Watts to Amps Calculator

To convert watts to amps, divide the watts by the volts: I = P / V on DC, I = P / (V × PF) on single-phase AC and I = P / (√3 × VL-L × PF) on three-phase, where PF is the power factor. A 1,500 W heater on 120 V is resistive (PF 1) and draws 1500 / 120 = 12.5 A. The voltage changes the answer: the same 1,500 W at 240 V draws 6.25 A.

Enter the power in watts and the supply voltage. For AC loads pick single or three-phase and set the power factor; DC needs only the two numbers. The result is the current the load draws in amps, which is the figure you need before choosing a breaker or a conductor.

Free download

Get the printable wire size charts

NEC 310.16 ampacity for copper and aluminium at 60, 75 and 90 C, how far each size runs before voltage drop bites, standard breaker sizes and AWG to mm2. Three pages, made for the van door.

We store your email with EmailOctopus to send the charts and occasional wiring and calculator tips, nothing else. Unsubscribe any time. Privacy policy.

How It Works

The formula

DC:  I = P / V

Single-phase AC:  I = P / (V × PF)

Three-phase AC:  I = P / (√3 × VL-L × PF)

I is current in amps, P is real power in watts, V is the supply voltage (line-to-line for three-phase) and PF is the power factor, 1 for a purely resistive load. √3 is about 1.732.

Worked examples

1500 watts to amps at 120 V

A 1,500 W space heater on a 120 V single-phase circuit is resistive, so PF = 1: I = 1500 / 120 = 12.5 A. That is 83% of a 15 A circuit on its own, which is why running two of them from the same circuit trips the breaker.

The same 1500 W at 240 V

Move the load to 240 V and the current halves: I = 1500 / 240 = 6.25 A. Power has not changed; a higher voltage simply delivers it with less current, which is the whole reason large loads are wired at 240 V.

10,000 W three-phase at 400 V, PF 0.85

A 10 kW three-phase motor load on a 400 V line-to-line supply at a power factor of 0.85: I = 10000 / (1.732 × 400 × 0.85) = 10000 / 588.9 = 17.0 A per line.

100 W at 12 V DC

A 100 W load on a 12 V battery draws I = 100 / 12 = 8.33 A. Low-voltage DC currents are high for modest power, which is why 12 V cable gets thick quickly.

Watts to amps, single-phase and DC (PF 1)

Amps at unity power factor. For an AC load with a lower power factor, divide the figure by the power factor: 1,500 W at 120 V and PF 0.8 is 12.5 / 0.8 = 15.6 A.

W 12 V 24 V 48 V 120 V 208 V 240 V 277 V
100 W 8.333 4.167 2.083 0.833 0.481 0.417 0.361
200 W 16.67 8.333 4.167 1.667 0.962 0.833 0.722
300 W 25.00 12.50 6.250 2.500 1.442 1.250 1.083
400 W 33.33 16.67 8.333 3.333 1.923 1.667 1.444
500 W 41.67 20.83 10.42 4.167 2.404 2.083 1.805
600 W 50.00 25.00 12.50 5.000 2.885 2.500 2.166
750 W 62.50 31.25 15.63 6.250 3.606 3.125 2.708
800 W 66.67 33.33 16.67 6.667 3.846 3.333 2.888
1,000 W 83.33 41.67 20.83 8.333 4.808 4.167 3.610
1,200 W 100.0 50.00 25.00 10.00 5.769 5.000 4.332
1,500 W 125.0 62.50 31.25 12.50 7.212 6.250 5.415
1,800 W 150.0 75.00 37.50 15.00 8.654 7.500 6.498
2,000 W 166.7 83.33 41.67 16.67 9.615 8.333 7.220
2,500 W 208.3 104.2 52.08 20.83 12.02 10.42 9.025
3,000 W 250.0 125.0 62.50 25.00 14.42 12.50 10.83
4,000 W 333.3 166.7 83.33 33.33 19.23 16.67 14.44
5,000 W 416.7 208.3 104.2 41.67 24.04 20.83 18.05
7,500 W 625.0 312.5 156.3 62.50 36.06 31.25 27.08
10,000 W 833.3 416.7 208.3 83.33 48.08 41.67 36.10

Watts to amps, three-phase (PF 1)

Line current per phase conductor at line-to-line voltage and unity power factor.

W 208 V 400 V 415 V 480 V
1,000 W 2.776 1.443 1.391 1.203
2,000 W 5.551 2.887 2.782 2.406
3,000 W 8.327 4.330 4.174 3.608
5,000 W 13.88 7.217 6.956 6.014
7,500 W 20.82 10.83 10.43 9.021
10,000 W 27.76 14.43 13.91 12.03
15,000 W 41.64 21.65 20.87 18.04
20,000 W 55.51 28.87 27.82 24.06
30,000 W 83.27 43.30 41.74 36.08
50,000 W 138.8 72.17 69.56 60.14

Frequently Asked Questions

How many amps is 1500 watts?

It depends on the voltage. At 120 V single-phase, 1,500 W draws 12.5 A; at 240 V it draws 6.25 A; at 12 V DC it draws 125 A. Watts alone do not fix the current, which is why the calculator asks for the voltage.

Why does the calculator need the voltage?

Because watts are power and amps are current, and the two are linked by voltage: P = V × I. The same power at twice the voltage flows as half the current. A 3,000 W load is 25 A at 120 V but 12.5 A at 240 V.

What power factor should I use?

Use 1 for resistive loads: heaters, kettles, incandescent lamps, water heaters. Motors at full load are typically 0.8 to 0.9. Electronics and LED drivers without power factor correction can be 0.5 to 0.9. If the nameplate gives both watts and VA, the power factor is watts divided by VA.

Is the three-phase voltage line-to-line or line-to-neutral?

Line-to-line: 208 V, 400 V, 415 V or 480 V. If the only figure you have is line-to-neutral (120 V, 230 V or 277 V), multiply it by 1.732 to get line-to-line before using the three-phase formula.

Can I size a breaker or wire from this result?

It gives the load current, which is the starting point. A continuous load, one that runs three hours or more, needs a circuit rated at 125% of that current under NEC 210.19 and 210.20. Take the current to the breaker sizing calculator and then the wire size calculator.