35 Amp Wire Size
What gauge wire do you need for a 35 amp circuit? The short answer, the full NEC 310.16 table at all three termination ratings, and how far you can run it before voltage drop forces a bigger conductor.
Short answer
A 35 amp circuit needs 8 AWG copper or aluminium, sized from the 60°C column of NEC 310.16.
At 240 V that copper conductor stays inside a 3% voltage drop for roughly 131 ft one-way. Past that, go up a size.
A 35 A breaker may serve a continuous load of no more than 28 A (NEC 210.20(A) and 215.3, the 125% rule).
Minimum conductor by termination rating
Terminations on breakers, lugs and equipment carry a temperature rating. You size the conductor from the lowest-rated component in the circuit, so the same 35 A load can call for different sizes.
| Termination rating | Copper | Aluminium |
|---|---|---|
| 60°C (applies here) | 8 AWG (40 A) | 8 AWG (35 A) |
| 75°C | 8 AWG (50 A) | 8 AWG (40 A) |
| 90°C | 8 AWG (55 A) | 8 AWG (45 A) |
NEC 110.14(C)(1) requires the 60°C column for circuits rated 100 A or less unless every termination is listed for a higher temperature, and the 75°C column above 100 A. Most modern breakers and panels are listed 75°C, which is why the 75°C size is often what actually gets installed. The 90°C column is normally used only as a starting point for derating, not for the final size.
How far can you run it?
Ampacity sets the minimum size; voltage drop sets the maximum distance. These are one-way run lengths at 35 A on a 240 V single-phase circuit, holding drop to 3%.
| Copper size | Max one-way run at 3% | Max one-way run at 5% |
|---|---|---|
| 8 AWG | 131 ft | 219 ft |
| 6 AWG | 209 ft | 349 ft |
| 4 AWG | 330 ft | 551 ft |
| 3 AWG | 411 ft | 685 ft |
3% is the NEC's recommended limit for a branch circuit and 5% for feeder plus branch combined. Both are recommendations in informational notes, not enforceable rules, but most inspectors and specifiers treat 3% as the working target.
What runs on a 35 amp circuit
Typical loads at this rating: larger residential air-conditioning condensers and heat pumps, small tankless water heaters, 240 V shop equipment, motor circuits.
35 A sits between the two most common household ratings and turns up mostly on HVAC nameplates. 10 AWG copper is rated 35 A at the 75°C column, which looks like a match, but 2023 NEC 240.4(D)(8) caps 10 AWG at 30 A for general circuits, so a general-purpose 35 A circuit needs 8 AWG.
Worked example
A 35 A circuit to a workshop welder receptacle 120 ft from the panel: 8 AWG copper carries 40 A at the 60°C column and its 3% ceiling at 240 V and 35 A is about 131 ft, so the run clears with 11 ft to spare. A welder rarely draws its rated current for long, but a run that lands right at the ceiling is a poor place to leave a receptacle that may one day feed something else; 6 AWG raises the ceiling to about 209 ft for a modest cost on a single run.
Check your exact run
These figures assume a standard installation with no derating. For your actual length, voltage, conductor material and temperature, run the numbers:
Ampacities are NEC 310.16 reference values for not more than three current-carrying conductors at 30°C ambient. They do not include ambient-temperature or conductor-bundling derating, and local wiring rules take precedence. Verify against the applicable code before installing.
Frequently Asked Questions
What size wire do I need for a 35 amp breaker?
8 AWG copper or aluminium, sized from the 60°C column of NEC 310.16. Where every termination in the circuit is listed for 75°C, 8 AWG copper is permitted.
Can I use aluminium wire for a 35 amp circuit?
Yes, provided every terminal is rated for aluminium (marked AL/CU) and the connector maker's instructions on antioxidant compound are followed. Aluminium has lower ampacity for a given size, but at 35 A both metals land on 8 AWG: 8 AWG aluminium carries 35 A at the 60°C column, against 40 A for copper. Aluminium is cheaper and lighter on long feeder runs, which is why services are often aluminium.
How far can I run 8 AWG at 35 amps?
About 131 ft one-way on a 240 V single-phase circuit before voltage drop reaches 3%. Beyond that, step up one conductor size for every further increment of length.
What is the largest continuous load on a 35 amp circuit?
28 A. A continuous load is one expected to run for three hours or more, and NEC 210.19(A)(1) and 210.20(A) require the conductors and the breaker to be rated at 125% of it (215.2 and 215.3 for feeders). That is why, for example, EV chargers are always on a breaker well above their charging current.
Does this include derating?
No. These are base ampacities for not more than three current-carrying conductors at 30°C ambient. If you have more conductors in a raceway, a hot attic, or conduit in direct sun, apply the NEC 310.15 adjustment and correction factors, which will push the required size up.
My heat pump nameplate says maximum overcurrent 35 A with a minimum circuit ampacity of 28 A. Do I need 8 AWG?
Not necessarily. Under NEC 440.33 the conductor is sized to the minimum circuit ampacity, and under 240.4(G) the 240.4(D) small-conductor caps do not apply to Article 440 equipment. 10 AWG copper carries 30 A at 60°C and 35 A at 75°C, so with 75°C terminations it satisfies a 28 A minimum circuit ampacity and may sit on the 35 A breaker the nameplate specifies. The 8 AWG figure above is for a general-purpose 35 A circuit without that exemption.
Wire size for other amperages
All the breaker sizes side by side are in the wire ampacity chart, and the wire gauge chart gives each size's diameter and area.
Free download
Get the printable wire size charts
NEC 310.16 ampacity for copper and aluminium at 60, 75 and 90 C, how far each size runs before voltage drop bites, standard breaker sizes and AWG to mm2. Three pages, made for the van door.
Related Calculators
Continue with these related electrical tools
Wire Size Calculator
Smallest conductor that meets ampacity and the voltage-drop limit (AWG/mm2)
Ampacity Chart
NEC 310.16 copper and aluminium ampacity at 60, 75 and 90 C, with AWG to mm2
Wire Gauge Chart
AWG sizes 4/0 to 40 with diameter, area, resistance and copper amps
Conduit Fill Chart
How many THHN wires fit in EMT and PVC conduit, from NEC Chapter 9
Voltage Drop Calculator
Voltage drop over a run by length, current and conductor (AWG/mm2, 1ph/3ph/DC)
Breaker / Fuse Sizing Calculator
Next standard breaker or fuse size for a load (NEC 240.6)
Conduit Fill Calculator
NEC conduit fill percentage by conductor size and count