Amps to kW Calculator

To convert amps to kW, multiply the amps by the volts and the power factor, then divide by 1,000: kW = V × I × PF / 1000 on single-phase, or kW = √3 × VL-L × I × PF / 1000 on three-phase. 30 A at 240 V single-phase on a resistive load (PF 1) is 240 × 30 / 1000 = 7.2 kW. Without the power factor the result is kVA, which equals kW only at PF 1.

Enter the current you measured or read off the nameplate, the voltage, and the phase and power factor. The result is real power in kilowatts, the unit a generator, a service or an energy bill is expressed in. A clamp meter gives you amps; this page turns that reading into kW.

Free download

Get the printable wire size charts

NEC 310.16 ampacity for copper and aluminium at 60, 75 and 90 C, how far each size runs before voltage drop bites, standard breaker sizes and AWG to mm2. Three pages, made for the van door.

We store your email with EmailOctopus to send the charts and occasional wiring and calculator tips, nothing else. Unsubscribe any time. Privacy policy.

How It Works

The formula

DC:  kW = V × I / 1000

Single-phase AC:  kW = V × I × PF / 1000

Three-phase AC:  kW = √3 × VL-L × I × PF / 1000

I is the line current in amps. Leave the power factor out and you get kVA rather than kW; the calculator shows both.

Worked examples

30 A at 240 V single-phase

A resistive load, so PF = 1: kW = 240 × 30 / 1000 = 7.2 kW. This is the full rating of a 30 A, 240 V circuit; the continuous limit is 80% of it, 24 A or 5.76 kW.

63 A three-phase at 400 V, PF 0.9

kW = 1.732 × 400 × 63 × 0.9 / 1000 = 39.3 kW. The same 63 A supply is 43.6 kVA; the 0.9 power factor is the gap between the two.

A 200 A clamp reading on a 208 V three-phase panel

Mixed commercial loads are typically around PF 0.85: kW = 1.732 × 208 × 200 × 0.85 / 1000 = 61.2 kW. Read all three phases; if they are unbalanced, average them or work each phase out separately as single-phase at 120 V.

100 A from a 48 V DC bank

kW = 48 × 100 / 1000 = 4.8 kW. At that rate a 400 Ah bank discharged to 80% depth (15.4 kWh usable) lasts a little over three hours.

A 48 A EV charger at 240 V

A charger is resistive enough to take PF = 1: kW = 240 × 48 / 1000 = 11.52 kW, the 11.5 kW on the box. It draws that for hours, so it is a continuous load and sits on a 60 A circuit (48 × 1.25); the EV charger wire and breaker guide covers the cable. On a 208 V apartment supply the same 48 A is only 9.98 kW.

16 A three-phase at 400 V, PF 1

kW = 1.732 × 400 × 16 × 1 / 1000 = 11.09 kW. This is why a UK or European 11 kW wallbox is a 16 A three-phase unit: the same 16 A on a single-phase 230 V supply is only 3.68 kW. Three phases at 32 A give 22.2 kW, the other common rating.

Amps to kW, single-phase (PF 1)

Kilowatts at unity power factor. Multiply by the power factor for motor or electronic loads. 208 V is two legs of a 208Y/120 supply, the usual single-phase circuit in apartment blocks and light commercial buildings.

A 120 V 208 V 230 V 240 V 277 V
5 A 0.600 1.040 1.150 1.200 1.385
10 A 1.200 2.080 2.300 2.400 2.770
13 A 1.560 2.704 2.990 3.120 3.601
15 A 1.800 3.120 3.450 3.600 4.155
16 A 1.920 3.328 3.680 3.840 4.432
20 A 2.400 4.160 4.600 4.800 5.540
25 A 3.000 5.200 5.750 6.000 6.925
30 A 3.600 6.240 6.900 7.200 8.310
32 A 3.840 6.656 7.360 7.680 8.864
40 A 4.800 8.320 9.200 9.600 11.08
48 A 5.760 9.984 11.04 11.52 13.30
50 A 6.000 10.40 11.50 12.00 13.85
60 A 7.200 12.48 13.80 14.40 16.62
63 A 7.560 13.10 14.49 15.12 17.45
80 A 9.600 16.64 18.40 19.20 22.16
100 A 12.00 20.80 23.00 24.00 27.70
125 A 15.00 26.00 28.75 30.00 34.63
150 A 18.00 31.20 34.50 36.00 41.55
200 A 24.00 41.60 46.00 48.00 55.40

Amps to kW, three-phase (PF 0.8)

Balanced three-phase load at line-to-line voltage and PF 0.8. Divide by 0.8 for the unity power factor figure, which is also the kVA.

