Amps to kVA Calculator
Enter the current and voltage of the load and choose single or three-phase. The result is apparent power in kVA, the unit generators, transformers and UPS units are rated in. Because it is amps times volts with no power factor applied, it is the figure that tells you how big the supply equipment has to be.
Free download
Get the printable wire size charts
NEC 310.16 ampacity for copper and aluminium at 60, 75 and 90 C, how far each size runs before voltage drop bites, standard breaker sizes and AWG to mm2. Three pages, made for the van door.
How It Works
The formula
Single-phase: kVA = V × I / 1000
Three-phase: kVA = √3 × VL-L × I / 1000
V is line-to-line voltage for three-phase and I is the line current. To get kW from this kVA, multiply by the power factor.
Worked examples
50 A at 240 V single-phase
kVA = 240 × 50 / 1000 = 12 kVA. A 50 A, 240 V circuit, whether it feeds a range, a hot tub or an RV pedestal, is a 12 kVA demand on the supply.
200 A three-phase at 480 V
kVA = 1.732 × 480 × 200 / 1000 = 166.3 kVA. To supply it from a transformer you would pick the next standard rating up, 225 kVA, which also leaves room to grow.
100 A three-phase at 208 V
kVA = 1.732 × 208 × 100 / 1000 = 36.0 kVA. A 100 A, 208Y/120 panel is a 36 kVA panel; a 45 kVA transformer is the usual match.
A 13 A socket at 230 V
kVA = 230 × 13 / 1000 = 2.99 kVA. If the appliance behind it is a heater the kW is the same; if it is a motor at PF 0.8, it is only 2.4 kW of real power for the same 2.99 kVA.
63 A three-phase at 400 V
kVA = 1.732 × 400 × 63 / 1000 = 43.6 kVA. A 63 A three-phase supply is a common small commercial service in the UK and Australia; the same 63 A on a single-phase 230 V supply is 14.5 kVA, a third of it.
A 200 A, 120/240 V house service
kVA = 240 × 200 / 1000 = 48 kVA. That is the most the service can deliver, not what the house draws. A standby generator is sized from the NEC Article 220 load calculation, or from the circuits it will actually back up, which usually comes to far less than the service rating.
Amps to kVA, single-phase
Apparent power of a single-phase load. No power factor applies.
| A | 120 V | 208 V | 230 V | 240 V | 277 V |
|---|---|---|---|---|---|
| 5 A | 0.600 | 1.040 | 1.150 | 1.200 | 1.385 |
| 10 A | 1.200 | 2.080 | 2.300 | 2.400 | 2.770 |
| 13 A | 1.560 | 2.704 | 2.990 | 3.120 | 3.601 |
| 15 A | 1.800 | 3.120 | 3.450 | 3.600 | 4.155 |
| 16 A | 1.920 | 3.328 | 3.680 | 3.840 | 4.432 |
| 20 A | 2.400 | 4.160 | 4.600 | 4.800 | 5.540 |
| 25 A | 3.000 | 5.200 | 5.750 | 6.000 | 6.925 |
| 30 A | 3.600 | 6.240 | 6.900 | 7.200 | 8.310 |
| 32 A | 3.840 | 6.656 | 7.360 | 7.680 | 8.864 |
| 40 A | 4.800 | 8.320 | 9.200 | 9.600 | 11.08 |
| 50 A | 6.000 | 10.40 | 11.50 | 12.00 | 13.85 |
| 60 A | 7.200 | 12.48 | 13.80 | 14.40 | 16.62 |
| 63 A | 7.560 | 13.10 | 14.49 | 15.12 | 17.45 |
| 80 A | 9.600 | 16.64 | 18.40 | 19.20 | 22.16 |
| 100 A | 12.00 | 20.80 | 23.00 | 24.00 | 27.70 |
| 125 A | 15.00 | 26.00 | 28.75 | 30.00 | 34.63 |
| 150 A | 18.00 | 31.20 | 34.50 | 36.00 | 41.55 |
| 200 A | 24.00 | 41.60 | 46.00 | 48.00 | 55.40 |
Amps to kVA, three-phase
Balanced three-phase load, line current at line-to-line voltage. 600 V is the Canadian 347/600 V system.
