kVA to Amps Calculator
Enter the rating in kVA and the voltage of the winding or output you care about, then pick single or three-phase. The result is the full-load current. kVA is apparent power, volts times amps already, so unlike the kW conversions this one needs no power factor.
Free download
Get the printable wire size charts
NEC 310.16 ampacity for copper and aluminium at 60, 75 and 90 C, how far each size runs before voltage drop bites, standard breaker sizes and AWG to mm2. Three pages, made for the van door.
How It Works
The formula
Single-phase: I = kVA × 1000 / V
Three-phase: I = kVA × 1000 / (√3 × VL-L)
I is the full-load line current in amps and V is the line-to-line voltage of the winding in question. A transformer has a different full-load current on each side; run the calculation once per winding.
Worked examples
A 75 kVA transformer, 480 V primary
I = 75 × 1000 / (1.732 × 480) = 75000 / 831.4 = 90.2 A. This is the primary full-load current that NEC 450.3 protection is sized from.
The same 75 kVA at the 208 V secondary
I = 75000 / (1.732 × 208) = 75000 / 360.3 = 208.2 A. Lower voltage, higher current: the secondary conductors and the panel it feeds are sized to this figure, not to the primary.
A 25 kVA single-phase pole transformer at 240 V
I = 25 × 1000 / 240 = 104.2 A. A single 25 kVA pot serving a house can only deliver a little more than 100 A at 240 V, which is why a 200 A service on a shared pot leans on diversity.
A 500 kVA unit at 208 V three-phase
I = 500000 / (1.732 × 208) = 1,388 A. At this scale the secondary is a bus duct or parallel sets of 500 kcmil conductors rather than a single cable.
kVA to amps, single-phase
Full-load current of single-phase transformers, UPS units and generators at the stated winding voltage.
| kVA | 120 V | 208 V | 230 V | 240 V | 277 V |
|---|---|---|---|---|---|
| 1 kVA | 8.333 | 4.808 | 4.348 | 4.167 | 3.610 |
| 1.5 kVA | 12.50 | 7.212 | 6.522 | 6.250 | 5.415 |
| 2 kVA | 16.67 | 9.615 | 8.696 | 8.333 | 7.220 |
| 3 kVA | 25.00 | 14.42 | 13.04 | 12.50 | 10.83 |
| 5 kVA | 41.67 | 24.04 | 21.74 | 20.83 | 18.05 |
| 7.5 kVA | 62.50 | 36.06 | 32.61 | 31.25 | 27.08 |
| 10 kVA | 83.33 | 48.08 | 43.48 | 41.67 | 36.10 |
| 15 kVA | 125.0 | 72.12 | 65.22 | 62.50 | 54.15 |
| 20 kVA | 166.7 | 96.15 | 86.96 | 83.33 | 72.20 |
| 25 kVA | 208.3 | 120.2 | 108.7 | 104.2 | 90.25 |
| 37.5 kVA | 312.5 | 180.3 | 163.0 | 156.3 | 135.4 |
| 50 kVA | 416.7 | 240.4 | 217.4 | 208.3 | 180.5 |
| 75 kVA | 625.0 | 360.6 | 326.1 | 312.5 | 270.8 |
| 100 kVA | 833.3 | 480.8 | 434.8 | 416.7 | 361.0 |
kVA to amps, three-phase
The rows are the standard three-phase transformer ratings. Line current at line-to-line voltage.
| kVA | 208 V | 400 V | 415 V | 480 V |
|---|---|---|---|---|
| 5 kVA | 13.88 | 7.217 | 6.956 | 6.014 |
| 10 kVA | 27.76 | 14.43 | 13.91 | 12.03 |
| 15 kVA | 41.64 | 21.65 | 20.87 | 18.04 |
| 20 kVA | 55.51 | 28.87 | 27.82 | 24.06 |
| 25 kVA | 69.39 | 36.08 | 34.78 | 30.07 |
| 30 kVA | 83.27 | 43.30 | 41.74 | 36.08 |
| 45 kVA | 124.9 | 64.95 | 62.60 | 54.13 |
| 50 kVA | 138.8 | 72.17 | 69.56 | 60.14 |
| 75 kVA | 208.2 | 108.3 | 104.3 | 90.21 |
| 100 kVA | 277.6 | 144.3 | 139.1 | 120.3 |
| 112.5 kVA | 312.3 | 162.4 | 156.5 | 135.3 |
| 150 kVA | 416.4 | 216.5 | 208.7 | 180.4 |
| 200 kVA | 555.1 | 288.7 | 278.2 | 240.6 |
| 225 kVA | 624.5 | 324.8 | 313.0 | 270.6 |
| 250 kVA | 693.9 | 360.8 | 347.8 | 300.7 |
| 300 kVA | 832.7 | 433.0 | 417.4 | 360.8 |
| 400 kVA | 1,110 | 577.4 | 556.5 | 481.1 |
| 500 kVA | 1,388 | 721.7 | 695.6 | 601.4 |
| 750 kVA | 2,082 | 1,083 | 1,043 | 902.1 |
| 1,000 kVA | 2,776 | 1,443 | 1,391 | 1,203 |
| 1,500 kVA | 4,164 | 2,165 | 2,087 | 1,804 |
| 2,000 kVA | 5,551 | 2,887 | 2,782 | 2,406 |
Frequently Asked Questions
How many amps is a 75 kVA transformer?
On a 480 V three-phase primary, 90.2 A. On a 208 V three-phase secondary, 208.2 A. On a 240 V single-phase secondary it would be 312.5 A. The kVA is the same on both sides; the current depends on which winding you are looking at.
Why is there no power factor in the kVA to amps formula?
kVA is already volts times amps. Power factor is the ratio between that apparent power and the real power in kW, so it is needed to get from kVA to kW, not from kVA to current. A transformer is rated in kVA for exactly this reason: its heating depends on the current, whatever the load's power factor.
Do I use the primary or the secondary voltage?
Whichever side you are sizing. Primary protection and primary conductors use the primary full-load current; the secondary conductors, secondary protection and the panel it feeds use the secondary figure. NEC 450.3 sets the overcurrent limits for each side as a percentage of that side's rated current.
Is the three-phase voltage line-to-line?
Yes. Use 208 V, not 120 V, for a 208Y/120 system, and 480 V, not 277 V, for 480Y/277. The √3 in the formula is what accounts for the line-to-neutral relationship.
How do I choose the transformer kVA in the first place?
Add up the connected load in VA or kVA, apply any demand factors, and pick the next standard rating up with some margin for growth. The transformer sizing calculator does that and returns the full-load current on both sides.
Other electrical conversions
Related Calculators
Continue with these related electrical tools
Amps to kVA Calculator
Apparent power from current and voltage for sizing supply equipment
kVA to kW Calculator
Real power and kVAR from apparent power and power factor