HP to Amps Calculator

Enter the motor horsepower and the supply voltage, then the phase, power factor and efficiency. The result is the running current. A motor rated in horsepower is rated on its shaft output, so the electrical input, and the amps, are higher by the efficiency and the power factor. The defaults are the same conventions the motor FLA calculator uses.

Free download

Get the printable wire size charts

NEC 310.16 ampacity for copper and aluminium at 60, 75 and 90 C, how far each size runs before voltage drop bites, standard breaker sizes and AWG to mm2. Three pages, made for the van door.

We store your email with EmailOctopus to send the charts and occasional wiring and calculator tips, nothing else. Unsubscribe any time. Privacy policy.

How It Works

The formula

DC:  I = hp × 746 / (V × η)

Single-phase AC:  I = hp × 746 / (V × PF × η)

Three-phase AC:  I = hp × 746 / (√3 × VL-L × PF × η)

One horsepower is 746 W. η is the motor efficiency as a decimal (0.9 for 90%) and PF the full-load power factor. Both come off the nameplate; without them the defaults are 0.9 and 0.85.

Worked examples

A 5 hp single-phase motor at 230 V

I = 5 × 746 / (230 × 0.85 × 0.9) = 3730 / 176.0 = 21.2 A. For comparison NEC Table 430.248 lists 28 A for a 5 hp, 230 V single-phase motor; the code table is deliberately conservative and is the figure the conductors and breaker must be sized from.

A 10 hp three-phase motor at 460 V

I = 10 × 746 / (1.732 × 460 × 0.85 × 0.9) = 7460 / 609.5 = 12.2 A. Table 430.250 gives 14 A for the same motor.

A 1 hp 24 V DC motor at 85% efficiency

DC has no power factor: I = 746 / (24 × 0.85) = 36.6 A. Low-voltage DC motors draw heavy current for their size, which is why a 1 hp winch or thruster needs cable that looks oversized for the job.

A 50 hp premium motor at 400 V, PF 0.88, 93% efficient

I = 50 × 746 / (1.732 × 400 × 0.88 × 0.93) = 37300 / 567.0 = 65.8 A. Better efficiency and power factor take real amps off the feeder: at the default 0.85 and 0.9 the same motor would show 70.4 A.

A 3/4 hp pump motor at 115 V

At the defaults: I = 0.75 × 746 / (115 × 0.85 × 0.9) = 559.5 / 88.0 = 6.36 A. NEC Table 430.248 lists 13.8 A, more than twice that. The gap is the motor, not the maths: a small capacitor-start motor can run nearer PF 0.65 and 65% efficiency, and at those figures the formula gives 559.5 / (115 × 0.65 × 0.65) = 11.5 A. Size the circuit from the 13.8 A.

A 3 hp three-phase motor on a 208 V supply

I = 3 × 746 / (1.732 × 208 × 0.85 × 0.9) = 2238 / 275.6 = 8.12 A, against 7.34 A for the same motor at 230 V. Table 430.250 has a separate 208 V column for this reason: 10.6 A at 208 V, 9.6 A at 230 V. A motor moved from a 230 V plant to a 208Y/120 building draws about 10% more current for the same shaft power.

HP to amps, single-phase motors: formula and NEC Table 430.248

Formula columns are the running current at PF 0.85 and 90% efficiency, the calculator defaults. NEC columns are Table 430.248, which NEC 430.6(A)(1) requires for the conductors, the disconnect and the branch-circuit breaker. On fractional-horsepower motors the code figure is two to three times the formula, because small single-phase motors run well below the default power factor and efficiency.

hp 115 V formula 115 V NEC 208 V formula 208 V NEC 230 V formula 230 V NEC
1/6 hp (0.17) 1.413 4.4 0.781 2.4 0.707 2.2
1/4 hp (0.25) 2.120 5.8 1.172 3.2 1.060 2.9
1/3 hp (0.33) 2.827 7.2 1.563 4.0 1.413 3.6
1/2 hp (0.5) 4.240 9.8 2.344 5.4 2.120 4.9
3/4 hp (0.75) 6.360 13.8 3.516 7.6 3.180 6.9
1 hp 8.480 16 4.688 8.8 4.240 8.0
1-1/2 hp (1.5) 12.72 20 7.032 11 6.360 10
2 hp 16.96 24 9.377 13.2 8.480 12
3 hp 25.44 34 14.06 18.7 12.72 17
5 hp 42.40 56 23.44 30.8 21.20 28
7-1/2 hp (7.5) 63.60 80 35.16 44 31.80 40
10 hp 84.80 100 46.88 55 42.40 50

HP to amps, three-phase motors: formula and NEC Table 430.250

Line current at line-to-line voltage. Formula columns use PF 0.85 and 90% efficiency; NEC columns are Table 430.250 for induction motors, the figure to size from. From about 150 hp the formula reads slightly above the table, because large motors beat PF 0.85 and 90% efficiency. 400 V has no NEC column because it is an IEC voltage; the motor FLA calculator page carries the full code tables, including 115 V, 200 V and 575 V.

