HP to Amps Calculator
Enter the motor horsepower and the supply voltage, then the phase, power factor and efficiency. The result is the running current. A motor rated in horsepower is rated on its shaft output, so the electrical input, and the amps, are higher by the efficiency and the power factor. The defaults are the same conventions the motor FLA calculator uses.
Free download
Get the printable wire size charts
NEC 310.16 ampacity for copper and aluminium at 60, 75 and 90 C, how far each size runs before voltage drop bites, standard breaker sizes and AWG to mm2. Three pages, made for the van door.
How It Works
The formula
DC: I = hp × 746 / (V × η)
Single-phase AC: I = hp × 746 / (V × PF × η)
Three-phase AC: I = hp × 746 / (√3 × VL-L × PF × η)
One horsepower is 746 W. η is the motor efficiency as a decimal (0.9 for 90%) and PF the full-load power factor. Both come off the nameplate; without them the defaults are 0.9 and 0.85.
Worked examples
A 5 hp single-phase motor at 230 V
I = 5 × 746 / (230 × 0.85 × 0.9) = 3730 / 176.0 = 21.2 A. For comparison NEC Table 430.248 lists 28 A for a 5 hp, 230 V single-phase motor; the code table is deliberately conservative and is the figure the conductors and breaker must be sized from.
A 10 hp three-phase motor at 460 V
I = 10 × 746 / (1.732 × 460 × 0.85 × 0.9) = 7460 / 609.5 = 12.2 A. Table 430.250 gives 14 A for the same motor.
A 1 hp 24 V DC motor at 85% efficiency
DC has no power factor: I = 746 / (24 × 0.85) = 36.6 A. Low-voltage DC motors draw heavy current for their size, which is why a 1 hp winch or thruster needs cable that looks oversized for the job.
A 50 hp premium motor at 400 V, PF 0.88, 93% efficient
I = 50 × 746 / (1.732 × 400 × 0.88 × 0.93) = 37300 / 567.0 = 65.8 A. Better efficiency and power factor take real amps off the feeder: at the default 0.85 and 0.9 the same motor would show 70.4 A.
A 3/4 hp pump motor at 115 V
At the defaults: I = 0.75 × 746 / (115 × 0.85 × 0.9) = 559.5 / 88.0 = 6.36 A. NEC Table 430.248 lists 13.8 A, more than twice that. The gap is the motor, not the maths: a small capacitor-start motor can run nearer PF 0.65 and 65% efficiency, and at those figures the formula gives 559.5 / (115 × 0.65 × 0.65) = 11.5 A. Size the circuit from the 13.8 A.
A 3 hp three-phase motor on a 208 V supply
I = 3 × 746 / (1.732 × 208 × 0.85 × 0.9) = 2238 / 275.6 = 8.12 A, against 7.34 A for the same motor at 230 V. Table 430.250 has a separate 208 V column for this reason: 10.6 A at 208 V, 9.6 A at 230 V. A motor moved from a 230 V plant to a 208Y/120 building draws about 10% more current for the same shaft power.
HP to amps, single-phase motors: formula and NEC Table 430.248
Formula columns are the running current at PF 0.85 and 90% efficiency, the calculator defaults. NEC columns are Table 430.248, which NEC 430.6(A)(1) requires for the conductors, the disconnect and the branch-circuit breaker. On fractional-horsepower motors the code figure is two to three times the formula, because small single-phase motors run well below the default power factor and efficiency.
