 8 AWG | 4 AWG | 6 AWG |
| 50 A | 6 AWG | 8 AWG | 4 AWG | 6 AWG |
| 60 A | 4 AWG | 6 AWG | 3 AWG | 4 AWG |
| 70 A | 4 AWG | 4 AWG | 2 AWG | 3 AWG |
| 80 A | 3 AWG | 4 AWG | 1 AWG | 2 AWG |
| 90 A | 2 AWG | 3 AWG | 1/0 AWG | 2 AWG |
| 100 A | 1 AWG | 3 AWG | 1/0 AWG | 1 AWG |
| 110 A | 1 AWG | 2 AWG | 2/0 AWG | 1/0 AWG |
| 125 A | 1/0 AWG | 1 AWG | 3/0 AWG | 2/0 AWG |
| 150 A | 3/0 AWG | 1/0 AWG | 4/0 AWG | 3/0 AWG |
| 175 A | 4/0 AWG | 2/0 AWG | 300 kcmil | 4/0 AWG |
| 200 A | 250 kcmil | 3/0 AWG | 350 kcmil | 250 kcmil |
| 225 A | 300 kcmil | 4/0 AWG | 400 kcmil | 300 kcmil |
| 250 A | 350 kcmil | 250 kcmil | 500 kcmil | 350 kcmil |
| 300 A | 500 kcmil | 350 kcmil | 700 kcmil | 500 kcmil |
| 400 A | 750 kcmil | 600 kcmil | 1250 kcmil | 900 kcmil |
Use the 60°C column for circuits of 100 A or less unless every termination is listed for 75°C, and the 75°C column above 100 A (NEC 110.14(C)(1)). Loads that run three hours or more need the wire sized to 125% of the load. "Parallel" means no single conductor in the table is large enough. This is wire size for ampacity only, so add voltage drop with the wire size calculator, and see the wire gauge chart for diameters and the conduit fill chart for conduit size.
Copper ampacity (NEC 310.16)
Amps, for not more than three current-carrying conductors at 30°C ambient. Cross-section and AC resistance are shown alongside so the same row answers a metric or a voltage-drop question.
| Size | mm² | 60°C | 75°C | 90°C | Ω/km |
|---|---|---|---|---|---|
| 18 AWG | 0.82 | - | - | 14 | - |
| 16 AWG | 1.31 | - | - | 18 | - |
| 14 AWG | 2.08 | 15 | 20 | 25 | 10.200 |
| 12 AWG | 3.31 | 20 | 25 | 30 | 6.600 |
| 10 AWG | 5.26 | 30 | 35 | 40 | 3.900 |
| 8 AWG | 8.37 | 40 | 50 | 55 | 2.560 |
| 6 AWG | 13.30 | 55 | 65 | 75 | 1.610 |
| 4 AWG | 21.15 | 70 | 85 | 95 | 1.020 |
| 3 AWG | 26.67 | 85 | 100 | 115 | 0.820 |
| 2 AWG | 33.63 | 95 | 115 | 130 | 0.620 |
| 1 AWG | 42.41 | 110 | 130 | 145 | 0.490 |
| 1/0 AWG | 53.47 | 125 | 150 | 170 | 0.390 |
| 2/0 AWG | 67.43 | 145 | 175 | 195 | 0.330 |
| 3/0 AWG | 85.03 | 165 | 200 | 225 | 0.253 |
| 4/0 AWG | 107.22 | 195 | 230 | 260 | 0.203 |
| 250 kcmil | 126.68 | 215 | 255 | 290 | 0.171 |
| 300 kcmil | 152.01 | 240 | 285 | 320 | 0.144 |
| 350 kcmil | 177.35 | 260 | 310 | 350 | 0.125 |
| 400 kcmil | 202.68 | 280 | 335 | 380 | 0.108 |
| 500 kcmil | 253.35 | 320 | 380 | 430 | 0.089 |
| 600 kcmil | 304.02 | 350 | 420 | 475 | 0.075 |
| 700 kcmil | 354.69 | 385 | 460 | 520 | - |
| 750 kcmil | 380.03 | 400 | 475 | 535 | 0.062 |
| 800 kcmil | 405.36 | 410 | 490 | 555 | - |
| 900 kcmil | 456.03 | 435 | 520 | 585 | - |
| 1000 kcmil | 506.70 | 455 | 545 | 615 | 0.049 |
