kVA to kW Calculator

Enter the apparent power in kVA and the power factor. The result is real power in kW, the part that does work and that the meter charges for, alongside the reactive kVAR that makes up the rest. Voltage and phase do not enter into it: the ratio between kVA and kW is the power factor alone.

kVA vs kW: what is the difference?

kVA is apparent power, the volts times the amps, and kW is real power, the part that turns into heat, light or motion. The power factor links them: kW = kVA × PF. A 100 kVA generator at PF 0.8 delivers 100 × 0.8 = 80 kW; at PF 1 the two figures are equal, and kW is never larger than kVA.

Free download

Get the printable wire size charts

NEC 310.16 ampacity for copper and aluminium at 60, 75 and 90 C, how far each size runs before voltage drop bites, standard breaker sizes and AWG to mm2. Three pages, made for the van door.

We store your email with EmailOctopus to send the charts and occasional wiring and calculator tips, nothing else. Unsubscribe any time. Privacy policy.

How It Works

The formula

Real power:  kW = kVA × PF

Reactive power:  kVAR = kVA × √(1 − PF²)

The power triangle:  kVA² = kW² + kVAR²

PF is the power factor, between 0 and 1. It is the cosine of the phase angle between voltage and current; the kVAR is the sine component. The same formula works for VA to W and MVA to MW.

Worked examples

A 100 kVA generator at PF 0.8

kW = 100 × 0.8 = 80 kW, and kVAR = 100 × √(1 − 0.64) = 100 × 0.6 = 60 kVAR. This is the standard generator nameplate: the 100 kVA is the alternator limit, the 80 kW is what the engine can deliver.

A 500 kVA transformer feeding a PF 0.9 load

kW = 500 × 0.9 = 450 kW. The reactive component is 500 × √(1 − 0.81) = 500 × 0.436 = 217.9 kVAR, which is the size of capacitor bank that would take the load to unity.

A 30 kVA UPS rated at unity

Modern UPS units are often rated at PF 1, so kW = 30 × 1 = 30 kW. Older units rated at 0.8 or 0.9 deliver only 24 or 27 kW from the same 30 kVA frame.

15 kVA at a poor PF of 0.7

kW = 15 × 0.7 = 10.5 kW of useful power for 15 kVA of supply capacity, with 10.7 kVAR circulating. At this power factor almost half the current is doing no work, which is where utility penalties start.

kVA to kW by power factor

Real power in kW. The PF 1.0 column is also the kVA; the further left you read, the more of the rating is reactive.

kVA PF 0.70 PF 0.80 PF 0.85 PF 0.90 PF 0.95 PF 1.00
1 kVA 0.700 0.800 0.850 0.900 0.950 1.000
2 kVA 1.400 1.600 1.700 1.800 1.900 2.000
3 kVA 2.100 2.400 2.550 2.700 2.850 3.000
5 kVA 3.500 4.000 4.250 4.500 4.750 5.000
7.5 kVA 5.250 6.000 6.375 6.750 7.125 7.500
10 kVA 7.000 8.000 8.500 9.000 9.500 10.00
15 kVA 10.50 12.00 12.75 13.50 14.25 15.00
20 kVA 14.00 16.00 17.00 18.00 19.00 20.00
25 kVA 17.50 20.00 21.25 22.50 23.75 25.00
30 kVA 21.00 24.00 25.50 27.00 28.50 30.00
45 kVA 31.50 36.00 38.25 40.50 42.75 45.00
50 kVA 35.00 40.00 42.50 45.00 47.50 50.00
75 kVA 52.50 60.00 63.75 67.50 71.25 75.00
100 kVA 70.00 80.00 85.00 90.00 95.00 100.0
150 kVA 105.0 120.0 127.5 135.0 142.5 150.0
200 kVA 140.0 160.0 170.0 180.0 190.0 200.0
250 kVA 175.0 200.0 212.5 225.0 237.5 250.0
300 kVA 210.0 240.0 255.0 270.0 285.0 300.0
500 kVA 350.0 400.0 425.0 450.0 475.0 500.0
1,000 kVA 700.0 800.0 850.0 900.0 950.0 1,000

Frequently Asked Questions

How many kW is 1 kVA?

Between 0 and 1 kW, set by the power factor. At PF 1 it is 1 kW; at the usual 0.8 rating point it is 0.8 kW; at 0.9 it is 0.9 kW. There is no fixed conversion without the power factor.

Why are generators rated at 0.8 power factor?

It is the industry rating point that matches a typical mixed motor load. The alternator is sized on kVA (current) and the engine on kW (fuel), and 0.8 is the ratio the two are matched at. Running a unity power factor load on such a set overloads the engine before the alternator reaches its kVA.

What is kVAR?

Reactive power: the energy that shuttles between the source and the magnetic fields of motors, transformers and other inductive loads without being consumed. It adds current, and so adds losses and takes up capacity, without doing work. Capacitors supply it locally so the supply does not have to.

Can kW ever be larger than kVA?

No. kW = kVA × PF and the power factor cannot exceed 1, so kW is at most equal to kVA. If your figures suggest otherwise, one of them is wrong or the power factor is being applied twice.

How do I improve a poor power factor?

Add capacitors sized to cancel the reactive kVAR. The 500 kVA example above needs about 218 kVAR to reach unity, or less to reach a target like 0.95. The power factor correction calculator works out the capacitor kVAR for any target.