Amps to kW Calculator
To convert amps to kW, multiply the amps by the volts and the power factor, then divide by 1,000: kW = V × I × PF / 1000 on single-phase, or kW = √3 × VL-L × I × PF / 1000 on three-phase. 30 A at 240 V single-phase on a resistive load (PF 1) is 240 × 30 / 1000 = 7.2 kW. Without the power factor the result is kVA, which equals kW only at PF 1.
Enter the current you measured or read off the nameplate, the voltage, and the phase and power factor. The result is real power in kilowatts, the unit a generator, a service or an energy bill is expressed in. A clamp meter gives you amps; this page turns that reading into kW.
Free download
Get the printable wire size charts
NEC 310.16 ampacity for copper and aluminium at 60, 75 and 90 C, how far each size runs before voltage drop bites, standard breaker sizes and AWG to mm2. Three pages, made for the van door.
How It Works
The formula
DC: kW = V × I / 1000
Single-phase AC: kW = V × I × PF / 1000
Three-phase AC: kW = √3 × VL-L × I × PF / 1000
I is the line current in amps. Leave the power factor out and you get kVA rather than kW; the calculator shows both.
Worked examples
30 A at 240 V single-phase
A resistive load, so PF = 1: kW = 240 × 30 / 1000 = 7.2 kW. This is the full rating of a 30 A, 240 V circuit; the continuous limit is 80% of it, 24 A or 5.76 kW.
63 A three-phase at 400 V, PF 0.9
kW = 1.732 × 400 × 63 × 0.9 / 1000 = 39.3 kW. The same 63 A supply is 43.6 kVA; the 0.9 power factor is the gap between the two.
A 200 A clamp reading on a 208 V three-phase panel
Mixed commercial loads are typically around PF 0.85: kW = 1.732 × 208 × 200 × 0.85 / 1000 = 61.2 kW. Read all three phases; if they are unbalanced, average them or work each phase out separately as single-phase at 120 V.
100 A from a 48 V DC bank
kW = 48 × 100 / 1000 = 4.8 kW. At that rate a 400 Ah bank discharged to 80% depth (15.4 kWh usable) lasts a little over three hours.
A 48 A EV charger at 240 V
A charger is resistive enough to take PF = 1: kW = 240 × 48 / 1000 = 11.52 kW, the 11.5 kW on the box. It draws that for hours, so it is a continuous load and sits on a 60 A circuit (48 × 1.25); the EV charger wire and breaker guide covers the cable. On a 208 V apartment supply the same 48 A is only 9.98 kW.
16 A three-phase at 400 V, PF 1
kW = 1.732 × 400 × 16 × 1 / 1000 = 11.09 kW. This is why a UK or European 11 kW wallbox is a 16 A three-phase unit: the same 16 A on a single-phase 230 V supply is only 3.68 kW. Three phases at 32 A give 22.2 kW, the other common rating.
Amps to kW, single-phase (PF 1)
Kilowatts at unity power factor. Multiply by the power factor for motor or electronic loads. 208 V is two legs of a 208Y/120 supply, the usual single-phase circuit in apartment blocks and light commercial buildings.
| A | 120 V | 208 V | 230 V | 240 V | 277 V |
|---|---|---|---|---|---|
| 5 A | 0.600 | 1.040 | 1.150 | 1.200 | 1.385 |
| 10 A | 1.200 | 2.080 | 2.300 | 2.400 | 2.770 |
| 13 A | 1.560 | 2.704 | 2.990 | 3.120 | 3.601 |
| 15 A | 1.800 | 3.120 | 3.450 | 3.600 | 4.155 |
| 16 A | 1.920 | 3.328 | 3.680 | 3.840 | 4.432 |
| 20 A | 2.400 | 4.160 | 4.600 | 4.800 | 5.540 |
| 25 A | 3.000 | 5.200 | 5.750 | 6.000 | 6.925 |
| 30 A | 3.600 | 6.240 | 6.900 | 7.200 | 8.310 |
| 32 A | 3.840 | 6.656 | 7.360 | 7.680 | 8.864 |
| 40 A | 4.800 | 8.320 | 9.200 | 9.600 | 11.08 |
| 48 A | 5.760 | 9.984 | 11.04 | 11.52 | 13.30 |
| 50 A | 6.000 | 10.40 | 11.50 | 12.00 | 13.85 |
| 60 A | 7.200 | 12.48 | 13.80 | 14.40 | 16.62 |
| 63 A | 7.560 | 13.10 | 14.49 | 15.12 | 17.45 |
| 80 A | 9.600 | 16.64 | 18.40 | 19.20 | 22.16 |
| 100 A | 12.00 | 20.80 | 23.00 | 24.00 | 27.70 |
| 125 A | 15.00 | 26.00 | 28.75 | 30.00 | 34.63 |
| 150 A | 18.00 | 31.20 | 34.50 | 36.00 | 41.55 |
| 200 A | 24.00 | 41.60 | 46.00 | 48.00 | 55.40 |
Amps to kW, three-phase (PF 0.8)
Balanced three-phase load at line-to-line voltage and PF 0.8. Divide by 0.8 for the unity power factor figure, which is also the kVA.
