110 Amp Wire Size

What gauge wire do you need for a 110 amp circuit? The short answer, the full NEC 310.16 table at all three termination ratings, and how far you can run it before voltage drop forces a bigger conductor.

Short answer

A 110 amp circuit needs 2 AWG copper, or 1/0 AWG aluminium, sized from the 75°C column of NEC 310.16.

At 240 V that copper conductor stays inside a 3% voltage drop for roughly 173 ft one-way. Past that, go up a size.

A 110 A breaker may serve a continuous load of no more than 88 A (NEC 210.20(A) and 215.3, the 125% rule).

Minimum conductor by termination rating

Terminations on breakers, lugs and equipment carry a temperature rating. You size the conductor from the lowest-rated component in the circuit, so the same 110 A load can call for different sizes.

Termination rating Copper Aluminium
60°C 1 AWG (110 A) 2/0 AWG (115 A)
75°C (applies here) 2 AWG (115 A) 1/0 AWG (120 A)
90°C 3 AWG (115 A) 1 AWG (115 A)

NEC 110.14(C)(1) requires the 60°C column for circuits rated 100 A or less unless every termination is listed for a higher temperature, and the 75°C column above 100 A. Most modern breakers and panels are listed 75°C, which is why the 75°C size is often what actually gets installed. The 90°C column is normally used only as a starting point for derating, not for the final size.

How far can you run it?

Ampacity sets the minimum size; voltage drop sets the maximum distance. These are one-way run lengths at 110 A on a 240 V single-phase circuit, holding drop to 3%.

Copper size Max one-way run at 3% Max one-way run at 5%
2 AWG 173 ft 288 ft
1 AWG 219 ft 365 ft
1/0 AWG 275 ft 458 ft
2/0 AWG 325 ft 542 ft

3% is the NEC's recommended limit for a branch circuit and 5% for feeder plus branch combined. Both are recommendations in informational notes, not enforceable rules, but most inspectors and specifiers treat 3% as the working target.

What runs on a 110 amp circuit

Typical loads at this rating: feeders to 100 A sub-panels with headroom, small commercial tenant services, accessory dwelling unit feeders, larger workshop panels.

110 A is the first standard breaker size above 100 A, and that boundary changes the rule. NEC 110.14(C)(1)(b) allows the 75°C column for circuits over 100 A, so a 110 A feeder is sized from the 75°C ampacities, where 2 AWG copper carries 115 A, rather than the 60°C column that governs 100 A and below.

Worked example

A 110 A feeder to a detached studio 130 ft from the main panel: 2 AWG copper carries 115 A at the 75°C column and its 3% ceiling at 240 V and 110 A is about 173 ft, so the run clears with 43 ft in hand. In aluminium the feeder needs 1/0 (120 A at 75°C), and the ceiling shrinks to about 162 ft, which still covers 130 ft. Drop the same feeder to a 100 A breaker and the 60°C column applies instead, calling for 1 AWG copper; the 110 A circuit uses smaller wire than the 100 A one purely because of which column the code lets you read.

Check your exact run

These figures assume a standard installation with no derating. For your actual length, voltage, conductor material and temperature, run the numbers:

Ampacities are NEC 310.16 reference values for not more than three current-carrying conductors at 30°C ambient. They do not include ambient-temperature or conductor-bundling derating, and local wiring rules take precedence. Verify against the applicable code before installing.

Frequently Asked Questions

What size wire do I need for a 110 amp breaker?

2 AWG copper, or 1/0 AWG aluminium, sized from the 75°C column of NEC 310.16. Where every termination in the circuit is listed for 75°C, 2 AWG copper is permitted.

Can I use aluminium wire for a 110 amp circuit?

Yes, provided every terminal is rated for aluminium (marked AL/CU) and the connector maker's instructions on antioxidant compound are followed. Aluminium has lower ampacity for a given size, so you need 1/0 AWG aluminium in place of 2 AWG copper. Aluminium is cheaper and lighter on long feeder runs, which is why services are often aluminium.

How far can I run 2 AWG at 110 amps?

About 173 ft one-way on a 240 V single-phase circuit before voltage drop reaches 3%. Beyond that, step up one conductor size for every further increment of length.

What is the largest continuous load on a 110 amp circuit?

88 A. A continuous load is one expected to run for three hours or more, and NEC 210.19(A)(1) and 210.20(A) require the conductors and the breaker to be rated at 125% of it (215.2 and 215.3 for feeders). That is why, for example, EV chargers are always on a breaker well above their charging current.

Does this include derating?

No. These are base ampacities for not more than three current-carrying conductors at 30°C ambient. If you have more conductors in a raceway, a hot attic, or conduit in direct sun, apply the NEC 310.15 adjustment and correction factors, which will push the required size up.

Why does the column change at 100 A?

NEC 110.14(C)(1) splits the termination rules at 100 A. Circuits of 100 A or less, and conductors 14 AWG to 1 AWG, are sized from the 60°C column unless the equipment is listed otherwise, because small terminations historically were 60°C. Circuits over 100 A, and conductors larger than 1 AWG, are sized from the 75°C column, because that equipment is listed 75°C as standard. The result is that a 110 A feeder can legitimately use a conductor that a 100 A feeder with 60°C terminations cannot.

Wire size for other amperages

All the breaker sizes side by side are in the wire ampacity chart, and the wire gauge chart gives each size's diameter and area.

Free download

Get the printable wire size charts

NEC 310.16 ampacity for copper and aluminium at 60, 75 and 90 C, how far each size runs before voltage drop bites, standard breaker sizes and AWG to mm2. Three pages, made for the van door.

We store your email with EmailOctopus to send the charts and occasional wiring and calculator tips, nothing else. Unsubscribe any time. Privacy policy.