60 Amp Wire Size

What gauge wire do you need for a 60 amp circuit? The short answer, the full NEC 310.16 table at all three termination ratings, and how far you can run it before voltage drop forces a bigger conductor.

Short answer

A 60 amp circuit needs 4 AWG copper, or 3 AWG aluminium, sized from the 60°C column of NEC 310.16.

At 240 V that copper conductor stays inside a 3% voltage drop for roughly 192 ft one-way. Past that, go up a size.

A 60 A breaker may serve a continuous load of no more than 48 A (NEC 210.20(A) and 215.3, the 125% rule).

Minimum conductor by termination rating

Terminations on breakers, lugs and equipment carry a temperature rating. You size the conductor from the lowest-rated component in the circuit, so the same 60 A load can call for different sizes.

Termination rating Copper Aluminium
60°C (applies here) 4 AWG (70 A) 3 AWG (65 A)
75°C 6 AWG (65 A) 4 AWG (65 A)
90°C 6 AWG (75 A) 4 AWG (75 A)

NEC 110.14(C)(1) requires the 60°C column for circuits rated 100 A or less unless every termination is listed for a higher temperature, and the 75°C column above 100 A. Most modern breakers and panels are listed 75°C, which is why the 75°C size is often what actually gets installed. The 90°C column is normally used only as a starting point for derating, not for the final size.

How far can you run it?

Ampacity sets the minimum size; voltage drop sets the maximum distance. These are one-way run lengths at 60 A on a 240 V single-phase circuit, holding drop to 3%.

Copper size Max one-way run at 3% Max one-way run at 5%
4 AWG 192 ft 321 ft
3 AWG 240 ft 400 ft
2 AWG 317 ft 529 ft
1 AWG 401 ft 669 ft

3% is the NEC's recommended limit for a branch circuit and 5% for feeder plus branch combined. Both are recommendations in informational notes, not enforceable rules, but most inspectors and specifiers treat 3% as the working target.

What runs on a 60 amp circuit

Typical loads at this rating: sub-panels in garages and workshops, larger hot tubs, electric furnaces.

A 60 A feeder to a detached building or sub-panel usually runs a fair distance, so voltage drop rather than ampacity often sets the size.

Worked example

A 60 A feeder to a detached workshop 200 ft from the main panel: 4 AWG copper meets the 60 A ampacity at the 60°C column, but its 3% voltage-drop ceiling at 240 V is only about 192 ft, an 8 ft shortfall that would leave tools seeing a real sag under load. Stepping up to 3 AWG raises the ceiling to roughly 240 ft, comfortably covering the run. This is the exact case the note above means by "voltage drop rather than ampacity often sets the size" for a 60 A feeder.

Check your exact run

These figures assume a standard installation with no derating. For your actual length, voltage, conductor material and temperature, run the numbers:

Ampacities are NEC 310.16 reference values for not more than three current-carrying conductors at 30°C ambient. They do not include ambient-temperature or conductor-bundling derating, and local wiring rules take precedence. Verify against the applicable code before installing.

Frequently Asked Questions

What size wire do I need for a 60 amp breaker?

4 AWG copper, or 3 AWG aluminium, sized from the 60°C column of NEC 310.16. Where every termination in the circuit is listed for 75°C, 6 AWG copper is permitted.

Can I use aluminium wire for a 60 amp circuit?

Yes, provided every terminal is rated for aluminium (marked AL/CU) and the connector maker's instructions on antioxidant compound are followed. Aluminium has lower ampacity for a given size, so you need 3 AWG aluminium in place of 4 AWG copper. Aluminium is cheaper and lighter on long feeder runs, which is why services are often aluminium.

How far can I run 4 AWG at 60 amps?

About 192 ft one-way on a 240 V single-phase circuit before voltage drop reaches 3%. Beyond that, step up one conductor size for every further increment of length.

What is the largest continuous load on a 60 amp circuit?

48 A. A continuous load is one expected to run for three hours or more, and NEC 210.19(A)(1) and 210.20(A) require the conductors and the breaker to be rated at 125% of it (215.2 and 215.3 for feeders). That is why, for example, EV chargers are always on a breaker well above their charging current.

Does this include derating?

No. These are base ampacities for not more than three current-carrying conductors at 30°C ambient. If you have more conductors in a raceway, a hot attic, or conduit in direct sun, apply the NEC 310.15 adjustment and correction factors, which will push the required size up.

Does a detached workshop or garage sub-panel need its own ground rod?

Usually yes. NEC 250.32(A) requires a grounding electrode system at a separate building or structure supplied by a feeder, in addition to the equipment grounding conductor run with the feeder itself. A detached garage or workshop sub-panel is not exempt just because it already has a ground wire from the main panel. There is a narrow exception for a structure supplied by only a single branch circuit, which a 60 A feeder is not.

Wire size for other amperages

All the breaker sizes side by side are in the wire ampacity chart, and the wire gauge chart gives each size's diameter and area.

Free download

Get the printable wire size charts

NEC 310.16 ampacity for copper and aluminium at 60, 75 and 90 C, how far each size runs before voltage drop bites, standard breaker sizes and AWG to mm2. Three pages, made for the van door.

We store your email with EmailOctopus to send the charts and occasional wiring and calculator tips, nothing else. Unsubscribe any time. Privacy policy.