250 Amp Wire Size

What gauge wire do you need for a 250 amp circuit? The short answer, the full NEC 310.16 table at all three termination ratings, and how far you can run it before voltage drop forces a bigger conductor.

Short answer

A 250 amp circuit needs 250 kcmil copper, or 350 kcmil aluminium, sized from the 75°C column of NEC 310.16.

At 240 V that copper conductor stays inside a 3% voltage drop for roughly 276 ft one-way. Past that, go up a size.

A 250 A breaker may serve a continuous load of no more than 200 A (NEC 210.20(A) and 215.3, the 125% rule).

Minimum conductor by termination rating

Terminations on breakers, lugs and equipment carry a temperature rating. You size the conductor from the lowest-rated component in the circuit, so the same 250 A load can call for different sizes.

Termination rating Copper Aluminium
60°C 350 kcmil (260 A) 500 kcmil (260 A)
75°C (applies here) 250 kcmil (255 A) 350 kcmil (250 A)
90°C 4/0 AWG (260 A) 300 kcmil (260 A)

NEC 110.14(C)(1) requires the 60°C column for circuits rated 100 A or less unless every termination is listed for a higher temperature, and the 75°C column above 100 A. Most modern breakers and panels are listed 75°C, which is why the 75°C size is often what actually gets installed. The 90°C column is normally used only as a starting point for derating, not for the final size.

How far can you run it?

Ampacity sets the minimum size; voltage drop sets the maximum distance. These are one-way run lengths at 250 A on a 240 V single-phase circuit, holding drop to 3%.

Copper size Max one-way run at 3% Max one-way run at 5%
250 kcmil 276 ft 460 ft
300 kcmil 328 ft 546 ft
350 kcmil 377 ft 629 ft
400 kcmil 437 ft 729 ft

3% is the NEC's recommended limit for a branch circuit and 5% for feeder plus branch combined. Both are recommendations in informational notes, not enforceable rules, but most inspectors and specifiers treat 3% as the working target.

What runs on a 250 amp circuit

Typical loads at this rating: commercial feeders, large dwelling services, multi-family building risers, three-phase equipment feeders.

Above 4/0 AWG the size series changes to thousands of circular mils. 250 kcmil copper carries 255 A at the 75°C column, so a 250 A circuit is the rating where copper conductors are first named in kcmil; the aluminium answer, 350 kcmil, is already two sizes into that series.

Worked example

A 250 A feeder to a small commercial building 230 ft from the service: 250 kcmil copper carries 255 A at 75°C and its 3% ceiling at 240 V and 250 A is about 276 ft, so the run clears with 46 ft in hand. 350 kcmil aluminium carries 250 A exactly and its ceiling is about 236 ft, still clear of 230 ft but with only 6 ft of margin. At this rating aluminium is dramatically cheaper and the conduit is sized to suit it, so most installers accept the tighter margin or step to 400 kcmil aluminium rather than pulling copper.

Check your exact run

These figures assume a standard installation with no derating. For your actual length, voltage, conductor material and temperature, run the numbers:

Ampacities are NEC 310.16 reference values for not more than three current-carrying conductors at 30°C ambient. They do not include ambient-temperature or conductor-bundling derating, and local wiring rules take precedence. Verify against the applicable code before installing.

Frequently Asked Questions

What size wire do I need for a 250 amp breaker?

250 kcmil copper, or 350 kcmil aluminium, sized from the 75°C column of NEC 310.16. Where every termination in the circuit is listed for 75°C, 250 kcmil copper is permitted.

Can I use aluminium wire for a 250 amp circuit?

Yes, provided every terminal is rated for aluminium (marked AL/CU) and the connector maker's instructions on antioxidant compound are followed. Aluminium has lower ampacity for a given size, so you need 350 kcmil aluminium in place of 250 kcmil copper. Aluminium is cheaper and lighter on long feeder runs, which is why services are often aluminium.

How far can I run 250 kcmil at 250 amps?

About 276 ft one-way on a 240 V single-phase circuit before voltage drop reaches 3%. Beyond that, step up one conductor size for every further increment of length.

What is the largest continuous load on a 250 amp circuit?

200 A. A continuous load is one expected to run for three hours or more, and NEC 210.19(A)(1) and 210.20(A) require the conductors and the breaker to be rated at 125% of it (215.2 and 215.3 for feeders). That is why, for example, EV chargers are always on a breaker well above their charging current.

Does this include derating?

No. These are base ampacities for not more than three current-carrying conductors at 30°C ambient. If you have more conductors in a raceway, a hot attic, or conduit in direct sun, apply the NEC 310.15 adjustment and correction factors, which will push the required size up.

What does kcmil mean, and why does the sizing stop at 4/0 AWG?

The American Wire Gauge series ends at 4/0 (0000), which is about 212,000 circular mils of cross-section. Larger conductors are named directly by their area in thousands of circular mils: 250 kcmil is 250,000 circular mils, about 127 mm². A circular mil is the area of a circle one thousandth of an inch in diameter. The AWG conversion calculator converts between AWG, kcmil, circular mils and mm² for any size.

Wire size for other amperages

All the breaker sizes side by side are in the wire ampacity chart, and the wire gauge chart gives each size's diameter and area.