hp 208 V formula 208 V NEC 230 V formula 230 V NEC 400 V formula 460 V formula 460 V NEC 575 V formula
1/2 hp (0.5) 1.353 2.4 1.224 2.2 0.704 0.612 1.1 0.490
3/4 hp (0.75) 2.030 3.5 1.836 3.2 1.056 0.918 1.6 0.734
1 hp 2.707 4.6 2.448 4.2 1.408 1.224 2.1 0.979
1-1/2 hp (1.5) 4.060 6.6 3.672 6.0 2.111 1.836 3.0 1.469
2 hp 5.414 7.5 4.896 6.8 2.815 2.448 3.4 1.958
3 hp 8.120 10.6 7.344 9.6 4.223 3.672 4.8 2.937
5 hp 13.53 16.7 12.24 15.2 7.038 6.120 7.6 4.896
7-1/2 hp (7.5) 20.30 24.2 18.36 22 10.56 9.180 11 7.344
10 hp 27.07 30.8 24.48 28 14.08 12.24 14 9.791
15 hp 40.60 46.2 36.72 42 21.11 18.36 21 14.69
20 hp 54.14 59.4 48.96 54 28.15 24.48 27 19.58
25 hp 67.67 74.8 61.20 68 35.19 30.60 34 24.48
30 hp 81.20 88 73.44 80 42.23 36.72 40 29.37
40 hp 108.3 114 97.91 104 56.30 48.96 52 39.17
50 hp 135.3 143 122.4 130 70.38 61.20 65 48.96
60 hp 162.4 169 146.9 154 84.45 73.44 77 58.75
75 hp 203.0 211 183.6 192 105.6 91.80 96 73.44
100 hp 270.7 273 244.8 248 140.8 122.4 124 97.91
125 hp 338.3 343 306.0 312 175.9 153.0 156 122.4
150 hp 406.0 396 367.2 360 211.1 183.6 180 146.9
200 hp 541.4 528 489.6 480 281.5 244.8 240 195.8

HP to amps, DC motors (efficiency 85%)

DC has no power factor, so the current is the shaft power over volts and efficiency. 12 V to 48 V covers winches, trolling motors, golf carts and battery tools; 90 V and 180 V are the armature voltages of industrial DC drives, for which NEC Table 430.247 gives the sizing current.

hp 12 V 24 V 36 V 48 V 90 V 180 V
1/4 hp (0.25) 18.28 9.142 6.095 4.571 2.438 1.219
1/3 hp (0.33) 24.38 12.19 8.126 6.095 3.251 1.625
1/2 hp (0.5) 36.57 18.28 12.19 9.142 4.876 2.438
3/4 hp (0.75) 54.85 27.43 18.28 13.71 7.314 3.657
1 hp 73.14 36.57 24.38 18.28 9.752 4.876
1-1/2 hp (1.5) 109.7 54.85 36.57 27.43 14.63 7.314
2 hp 146.3 73.14 48.76 36.57 19.50 9.752
3 hp 219.4 109.7 73.14 54.85 29.25 14.63
5 hp 365.7 182.8 121.9 91.42 48.76 24.38

Frequently Asked Questions

How many amps does a 1 hp motor draw?

By the formula at PF 0.85 and 90% efficiency, about 8.5 A at 115 V single-phase and 4.2 A at 230 V. NEC Table 430.248 lists 16 A and 8 A for the same motor, because small single-phase motors have worse power factor and efficiency than the defaults and the table builds that in.

Why is the result lower than the NEC motor table?

The code tables (430.247 to 430.250) are conservative by design and reflect older, less efficient motors. NEC 430.6(A)(1) requires the table value, not the nameplate or a calculation, for sizing conductors, disconnects and short-circuit protection. The nameplate current is used only for the overload protection.

What efficiency and power factor should I use?

The nameplate figures, if you have them. Modern premium-efficiency three-phase motors run at 90 to 96% efficiency and 0.85 to 0.9 power factor at full load. Small single-phase motors are much worse, often 60 to 75% efficient at 0.6 to 0.8 power factor, which is why their real current is so far above the simple estimate.

What is the difference between horsepower and kilowatts?

They are both power. 1 hp is 746 W or 0.746 kW, and 1 kW is 1.34 hp. Motors in North America are rated in hp and in most of the rest of the world in kW; a 37 kW motor and a 50 hp motor are the same machine.

Can I size the breaker from this current?

No. Motor branch-circuit protection under NEC 430.52 is sized from the table full-load current, at up to 250% for an inverse-time breaker, to ride through the starting inrush. The motor FLA calculator and the breaker sizing calculator cover the code path.

Embed This Calculator

Add this free calculator to your website. Copy the code below and paste it into your page.