| 1250 kcmil | 633.38 | 495 | 590 | 665 | - |
| 1500 kcmil | 760.05 | 525 | 625 | 705 | - |
| 1750 kcmil | 886.73 | 545 | 650 | 735 | - |
| 2000 kcmil | 1,013.40 | 555 | 665 | 750 | - |
Table 310.16 gives 18 and 16 AWG copper a 90°C figure only. Under 2023 NEC 310.3(A), 14 AWG is the smallest copper conductor for general wiring, so those two rows are for reference: other articles permit them for uses such as fixture wires (Article 402). AC resistance is NEC Chapter 9 Table 9, 60 Hz in PVC conduit. Table 9 runs from 14 AWG to 1,000 kcmil and does not list 700, 800 or 900 kcmil, hence the gaps.
Aluminium and copper-clad aluminium ampacity (NEC 310.16)
Amps, for not more than three current-carrying conductors at 30°C ambient. Cross-section and AC resistance are shown alongside so the same row answers a metric or a voltage-drop question.
| Size | mm² | 60°C | 75°C | 90°C | Ω/km |
|---|---|---|---|---|---|
| 12 AWG | 3.31 | 15 | 20 | 25 | 10.500 |
| 10 AWG | 5.26 | 25 | 30 | 35 | 6.600 |
| 8 AWG | 8.37 | 35 | 40 | 45 | 4.300 |
| 6 AWG | 13.30 | 40 | 50 | 55 | 2.660 |
| 4 AWG | 21.15 | 55 | 65 | 75 | 1.670 |
| 3 AWG | 26.67 | 65 | 75 | 85 | 1.310 |
| 2 AWG | 33.63 | 75 | 90 | 100 | 1.050 |
| 1 AWG | 42.41 | 85 | 100 | 115 | 0.820 |
| 1/0 AWG | 53.47 | 100 | 120 | 135 | 0.660 |
| 2/0 AWG | 67.43 | 115 | 135 | 150 | 0.520 |
| 3/0 AWG | 85.03 | 130 | 155 | 175 | 0.430 |
| 4/0 AWG | 107.22 | 150 | 180 | 205 | 0.330 |
| 250 kcmil | 126.68 | 170 | 205 | 230 | 0.279 |
| 300 kcmil | 152.01 | 195 | 230 | 260 | 0.233 |
| 350 kcmil | 177.35 | 210 | 250 | 280 | 0.200 |
| 400 kcmil | 202.68 | 225 | 270 | 305 | 0.177 |
| 500 kcmil | 253.35 | 260 | 310 | 350 | 0.141 |
| 600 kcmil | 304.02 | 285 | 340 | 385 | 0.118 |
| 700 kcmil | 354.69 | 315 | 375 | 425 | - |
| 750 kcmil | 380.03 | 320 | 385 | 435 | 0.095 |
| 800 kcmil | 405.36 | 330 | 395 | 445 | - |
| 900 kcmil | 456.03 | 355 | 425 | 480 | - |
| 1000 kcmil | 506.70 | 375 | 445 | 500 | 0.075 |
| 1250 kcmil | 633.38 | 405 | 485 | 545 | - |
| 1500 kcmil | 760.05 | 435 | 520 | 585 | - |
| 1750 kcmil | 886.73 | 455 | 545 | 615 | - |
| 2000 kcmil | 1,013.40 | 470 | 560 | 630 | - |
Under 2023 NEC 310.3(A), 12 AWG is the smallest aluminium conductor, which is why the table starts there. Every terminal an aluminium conductor lands on must be identified for aluminium (NEC 110.14): AL/CU on breakers and lugs, CO/ALR on receptacles and switches of 20 A or less that the aluminium connects to directly. Aluminium is typically one to two sizes larger than copper for the same load. Table 9 resistance stops at 1,000 kcmil and does not list 700, 800 or 900 kcmil.