| A | 208 V | 400 V | 415 V | 480 V |
|---|---|---|---|---|
| 10 A | 2.882 | 5.543 | 5.750 | 6.651 |
| 16 A | 4.611 | 8.868 | 9.201 | 10.64 |
| 20 A | 5.764 | 11.09 | 11.50 | 13.30 |
| 25 A | 7.205 | 13.86 | 14.38 | 16.63 |
| 32 A | 9.223 | 17.74 | 18.40 | 21.28 |
| 40 A | 11.53 | 22.17 | 23.00 | 26.60 |
| 50 A | 14.41 | 27.71 | 28.75 | 33.26 |
| 63 A | 18.16 | 34.92 | 36.23 | 41.90 |
| 80 A | 23.06 | 44.34 | 46.00 | 53.21 |
| 100 A | 28.82 | 55.43 | 57.50 | 66.51 |
| 125 A | 36.03 | 69.28 | 71.88 | 83.14 |
| 160 A | 46.11 | 88.68 | 92.01 | 106.4 |
| 200 A | 57.64 | 110.9 | 115.0 | 133.0 |
| 250 A | 72.05 | 138.6 | 143.8 | 166.3 |
| 400 A | 115.3 | 221.7 | 230.0 | 266.0 |
Amps to kW, three-phase at PF 0.9 and PF 1
PF 0.9 is a modern induction motor at full load or a corrected industrial supply; PF 1 is resistive heating, immersion heaters and EV charging. Between this table and the PF 0.8 one above, read the column nearest the load's power factor.
| A | 208 V, PF 0.9 | 208 V, PF 1 | 400 V, PF 0.9 | 400 V, PF 1 | 480 V, PF 0.9 | 480 V, PF 1 |
|---|---|---|---|---|---|---|
| 10 A | 3.242 | 3.603 | 6.235 | 6.928 | 7.482 | 8.314 |
| 16 A | 5.188 | 5.764 | 9.977 | 11.09 | 11.97 | 13.30 |
| 20 A | 6.485 | 7.205 | 12.47 | 13.86 | 14.96 | 16.63 |
| 25 A | 8.106 | 9.007 | 15.59 | 17.32 | 18.71 | 20.78 |
| 32 A | 10.38 | 11.53 | 19.95 | 22.17 | 23.94 | 26.60 |
| 40 A | 12.97 | 14.41 | 24.94 | 27.71 | 29.93 | 33.26 |
| 50 A | 16.21 | 18.01 | 31.18 | 34.64 | 37.41 | 41.57 |
| 63 A | 20.43 | 22.70 | 39.28 | 43.65 | 47.14 | 52.38 |
| 80 A | 25.94 | 28.82 | 49.88 | 55.43 | 59.86 | 66.51 |
| 100 A | 32.42 | 36.03 | 62.35 | 69.28 | 74.82 | 83.14 |
| 125 A | 40.53 | 45.03 | 77.94 | 86.60 | 93.53 | 103.9 |
| 160 A | 51.88 | 57.64 | 99.77 | 110.9 | 119.7 | 133.0 |
| 200 A | 64.85 | 72.05 | 124.7 | 138.6 | 149.6 | 166.3 |
| 250 A | 81.06 | 90.07 | 155.9 | 173.2 | 187.1 | 207.8 |
| 400 A | 129.7 | 144.1 | 249.4 | 277.1 | 299.3 | 332.6 |
Amps to kW, DC battery and solar systems
DC power is volts times amps, with no power factor. This is the battery side of an inverter: divide by the inverter efficiency, typically 0.9 to 0.95, for the AC output.
| A | 12 V | 24 V | 36 V | 48 V |
|---|---|---|---|---|
| 5 A | 0.060 | 0.120 | 0.180 | 0.240 |
| 10 A | 0.120 | 0.240 | 0.360 | 0.480 |
| 20 A | 0.240 | 0.480 | 0.720 | 0.960 |
| 30 A | 0.360 | 0.720 | 1.080 | 1.440 |
| 40 A | 0.480 | 0.960 | 1.440 | 1.920 |
| 50 A | 0.600 | 1.200 | 1.800 | 2.400 |
| 75 A | 0.900 | 1.800 | 2.700 | 3.600 |
| 100 A | 1.200 | 2.400 | 3.600 | 4.800 |
| 125 A | 1.500 | 3.000 | 4.500 | 6.000 |
| 150 A | 1.800 | 3.600 | 5.400 | 7.200 |
| 200 A | 2.400 | 4.800 | 7.200 | 9.600 |
| 250 A | 3.000 | 6.000 | 9.000 | 12.00 |
| 300 A | 3.600 | 7.200 | 10.80 | 14.40 |
| 400 A | 4.800 | 9.600 | 14.40 | 19.20 |
Frequently Asked Questions
How many kW is 100 amps?
At 120 V single-phase, 100 A is 12 kW. At 240 V it is 24 kW. On a 400 V three-phase supply at unity power factor it is 69.3 kW. The voltage and the phase matter as much as the amps.
What is the difference between kW and kWh?
kW is a rate: how fast energy is being used right now. kWh is a quantity: kW multiplied by the hours it ran. A 7.2 kW load running for two hours uses 14.4 kWh, and that is what the meter bills. The energy cost calculator does the hours-and-tariff step.
Which power factor should I use for a whole panel?
A mixed residential or commercial panel usually measures between 0.85 and 0.95. If you are doing a load calculation rather than reading a meter, note that NEC Article 220 works in volt-amps, not watts, so leave the power factor at 1 and read the kVA figure the calculator also shows.
How do I get the shaft power of a motor from its amps?
The formula gives electrical input power. Multiply the input kW by the motor efficiency for the mechanical output; a motor drawing 39.3 kW at 92% efficiency delivers about 36.2 kW at the shaft, which is 48.5 hp.
What is the maximum kW on a 200 A service?
At 240 V single-phase, 200 A is 48 kVA, and at unity power factor 48 kW. Continuous loads are held to 80% of the rating, so the practical continuous ceiling is 160 A, or 38.4 kW.
Other electrical conversions
Related Calculators
Continue with these related electrical tools
kW to Amps Calculator
Line current from kilowatts for generators, motors and heaters
Amps to Watts Calculator
Real power from current, voltage and power factor
Amps to kVA Calculator
Apparent power from current and voltage for sizing supply equipment