kW to Amps Calculator

To convert kW to amps, multiply the kilowatts by 1,000 and divide by the voltage and the power factor: I = kW × 1000 / (V × PF) on single-phase, or I = kW × 1000 / (√3 × VL-L × PF) on three-phase. 10 kW on a 400 V three-phase supply at PF 0.8 is 10000 / (1.732 × 400 × 0.8) = 18.0 A per line. At PF 1 the same 10 kW draws 14.4 A.

Enter the load in kilowatts and the supply voltage, choose single or three-phase (or DC) and set the power factor. The result is the current in each line conductor. Generators, motors, heaters and welders are all specified in kW; this turns that figure into the amps the cable and breaker have to carry.

Free download

Get the printable wire size charts

NEC 310.16 ampacity for copper and aluminium at 60, 75 and 90 C, how far each size runs before voltage drop bites, standard breaker sizes and AWG to mm2. Three pages, made for the van door.

We store your email with EmailOctopus to send the charts and occasional wiring and calculator tips, nothing else. Unsubscribe any time. Privacy policy.

How It Works

The formula

DC:  I = kW × 1000 / V

Single-phase AC:  I = kW × 1000 / (V × PF)

Three-phase AC:  I = kW × 1000 / (√3 × VL-L × PF)

The factor of 1000 converts kilowatts to watts. V is line-to-line voltage for three-phase. Generator sets are rated at PF 0.8 by convention, resistive heating at PF 1.

Worked examples

10 kW three-phase at 400 V, PF 0.8

I = 10 × 1000 / (1.732 × 400 × 0.8) = 10000 / 554.3 = 18.0 A per line. At unity power factor the same 10 kW would be 14.4 A; the lower power factor costs 25% more current for the same real power.

A 9.5 kW electric shower at 230 V

Single-phase and resistive, so PF = 1: I = 9500 / 230 = 41.3 A. That current is why a 9.5 kW shower sits on a 45 A or 50 A protective device and 10 mm² cable rather than the 6 mm² used for lighter loads.

A 3 kW heater at 240 V

I = 3000 / 240 = 12.5 A. Resistive heating draws a steady current for as long as it runs, so a heater like this is a continuous load and belongs on a circuit rated at least 125% of 12.5 A, which is 15.6 A, so a 20 A circuit.

A 50 kW generator at 480 V three-phase

Generators quote kW at PF 0.8: I = 50000 / (1.732 × 480 × 0.8) = 50000 / 665.1 = 75.2 A. The set is also rated 62.5 kVA (50 / 0.8), and at 480 V that kVA gives the same 75.2 A.

kW to amps, single-phase (PF 1)

Unity power factor, which is right for heaters and resistive loads. Divide by the power factor for anything else.

kW 120 V 208 V 230 V 240 V 277 V
0.5 kW 4.167 2.404 2.174 2.083 1.805
1 kW 8.333 4.808 4.348 4.167 3.610
1.5 kW 12.50 7.212 6.522 6.250 5.415
2 kW 16.67 9.615 8.696 8.333 7.220
2.5 kW 20.83 12.02 10.87 10.42 9.025
3 kW 25.00 14.42 13.04 12.50 10.83
4 kW 33.33 19.23 17.39 16.67 14.44
5 kW 41.67 24.04 21.74 20.83 18.05
6 kW 50.00 28.85 26.09 25.00 21.66
7.5 kW 62.50 36.06 32.61 31.25 27.08
9 kW 75.00 43.27 39.13 37.50 32.49
10 kW 83.33 48.08 43.48 41.67 36.10
12 kW 100.0 57.69 52.17 50.00 43.32
15 kW 125.0 72.12 65.22 62.50 54.15
20 kW 166.7 96.15 86.96 83.33 72.20
25 kW 208.3 120.2 108.7 104.2 90.25
30 kW 250.0 144.2 130.4 125.0 108.3

kW to amps, three-phase (PF 0.8)

Line current at line-to-line voltage and a 0.8 power factor, the usual rating point for generator sets and motor loads. Multiply by 0.8 for a unity power factor load.

kW 208 V 400 V 415 V 480 V
1 kW 3.470 1.804 1.739 1.504
2 kW 6.939 3.608 3.478 3.007
3 kW 10.41 5.413 5.217 4.511
5 kW 17.35 9.021 8.695 7.518
7.5 kW 26.02 13.53 13.04 11.28
10 kW 34.70 18.04 17.39 15.04
15 kW 52.04 27.06 26.09 22.55
20 kW 69.39 36.08 34.78 30.07
25 kW 86.74 45.11 43.48 37.59
30 kW 104.1 54.13 52.17 45.11
37 kW 128.4 66.76 64.34 55.63
45 kW 156.1 81.19 78.26 67.66
55 kW 190.8 99.23 95.65 82.69
75 kW 260.2 135.3 130.4 112.8
90 kW 312.3 162.4 156.5 135.3
110 kW 381.7 198.5 191.3 165.4
150 kW 520.4 270.6 260.9 225.5
200 kW 693.9 360.8 347.8 300.7
250 kW 867.4 451.1 434.8 375.9
300 kW 1,041 541.3 521.7 451.1

Frequently Asked Questions

How many amps is 1 kW?

At 120 V single-phase, 1 kW is 8.33 A; at 230 V it is 4.35 A; at 240 V it is 4.17 A. On a 400 V three-phase supply at unity power factor, 1 kW is 1.44 A per line. All of those assume a resistive load; a motor at PF 0.8 draws 25% more.

Is kW the same as kVA?

No. kW is real power; kVA is apparent power, and kW = kVA × power factor. A generator nameplate usually gives both, for example 50 kW / 62.5 kVA at PF 0.8. If your figure is in kVA, use the kVA to amps calculator instead; no power factor is needed there.

What power factor should I use for a generator or a motor?

Generator sets are rated at 0.8 lagging, so use 0.8 unless the set is specified otherwise. Induction motors run at 0.8 to 0.9 at full load and lower at part load; use the nameplate figure. Resistive heating, immersion heaters and electric showers are 1.

Why does three-phase give fewer amps per kW?

The power is carried on three conductors instead of two, and the line-to-line voltage is √3 times the line-to-neutral voltage. Together that puts the line current at 1 / √3 of what the same kW would draw single-phase at the line-to-line voltage: 10 kW at 400 V is 14.4 A three-phase against 25 A single-phase.

How do I go the other way, from amps to kW?

Multiply amps by volts (and by √3 for three-phase) and by the power factor, then divide by 1,000. The amps to kW calculator does this directly.