Small-conductor caps (NEC 240.4(D))
These override the table above. Whatever the 75 or 90°C column allows, the overcurrent device on these conductors may not exceed the figure here for general circuits. NEC 240.4(G) exempts motor circuits (Article 430) and air-conditioning equipment (Article 440), which are sized from the nameplate instead.
| Conductor | Max overcurrent device | 75°C ampacity it would otherwise allow |
|---|---|---|
| 18 AWG copper | 7 A | - |
| 16 AWG copper | 10 A | - |
| 14 AWG copper | 15 A | 20 A |
| 12 AWG copper | 20 A | 25 A |
| 10 AWG copper | 30 A | 35 A |
| 12 AWG aluminium | 15 A | 20 A |
| 10 AWG aluminium | 25 A | 30 A |
The 18 and 16 AWG copper limits apply only where continuous loads stay at or below 5.6 A and 8 A respectively, and the breaker or fuse is one of the types 240.4(D)(1) and (2) list. Aluminium here includes copper-clad aluminium.
AWG to mm² and kcmil
Cross-section, diameter and area for every size in the ampacity tables. Derived from the AWG formula, so it agrees with the AWG conversion calculator to the same precision.
| Size | mm² | kcmil | Diameter (in) | Diameter (mm) |
|---|---|---|---|---|
| 18 AWG | 0.82 | 1.6 | 0.0403 | 1.02 |
| 16 AWG | 1.31 | 2.6 | 0.0508 | 1.29 |
| 14 AWG | 2.08 | 4.1 | 0.0641 | 1.63 |
| 12 AWG | 3.31 | 6.5 | 0.0808 | 2.05 |
| 10 AWG | 5.26 | 10.4 | 0.1019 | 2.59 |
| 8 AWG | 8.37 | 16.5 | 0.1285 | 3.26 |
| 6 AWG | 13.30 | 26.3 | 0.1620 | 4.12 |
| 4 AWG | 21.15 | 41.7 | 0.2043 | 5.19 |
| 3 AWG | 26.67 | 52.6 | 0.2294 | 5.83 |
| 2 AWG | 33.63 | 66.4 | 0.2576 | 6.54 |
| 1 AWG | 42.41 | 83.7 | 0.2893 | 7.35 |
| 1/0 AWG | 53.47 | 105.5 | 0.3249 | 8.25 |
| 2/0 AWG | 67.43 | 133.1 | 0.3648 | 9.27 |
| 3/0 AWG | 85.03 | 167.8 | 0.4096 | 10.40 |
| 4/0 AWG | 107.22 | 211.6 | 0.4600 | 11.68 |
| 250 kcmil | 126.68 | 250.0 | 0.5000 | 12.70 |
| 300 kcmil | 152.01 | 300.0 | 0.5477 | 13.91 |
| 350 kcmil | 177.35 | 350.0 | 0.5916 | 15.03 |
| 400 kcmil | 202.68 | 400.0 | 0.6325 | 16.06 |
| 500 kcmil | 253.35 | 500.0 | 0.7071 | 17.96 |
| 600 kcmil | 304.02 | 600.0 | 0.7746 | 19.67 |
| 700 kcmil | 354.69 | 700.0 | 0.8367 | 21.25 |
| 750 kcmil | 380.03 | 750.0 | 0.8660 | 22.00 |
| 800 kcmil | 405.36 | 800.0 | 0.8944 | 22.72 |
| 900 kcmil | 456.03 | 900.0 | 0.9487 | 24.10 |
| 1000 kcmil | 506.70 | 1,000.0 | 1.0000 | 25.40 |
| 1250 kcmil | 633.38 | 1,250.0 | 1.1180 | 28.40 |
| 1500 kcmil | 760.05 | 1,500.0 | 1.2247 | 31.11 |
| 1750 kcmil | 886.73 | 1,750.0 | 1.3229 | 33.60 |
| 2000 kcmil | 1,013.40 | 2,000.0 | 1.4142 | 35.92 |
Free download
Get the printable wire size charts
NEC 310.16 ampacity for copper and aluminium at 60, 75 and 90 C, how far each size runs before voltage drop bites, standard breaker sizes and AWG to mm2. Three pages, made for the van door.