| A | 208 V | 400 V | 415 V | 480 V | 600 V |
|---|---|---|---|---|---|
| 10 A | 3.603 | 6.928 | 7.188 | 8.314 | 10.39 |
| 16 A | 5.764 | 11.09 | 11.50 | 13.30 | 16.63 |
| 20 A | 7.205 | 13.86 | 14.38 | 16.63 | 20.78 |
| 25 A | 9.007 | 17.32 | 17.97 | 20.78 | 25.98 |
| 30 A | 10.81 | 20.78 | 21.56 | 24.94 | 31.18 |
| 32 A | 11.53 | 22.17 | 23.00 | 26.60 | 33.26 |
| 40 A | 14.41 | 27.71 | 28.75 | 33.26 | 41.57 |
| 50 A | 18.01 | 34.64 | 35.94 | 41.57 | 51.96 |
| 63 A | 22.70 | 43.65 | 45.28 | 52.38 | 65.47 |
| 80 A | 28.82 | 55.43 | 57.50 | 66.51 | 83.14 |
| 100 A | 36.03 | 69.28 | 71.88 | 83.14 | 103.9 |
| 125 A | 45.03 | 86.60 | 89.85 | 103.9 | 129.9 |
| 160 A | 57.64 | 110.9 | 115.0 | 133.0 | 166.3 |
| 200 A | 72.05 | 138.6 | 143.8 | 166.3 | 207.8 |
| 250 A | 90.07 | 173.2 | 179.7 | 207.8 | 259.8 |
| 300 A | 108.1 | 207.8 | 215.6 | 249.4 | 311.8 |
| 400 A | 144.1 | 277.1 | 287.5 | 332.6 | 415.7 |
| 600 A | 216.2 | 415.7 | 431.3 | 498.8 | 623.5 |
| 630 A | 227.0 | 436.5 | 452.8 | 523.8 | 654.7 |
| 800 A | 288.2 | 554.3 | 575.0 | 665.1 | 831.4 |
| 1,000 A | 360.3 | 692.8 | 718.8 | 831.4 | 1,039 |
| 1,200 A | 432.3 | 831.4 | 862.6 | 997.7 | 1,247 |
Panel and service sizes in kVA, with the transformer to match
The kVA a panel or service can deliver at its full rating, and the smallest standard transformer that covers it. A load calculation usually justifies a smaller unit; this is the one that can carry everything the panel is rated for. Single-phase units stop at 500 kVA, so the largest services are fed three-phase.
| A | 120/240 V 1-ph | Transformer | 208Y/120 V 3-ph | Transformer | 480Y/277 V 3-ph | Transformer |
|---|---|---|---|---|---|---|
| 60 A | 14.40 | 15 kVA | 21.62 | 30 kVA | 49.88 | 75 kVA |
| 100 A | 24.00 | 25 kVA | 36.03 | 45 kVA | 83.14 | 112.5 kVA |
| 125 A | 30.00 | 37.5 kVA | 45.03 | 45 kVA | 103.9 | 112.5 kVA |
| 150 A | 36.00 | 37.5 kVA | 54.04 | 75 kVA | 124.7 | 150 kVA |
| 200 A | 48.00 | 50 kVA | 72.05 | 75 kVA | 166.3 | 225 kVA |
| 225 A | 54.00 | 75 kVA | 81.06 | 112.5 kVA | 187.1 | 225 kVA |
| 400 A | 96.00 | 100 kVA | 144.1 | 150 kVA | 332.6 | 500 kVA |
| 600 A | 144.0 | 167 kVA | 216.2 | 225 kVA | 498.8 | 500 kVA |
| 800 A | 192.0 | 250 kVA | 288.2 | 300 kVA | 665.1 | 750 kVA |
| 1,000 A | 240.0 | 250 kVA | 360.3 | 500 kVA | 831.4 | 1,000 kVA |
| 1,200 A | 288.0 | 333 kVA | 432.3 | 500 kVA | 997.7 | 1,000 kVA |
Frequently Asked Questions
What size generator do I need for 100 amps at 240 V?
A 100 A, 240 V single-phase load is 24 kVA. Generator sets are rated in kVA at PF 0.8, so a 24 kVA set delivers 19.2 kW; if the load is resistive you still need the 24 kVA rating because the alternator is limited by current. Pick the next standard size up and allow for motor starting.
What is the difference between amps to kVA and amps to kW?
kVA ignores the power factor and kW includes it. For a heater the two are equal. For a motor at PF 0.8, 10 kVA of current is only 8 kW of work. Supply equipment is sized on kVA because it heats with current; bills and fuel burn are in kW.
Why are transformers and generators rated in kVA and not kW?
Their losses and temperature rise depend on the voltage and current they carry, not on how much of that is real power. A transformer delivering 100 A at 480 V heats the same whether the load is a furnace at PF 1 or a motor at PF 0.8, so the rating that protects it is kVA.
Should I add a margin to the kVA?
Yes, both for growth and for inrush. Motors draw around six times their running current for a moment at start, and transformer and generator manufacturers typically recommend sizing at 80% or so of continuous rating. A 36 kVA load on a 45 kVA transformer is a normal fit.
Is the current the same in all three lines?
For a balanced three-phase load, yes, and the formula assumes that. If the phases are unbalanced, work each phase as a single-phase load at line-to-neutral voltage and add the three kVA figures.
Other electrical conversions
Related Calculators
Continue with these related electrical tools
kVA to Amps Calculator
Transformer and generator full-load current from kVA
kW to kVA Calculator
Apparent power a generator or transformer must be rated for
Amps to kW Calculator
Kilowatts from a current reading, single or three-phase
kVA Calculator
Apparent power (kVA) from volts and amps, single or three phase
Embed This Calculator
Add this free calculator to your website. Copy the code below and paste it into your page.