kW to kVA Calculator

To convert kW to kVA, divide by the power factor: kVA = kW / PF. Generator sets are rated at PF 0.8, so a generator for an 80 kW load needs 80 / 0.8 = 100 kVA, which is how a 100 kVA / 80 kW set is labelled. Choose the next standard size up, and check the largest motor's starting kVA against the set's motor-starting rating.

Enter the real power in kW and the power factor of the load. The result is the apparent power in kVA, which is the rating you have to buy in a generator, transformer or UPS. A load list is in kW; supply equipment is in kVA; the power factor bridges the two, and it always pushes the kVA up.

Free download

Get the printable wire size charts

NEC 310.16 ampacity for copper and aluminium at 60, 75 and 90 C, how far each size runs before voltage drop bites, standard breaker sizes and AWG to mm2. Three pages, made for the van door.

We store your email with EmailOctopus to send the charts and occasional wiring and calculator tips, nothing else. Unsubscribe any time. Privacy policy.

How It Works

The formula

Apparent power:  kVA = kW / PF

Reactive power:  kVAR = kVA × √(1 − PF²)

Because PF is 1 or less, kVA is always equal to or larger than kW. The same arithmetic converts W to VA and MW to MVA.

Worked examples

80 kW of load at PF 0.8

kVA = 80 / 0.8 = 100 kVA. A generator set that has to deliver 80 kW to a mixed motor load needs a 100 kVA alternator, and that is exactly how a 100 kVA / 80 kW set is labelled.

A 37 kW motor at PF 0.85

kVA = 37 / 0.85 = 43.5 kVA. That is the running demand; starting draws several times more for a second or two, which a generator has to ride through and a transformer usually shrugs off.

150 kW at a corrected PF of 0.95

kVA = 150 / 0.95 = 157.9 kVA. Correcting from 0.8 to 0.95 takes the same 150 kW from 187.5 kVA down to 157.9 kVA, freeing about 30 kVA of transformer capacity without touching the load.

A 10 kW heater

Resistive, so PF = 1: kVA = 10 / 1 = 10 kVA. For heating the two units are the same number.

kW to kVA by power factor

Apparent power in kVA. Read the row for your kW and the column for the load's power factor, then buy the next standard rating up.

kW PF 0.70 PF 0.80 PF 0.85 PF 0.90 PF 0.95 PF 1.00
1 kW 1.429 1.250 1.176 1.111 1.053 1.000
2 kW 2.857 2.500 2.353 2.222 2.105 2.000
3 kW 4.286 3.750 3.529 3.333 3.158 3.000
5 kW 7.143 6.250 5.882 5.556 5.263 5.000
7.5 kW 10.71 9.375 8.824 8.333 7.895 7.500
10 kW 14.29 12.50 11.76 11.11 10.53 10.00
15 kW 21.43 18.75 17.65 16.67 15.79 15.00
20 kW 28.57 25.00 23.53 22.22 21.05 20.00
25 kW 35.71 31.25 29.41 27.78 26.32 25.00
30 kW 42.86 37.50 35.29 33.33 31.58 30.00
40 kW 57.14 50.00 47.06 44.44 42.11 40.00
50 kW 71.43 62.50 58.82 55.56 52.63 50.00
75 kW 107.1 93.75 88.24 83.33 78.95 75.00
100 kW 142.9 125.0 117.6 111.1 105.3 100.0
150 kW 214.3 187.5 176.5 166.7 157.9 150.0
200 kW 285.7 250.0 235.3 222.2 210.5 200.0
250 kW 357.1 312.5 294.1 277.8 263.2 250.0
300 kW 428.6 375.0 352.9 333.3 315.8 300.0
500 kW 714.3 625.0 588.2 555.6 526.3 500.0
1,000 kW 1,429 1,250 1,176 1,111 1,053 1,000

Frequently Asked Questions

How many kVA is 10 kW?

At PF 1, 10 kVA. At PF 0.8, 12.5 kVA. At PF 0.9, 11.1 kVA. The kVA grows as the power factor falls, because more current is needed to deliver the same real power.

Why does a low power factor increase the kVA?

kW is the work being done. At a lower power factor the same work needs more current, and current is what kVA measures. The extra is the reactive kVAR that circulates without being consumed but still has to be carried by the alternator or transformer.

How do I size a generator from a list of loads in kW?

Add the kW that will run at the same time, divide by the power factor (0.8 for a mixed motor load, 1 for pure heating), then check the largest motor's starting kVA against the set's motor-starting rating. Choose the next standard size up from the larger of the two.

How do I size a transformer from kW?

Divide the kW by the power factor to get kVA, allow 20 to 25% for growth and inrush, and pick the next standard rating. Common three-phase sizes are 15, 30, 45, 75, 112.5, 150, 225, 300, 500, 750 and 1,000 kVA. The transformer sizing calculator gives the full-load current too.

What if I do not know the power factor?

Use the nameplate if there is one. Otherwise 1 for resistive heating and lighting, 0.8 for a mixed motor load, 0.85 to 0.9 for a single modern induction motor at full load, and 0.9 to 1 for equipment with active power factor correction such as modern UPS units and LED drivers.

Embed This Calculator

Add this free calculator to your website. Copy the code below and paste it into your page.