Volts to Amps Calculator

Voltage on its own does not set a current: you also need to know either how much power the load takes or what its resistance is. Enter the volts, then either the watts (for an appliance, a motor or a heater with a nameplate) or the ohms (for a resistor, an element or a measured winding), and the calculator gives the amps.

Free download

Get the printable wire size charts

NEC 310.16 ampacity for copper and aluminium at 60, 75 and 90 C, how far each size runs before voltage drop bites, standard breaker sizes and AWG to mm2. Three pages, made for the van door.

We store your email with EmailOctopus to send the charts and occasional wiring and calculator tips, nothing else. Unsubscribe any time. Privacy policy.

How It Works

The formula

From resistance (Ohm's law):  I = V / R

From power, DC:  I = P / V

From power, single-phase AC:  I = P / (V × PF)

From power, three-phase AC:  I = P / (√3 × VL-L × PF)

R is resistance in ohms and P is real power in watts. The resistance route assumes a resistive load; for a reactive AC load, use the power route with its power factor.

Worked examples

12 V across a 4 Ω resistor

Ohm's law: I = 12 / 4 = 3 A. The resistor dissipates P = V × I = 36 W, so it needs to be a 50 W part, not a 1/4 W one.

120 V with a 1,500 W load

From power, single-phase, PF 1: I = 1500 / 120 = 12.5 A. This is the same sum as the watts to amps page, approached from the voltage side.

A 2.3 kW kettle at 230 V

Resistive, so either route works. From power: I = 2300 / 230 = 10 A. From resistance, the element measures about 23 Ω hot, and 230 / 23 = 10 A again.

480 V three-phase with a 30 kW load at PF 0.85

I = 30000 / (1.732 × 480 × 0.85) = 30000 / 706.7 = 42.5 A per line. Here resistance is not useful; the power factor route is the only one that gives the line current.

Amps from volts and resistance (I = V / R)

Ohm's law for a resistive load. Rows are resistance in ohms, columns are the applied voltage.

Ω 5 V 9 V 12 V 24 V 48 V 120 V 240 V
1 Ω 5.000 9.000 12.00 24.00 48.00 120.0 240.0
2 Ω 2.500 4.500 6.000 12.00 24.00 60.00 120.0
4 Ω 1.250 2.250 3.000 6.000 12.00 30.00 60.00
8 Ω 0.625 1.125 1.500 3.000 6.000 15.00 30.00
10 Ω 0.500 0.900 1.200 2.400 4.800 12.00 24.00
20 Ω 0.250 0.450 0.600 1.200 2.400 6.000 12.00
50 Ω 0.100 0.180 0.240 0.480 0.960 2.400 4.800
100 Ω 0.050 0.090 0.120 0.240 0.480 1.200 2.400
1,000 Ω 0.005 0.009 0.012 0.024 0.048 0.120 0.240

Amps from volts and watts, single-phase and DC (PF 1)

Current for a load of known power. Divide by the power factor for a motor or electronic load.

W 12 V 24 V 48 V 120 V 240 V
100 W 8.333 4.167 2.083 0.833 0.417
500 W 41.67 20.83 10.42 4.167 2.083
1,000 W 83.33 41.67 20.83 8.333 4.167
1,500 W 125.0 62.50 31.25 12.50 6.250
2,000 W 166.7 83.33 41.67 16.67 8.333
3,000 W 250.0 125.0 62.50 25.00 12.50
5,000 W 416.7 208.3 104.2 41.67 20.83

Frequently Asked Questions

Can you convert volts to amps directly?

No. Volts and amps are different quantities, linked only through the load. Ohm's law (I = V / R) needs the resistance, and the power formula (I = P / V) needs the watts. Give the calculator one of those and it will give you the amps.

How many amps is 120 volts?

Whatever the load draws. A 60 W lamp at 120 V is 0.5 A; a 1,500 W heater is 12.5 A; a 120 V circuit with nothing plugged in is 0 A. The voltage is the pressure, the current depends on what is connected.

How do I convert volts to watts?

You need the current as well: P = V × I. 120 V at 10 A is 1,200 W. The amps to watts calculator does that, including the power factor for AC loads.

Why does a heater draw more current when it is cold?

The resistance of a metal element rises with temperature. A cold tungsten filament or heating element has a much lower resistance than its running figure, so the current at switch-on is several times the steady-state value. Measure resistance cold and the calculated current will be too high for normal running.

Which voltage do I use for three-phase?

Line-to-line (208, 400, 415 or 480 V), together with the total three-phase watts. The √3 in the formula handles the relationship to the line-to-neutral voltage; do not use 120 V or 230 V with a three-phase kW figure.