A 208 V 400 V 415 V 480 V
10 A 2.882 5.543 5.750 6.651
16 A 4.611 8.868 9.201 10.64
20 A 5.764 11.09 11.50 13.30
25 A 7.205 13.86 14.38 16.63
32 A 9.223 17.74 18.40 21.28
40 A 11.53 22.17 23.00 26.60
50 A 14.41 27.71 28.75 33.26
63 A 18.16 34.92 36.23 41.90
80 A 23.06 44.34 46.00 53.21
100 A 28.82 55.43 57.50 66.51
125 A 36.03 69.28 71.88 83.14
160 A 46.11 88.68 92.01 106.4
200 A 57.64 110.9 115.0 133.0
250 A 72.05 138.6 143.8 166.3
400 A 115.3 221.7 230.0 266.0

Amps to kW, three-phase at PF 0.9 and PF 1

PF 0.9 is a modern induction motor at full load or a corrected industrial supply; PF 1 is resistive heating, immersion heaters and EV charging. Between this table and the PF 0.8 one above, read the column nearest the load's power factor.

A 208 V, PF 0.9 208 V, PF 1 400 V, PF 0.9 400 V, PF 1 480 V, PF 0.9 480 V, PF 1
10 A 3.242 3.603 6.235 6.928 7.482 8.314
16 A 5.188 5.764 9.977 11.09 11.97 13.30
20 A 6.485 7.205 12.47 13.86 14.96 16.63
25 A 8.106 9.007 15.59 17.32 18.71 20.78
32 A 10.38 11.53 19.95 22.17 23.94 26.60
40 A 12.97 14.41 24.94 27.71 29.93 33.26
50 A 16.21 18.01 31.18 34.64 37.41 41.57
63 A 20.43 22.70 39.28 43.65 47.14 52.38
80 A 25.94 28.82 49.88 55.43 59.86 66.51
100 A 32.42 36.03 62.35 69.28 74.82 83.14
125 A 40.53 45.03 77.94 86.60 93.53 103.9
160 A 51.88 57.64 99.77 110.9 119.7 133.0
200 A 64.85 72.05 124.7 138.6 149.6 166.3
250 A 81.06 90.07 155.9 173.2 187.1 207.8
400 A 129.7 144.1 249.4 277.1 299.3 332.6

Amps to kW, DC battery and solar systems

DC power is volts times amps, with no power factor. This is the battery side of an inverter: divide by the inverter efficiency, typically 0.9 to 0.95, for the AC output.

A 12 V 24 V 36 V 48 V
5 A 0.060 0.120 0.180 0.240
10 A 0.120 0.240 0.360 0.480
20 A 0.240 0.480 0.720 0.960
30 A 0.360 0.720 1.080 1.440
40 A 0.480 0.960 1.440 1.920
50 A 0.600 1.200 1.800 2.400
75 A 0.900 1.800 2.700 3.600
100 A 1.200 2.400 3.600 4.800
125 A 1.500 3.000 4.500 6.000
150 A 1.800 3.600 5.400 7.200
200 A 2.400 4.800 7.200 9.600
250 A 3.000 6.000 9.000 12.00
300 A 3.600 7.200 10.80 14.40
400 A 4.800 9.600 14.40 19.20

Frequently Asked Questions

How many kW is 100 amps?

At 120 V single-phase, 100 A is 12 kW. At 240 V it is 24 kW. On a 400 V three-phase supply at unity power factor it is 69.3 kW. The voltage and the phase matter as much as the amps.

What is the difference between kW and kWh?

kW is a rate: how fast energy is being used right now. kWh is a quantity: kW multiplied by the hours it ran. A 7.2 kW load running for two hours uses 14.4 kWh, and that is what the meter bills. The energy cost calculator does the hours-and-tariff step.

Which power factor should I use for a whole panel?

A mixed residential or commercial panel usually measures between 0.85 and 0.95. If you are doing a load calculation rather than reading a meter, note that NEC Article 220 works in volt-amps, not watts, so leave the power factor at 1 and read the kVA figure the calculator also shows.

How do I get the shaft power of a motor from its amps?

The formula gives electrical input power. Multiply the input kW by the motor efficiency for the mechanical output; a motor drawing 39.3 kW at 92% efficiency delivers about 36.2 kW at the shaft, which is 48.5 hp.

What is the maximum kW on a 200 A service?

At 240 V single-phase, 200 A is 48 kVA, and at unity power factor 48 kW. Continuous loads are held to 80% of the rating, so the practical continuous ceiling is 160 A, or 38.4 kW.

Embed This Calculator

Add this free calculator to your website. Copy the code below and paste it into your page.