| hp | 115 V formula | 115 V NEC | 208 V formula | 208 V NEC | 230 V formula | 230 V NEC |
|---|---|---|---|---|---|---|
| 1/6 hp (0.17) | 1.413 | 4.4 | 0.781 | 2.4 | 0.707 | 2.2 |
| 1/4 hp (0.25) | 2.120 | 5.8 | 1.172 | 3.2 | 1.060 | 2.9 |
| 1/3 hp (0.33) | 2.827 | 7.2 | 1.563 | 4.0 | 1.413 | 3.6 |
| 1/2 hp (0.5) | 4.240 | 9.8 | 2.344 | 5.4 | 2.120 | 4.9 |
| 3/4 hp (0.75) | 6.360 | 13.8 | 3.516 | 7.6 | 3.180 | 6.9 |
| 1 hp | 8.480 | 16 | 4.688 | 8.8 | 4.240 | 8.0 |
| 1-1/2 hp (1.5) | 12.72 | 20 | 7.032 | 11 | 6.360 | 10 |
| 2 hp | 16.96 | 24 | 9.377 | 13.2 | 8.480 | 12 |
| 3 hp | 25.44 | 34 | 14.06 | 18.7 | 12.72 | 17 |
| 5 hp | 42.40 | 56 | 23.44 | 30.8 | 21.20 | 28 |
| 7-1/2 hp (7.5) | 63.60 | 80 | 35.16 | 44 | 31.80 | 40 |
| 10 hp | 84.80 | 100 | 46.88 | 55 | 42.40 | 50 |
HP to amps, three-phase motors: formula and NEC Table 430.250
Line current at line-to-line voltage. Formula columns use PF 0.85 and 90% efficiency; NEC columns are Table 430.250 for induction motors, the figure to size from. From about 150 hp the formula reads slightly above the table, because large motors beat PF 0.85 and 90% efficiency. 400 V has no NEC column because it is an IEC voltage; the motor FLA calculator page carries the full code tables, including 115 V, 200 V and 575 V.
| hp | 208 V formula | 208 V NEC | 230 V formula | 230 V NEC | 400 V formula | 460 V formula | 460 V NEC | 575 V formula |
|---|---|---|---|---|---|---|---|---|
| 1/2 hp (0.5) | 1.353 | 2.4 | 1.224 | 2.2 | 0.704 | 0.612 | 1.1 | 0.490 |
| 3/4 hp (0.75) | 2.030 | 3.5 | 1.836 | 3.2 | 1.056 | 0.918 | 1.6 | 0.734 |
| 1 hp | 2.707 | 4.6 | 2.448 | 4.2 | 1.408 | 1.224 | 2.1 | 0.979 |
| 1-1/2 hp (1.5) | 4.060 | 6.6 | 3.672 | 6.0 | 2.111 | 1.836 | 3.0 | 1.469 |
| 2 hp | 5.414 | 7.5 | 4.896 | 6.8 | 2.815 | 2.448 | 3.4 | 1.958 |
| 3 hp | 8.120 | 10.6 | 7.344 | 9.6 | 4.223 | 3.672 | 4.8 | 2.937 |
| 5 hp | 13.53 | 16.7 | 12.24 | 15.2 | 7.038 | 6.120 | 7.6 | 4.896 |
| 7-1/2 hp (7.5) | 20.30 | 24.2 | 18.36 | 22 | 10.56 | 9.180 | 11 | 7.344 |
| 10 hp | 27.07 | 30.8 | 24.48 | 28 | 14.08 | 12.24 | 14 | 9.791 |
| 15 hp | 40.60 | 46.2 | 36.72 | 42 | 21.11 | 18.36 | 21 | 14.69 |
| 20 hp | 54.14 | 59.4 | 48.96 | 54 | 28.15 | 24.48 | 27 | 19.58 |
| 25 hp | 67.67 | 74.8 | 61.20 | 68 | 35.19 | 30.60 | 34 | 24.48 |
| 30 hp | 81.20 | 88 | 73.44 | 80 | 42.23 | 36.72 | 40 | 29.37 |
| 40 hp | 108.3 | 114 | 97.91 | 104 | 56.30 | 48.96 | 52 | 39.17 |
| 50 hp | 135.3 | 143 | 122.4 | 130 | 70.38 | 61.20 | 65 | 48.96 |
| 60 hp | 162.4 | 169 | 146.9 | 154 | 84.45 | 73.44 | 77 | 58.75 |
| 75 hp | 203.0 | 211 | 183.6 | 192 | 105.6 | 91.80 | 96 | 73.44 |
| 100 hp | 270.7 | 273 | 244.8 | 248 | 140.8 | 122.4 | 124 | 97.91 |
| 125 hp | 338.3 | 343 | 306.0 | 312 | 175.9 | 153.0 | 156 | 122.4 |
| 150 hp | 406.0 | 396 | 367.2 | 360 | 211.1 | 183.6 | 180 | 146.9 |
| 200 hp | 541.4 | 528 | 489.6 | 480 | 281.5 | 244.8 | 240 | 195.8 |
HP to amps, DC motors (efficiency 85%)
DC has no power factor, so the current is the shaft power over volts and efficiency. 12 V to 48 V covers winches, trolling motors, golf carts and battery tools; 90 V and 180 V are the armature voltages of industrial DC drives, for which NEC Table 430.247 gives the sizing current.
