Amps to Watts Calculator
Enter the current in amps and the voltage the load runs at. The result is real power in watts, the figure that turns into heat, light or motion and that the electricity meter charges for. On AC the power factor scales it down; on DC there is no power factor.
Free download
Get the printable wire size charts
NEC 310.16 ampacity for copper and aluminium at 60, 75 and 90 C, how far each size runs before voltage drop bites, standard breaker sizes and AWG to mm2. Three pages, made for the van door.
How It Works
The formula
DC: P = V × I
Single-phase AC: P = V × I × PF
Three-phase AC: P = √3 × VL-L × I × PF
P is real power in watts, V the voltage, I the current in amps and PF the power factor. Without the power factor the product V × I is apparent power in volt-amps (VA), not watts.
Worked examples
A 13 A plug at 230 V
The largest UK plug-in appliance is fused at 13 A. At 230 V and PF 1 that is P = 230 × 13 = 2,990 W, which is why 3 kW is the ceiling for a kettle, a fan heater or a single-socket load.
A 20 A circuit at 120 V
A 20 A branch circuit at 120 V can deliver P = 120 × 20 = 2,400 W, but only for short periods. A load that runs for three hours or more is limited to 80% of the breaker, 16 A, which is 120 × 16 = 1,920 W continuous.
32 A three-phase at 400 V, PF 0.9
A 32 A three-phase machine supply at 400 V line-to-line with a 0.9 power factor: P = 1.732 × 400 × 32 × 0.9 = 19,953 W, just under 20 kW.
50 A from a 48 V battery bank
An inverter pulling 50 A from a 48 V DC battery: P = 48 × 50 = 2,400 W. Divide by the inverter efficiency to see what reaches the AC side; at 92% that is about 2,208 W.
Amps to watts, single-phase and DC (PF 1)
Watts at unity power factor. Multiply by the power factor for a motor or electronic load: 10 A at 120 V and PF 0.8 is 1,200 × 0.8 = 960 W.
| A | 12 V | 24 V | 48 V | 120 V | 230 V | 240 V |
|---|---|---|---|---|---|---|
| 1 A | 12.00 | 24.00 | 48.00 | 120.0 | 230.0 | 240.0 |
| 2 A | 24.00 | 48.00 | 96.00 | 240.0 | 460.0 | 480.0 |
| 3 A | 36.00 | 72.00 | 144.0 | 360.0 | 690.0 | 720.0 |
| 5 A | 60.00 | 120.0 | 240.0 | 600.0 | 1,150 | 1,200 |
| 8 A | 96.00 | 192.0 | 384.0 | 960.0 | 1,840 | 1,920 |
| 10 A | 120.0 | 240.0 | 480.0 | 1,200 | 2,300 | 2,400 |
| 13 A | 156.0 | 312.0 | 624.0 | 1,560 | 2,990 | 3,120 |
| 15 A | 180.0 | 360.0 | 720.0 | 1,800 | 3,450 | 3,600 |
| 16 A | 192.0 | 384.0 | 768.0 | 1,920 | 3,680 | 3,840 |
| 20 A | 240.0 | 480.0 | 960.0 | 2,400 | 4,600 | 4,800 |
| 25 A | 300.0 | 600.0 | 1,200 | 3,000 | 5,750 | 6,000 |
| 30 A | 360.0 | 720.0 | 1,440 | 3,600 | 6,900 | 7,200 |
| 32 A | 384.0 | 768.0 | 1,536 | 3,840 | 7,360 | 7,680 |
| 40 A | 480.0 | 960.0 | 1,920 | 4,800 | 9,200 | 9,600 |
| 50 A | 600.0 | 1,200 | 2,400 | 6,000 | 11,500 | 12,000 |
| 60 A | 720.0 | 1,440 | 2,880 | 7,200 | 13,800 | 14,400 |
| 100 A | 1,200 | 2,400 | 4,800 | 12,000 | 23,000 | 24,000 |
Amps to watts, three-phase (PF 1)
Line current at line-to-line voltage, balanced load, unity power factor.
| A | 208 V | 400 V | 415 V | 480 V |
|---|---|---|---|---|
| 10 A | 3,603 | 6,928 | 7,188 | 8,314 |
| 16 A | 5,764 | 11,085 | 11,501 | 13,302 |
| 20 A | 7,205 | 13,856 | 14,376 | 16,628 |
| 32 A | 11,529 | 22,170 | 23,002 | 26,604 |
| 50 A | 18,013 | 34,641 | 35,940 | 41,569 |
| 63 A | 22,697 | 43,648 | 45,284 | 52,377 |
| 100 A | 36,027 | 69,282 | 71,880 | 83,138 |
| 200 A | 72,053 | 138,564 | 143,760 | 166,277 |
Frequently Asked Questions
How many watts is 15 amps?
At 120 V, 15 A is 1,800 W. At 240 V it is 3,600 W, and at 12 V DC it is 180 W. Current has to be paired with a voltage before it means anything in watts.
What is the difference between watts and volt-amps?
Volt-amps (VA) are volts times amps with no correction: apparent power. Watts are the part that does work: real power. The ratio between them is the power factor, so W = VA × PF. For a heater they are equal; for a motor at PF 0.85, 1,000 VA is only 850 W.
Why can a 20 A circuit only supply 1,920 W continuously?
NEC 210.20(A) limits a continuous load to 80% of the overcurrent device rating, so a 20 A breaker serves 16 A continuously. At 120 V that is 1,920 W. The full 2,400 W is available to loads that cycle or run under three hours.
How do I convert amps to kilowatts?
Work out the watts and divide by 1,000, or use the amps to kW calculator, which does the same job with the answer in kW. 30 A at 240 V is 7,200 W, which is 7.2 kW.
Should I use the breaker rating or the actual current?
The actual current: the nameplate figure or a clamp-meter reading. The breaker rating tells you the most the circuit may carry, not what the load draws. A 20 A circuit with a 3 A lamp on it is drawing 360 W, not 2,400 W.
Other electrical conversions
Related Calculators
Continue with these related electrical tools
Watts to Amps Calculator
Current from power and voltage, DC, single and three-phase
Amps to kW Calculator
Kilowatts from a current reading, single or three-phase
Watts Amps Volts Calculator
Convert between watts, volts and amps (DC, 1-phase, 3-phase)
Energy Cost Calculator (kWh)
Energy use and running cost from power, hours and rate
Embed This Calculator
Add this free calculator to your website. Copy the code below and paste it into your page.