What the chart does not include
The figures above are base ampacities for a defined set of conditions. Three adjustments are applied on top of them, and all three make the required conductor larger, never smaller:
- Ambient temperature. The table assumes 30°C. NEC Table 310.15(B)(1) gives correction factors for hotter surroundings, and a conduit in direct sun or a hot attic is well above 30°C.
- Conductor bundling. More than three current-carrying conductors in a raceway or cable triggers the adjustment factors in NEC 310.15(C)(1): 80% for four to six, 70% for seven to nine, and lower again beyond that.
- Continuous loads. A load running three hours or more requires the circuit to be rated at 125% of it under NEC 210.19 and 215.2.
Derating starts from the ampacity of the conductor's own insulation rating, which is why a 90°C conductor is useful even though its 90°C column is rarely the final answer: you derate from the 90°C figure and then check the result against the termination column.
Frequently Asked Questions
What is ampacity?
The maximum current a conductor can carry continuously without exceeding its temperature rating. It is a property of the conductor in its installed conditions, not of the wire alone: the same conductor has a lower ampacity in a hot attic, or bundled with others, than it does in the table.
Which column should I use, 60, 75 or 90°C?
The one matching the lowest termination rating in the circuit. NEC 110.14(C)(1) requires the 60°C column for circuits of 100 A or less unless every termination is listed for a higher temperature, and the 75°C column above 100 A. Most modern breakers and lugs are listed 75°C. The 90°C column is normally a starting point for derating rather than a final answer, and NM cable is fixed at the 60°C column by NEC 334.80 regardless of the terminations.
Why can 12 AWG copper only take a 20 A breaker when the chart says 25 A?
NEC 240.4(D) caps the overcurrent device on the smallest conductors regardless of their ampacity, to allow for the damage a small conductor suffers from repeated overload. 14 AWG copper is capped at 15 A, 12 AWG at 20 A and 10 AWG at 30 A; in aluminium, 12 AWG is capped at 15 A and 10 AWG at 25 A. The cap does not apply to motor or air-conditioning circuits, which follow Articles 430 and 440 instead.
Is this table the same as NEC Table 310.15(B)(16)?
Yes, renumbered. The allowable ampacity table was Table 310.16 in older editions, became Table 310.15(B)(16) in the 2011 through 2017 cycles, and returned to Table 310.16 in the 2020 edition. The values are the ones in current use; older references to 310.15(B)(16) point at the same data.
Does a bigger conductor always fix a voltage drop problem?
It is the usual fix, because drop is proportional to resistance and resistance falls as cross-section rises. Going one size up typically buys around 25% more distance at the same current. Raising the system voltage is more effective where it is an option, since drop as a percentage falls with the square of the voltage for a given power.
Related Calculators
Continue with these related electrical tools
Wire Size Calculator
Smallest conductor that meets ampacity and the voltage-drop limit (AWG/mm2)
Voltage Drop Calculator
Voltage drop over a run by length, current and conductor (AWG/mm2, 1ph/3ph/DC)
Wire Gauge Chart
AWG sizes 4/0 to 40 with diameter, area, resistance and copper amps
Conduit Fill Chart
How many THHN wires fit in EMT and PVC conduit, from NEC Chapter 9
AWG Conversion Calculator
Convert AWG to mm2, circular mils, kcmil and diameter