| hp | 12 V | 24 V | 36 V | 48 V | 90 V | 180 V |
|---|---|---|---|---|---|---|
| 1/4 hp (0.25) | 18.28 | 9.142 | 6.095 | 4.571 | 2.438 | 1.219 |
| 1/3 hp (0.33) | 24.38 | 12.19 | 8.126 | 6.095 | 3.251 | 1.625 |
| 1/2 hp (0.5) | 36.57 | 18.28 | 12.19 | 9.142 | 4.876 | 2.438 |
| 3/4 hp (0.75) | 54.85 | 27.43 | 18.28 | 13.71 | 7.314 | 3.657 |
| 1 hp | 73.14 | 36.57 | 24.38 | 18.28 | 9.752 | 4.876 |
| 1-1/2 hp (1.5) | 109.7 | 54.85 | 36.57 | 27.43 | 14.63 | 7.314 |
| 2 hp | 146.3 | 73.14 | 48.76 | 36.57 | 19.50 | 9.752 |
| 3 hp | 219.4 | 109.7 | 73.14 | 54.85 | 29.25 | 14.63 |
| 5 hp | 365.7 | 182.8 | 121.9 | 91.42 | 48.76 | 24.38 |
Frequently Asked Questions
How many amps does a 1 hp motor draw?
By the formula at PF 0.85 and 90% efficiency, about 8.5 A at 115 V single-phase and 4.2 A at 230 V. NEC Table 430.248 lists 16 A and 8 A for the same motor, because small single-phase motors have worse power factor and efficiency than the defaults and the table builds that in.
Why is the result lower than the NEC motor table?
The code tables (430.247 to 430.250) are conservative by design and reflect older, less efficient motors. NEC 430.6(A)(1) requires the table value, not the nameplate or a calculation, for sizing conductors, disconnects and short-circuit protection. The nameplate current is used only for the overload protection.
What efficiency and power factor should I use?
The nameplate figures, if you have them. Modern premium-efficiency three-phase motors run at 90 to 96% efficiency and 0.85 to 0.9 power factor at full load. Small single-phase motors are much worse, often 60 to 75% efficient at 0.6 to 0.8 power factor, which is why their real current is so far above the simple estimate.
What is the difference between horsepower and kilowatts?
They are both power. 1 hp is 746 W or 0.746 kW, and 1 kW is 1.34 hp. Motors in North America are rated in hp and in most of the rest of the world in kW; a 37 kW motor and a 50 hp motor are the same machine.
Can I size the breaker from this current?
No. Motor branch-circuit protection under NEC 430.52 is sized from the table full-load current, at up to 250% for an inverse-time breaker, to ride through the starting inrush. The motor FLA calculator and the breaker sizing calculator cover the code path.
Other electrical conversions
Related Calculators
Continue with these related electrical tools
Motor FLA Calculator
Motor full-load amps from horsepower, voltage and phase
kW to Amps Calculator
Line current from kilowatts for generators, motors and heaters
Breaker / Fuse Sizing Calculator
Next standard breaker or fuse size for a load (NEC 240.6)
Wire Size Calculator
Smallest conductor that meets ampacity and the voltage-drop limit (AWG/mm2)