25 Amp Wire Size
What gauge wire do you need for a 25 amp circuit? The short answer, the full NEC 310.16 table at all three termination ratings, and how far you can run it before voltage drop forces a bigger conductor.
Short answer
A 25 amp circuit needs 10 AWG copper or aluminium, sized from the 60°C column of NEC 310.16.
At 240 V that copper conductor stays inside a 3% voltage drop for roughly 121 ft one-way. Past that, go up a size.
A 25 A breaker may serve a continuous load of no more than 20 A (NEC 210.20(A) and 215.3, the 125% rule).
Minimum conductor by termination rating
Terminations on breakers, lugs and equipment carry a temperature rating. You size the conductor from the lowest-rated component in the circuit, so the same 25 A load can call for different sizes.
| Termination rating | Copper | Aluminium |
|---|---|---|
| 60°C (applies here) | 10 AWG (30 A) | 10 AWG (25 A) |
| 75°C | 10 AWG (35 A) | 10 AWG (30 A) |
| 90°C | 10 AWG (40 A) | 10 AWG (35 A) |
The 75°C column rates 12 AWG copper at 25 A, which looks like enough for a 25 A circuit, but NEC 240.4(D) caps that conductor at a 20 A overcurrent device. That cap is what rules it out and puts 10 AWG in the answer above. The cap does not apply to motor circuits (NEC 430) or air-conditioning equipment (NEC 440), which are sized from the nameplate instead under 240.4(G).
NEC 110.14(C)(1) requires the 60°C column for circuits rated 100 A or less unless every termination is listed for a higher temperature, and the 75°C column above 100 A. Most modern breakers and panels are listed 75°C, which is why the 75°C size is often what actually gets installed. The 90°C column is normally used only as a starting point for derating, not for the final size.
How far can you run it?
Ampacity sets the minimum size; voltage drop sets the maximum distance. These are one-way run lengths at 25 A on a 240 V single-phase circuit, holding drop to 3%.
| Copper size | Max one-way run at 3% | Max one-way run at 5% |
|---|---|---|
| 10 AWG | 121 ft | 201 ft |
| 8 AWG | 184 ft | 307 ft |
| 6 AWG | 293 ft | 489 ft |
| 4 AWG | 463 ft | 771 ft |
3% is the NEC's recommended limit for a branch circuit and 5% for feeder plus branch combined. Both are recommendations in informational notes, not enforceable rules, but most inspectors and specifiers treat 3% as the working target.
What runs on a 25 amp circuit
Typical loads at this rating: residential air-conditioning condensers with a 25 A maximum overcurrent protection, small electric water heaters, 240 V baseboard heater circuits, single-phase motor circuits.
25 A is a standard NEC 240.6(A) breaker size but an uncommon general-purpose one. Most 25 A breakers protect equipment with a nameplate maximum, typically an air-conditioning unit or a motor, where the conductor is sized to the nameplate minimum circuit ampacity and the breaker to the nameplate maximum rather than to each other.
Worked example
A 4,500 W storage water heater at 240 V draws 18.75 A. NEC 422.13 treats a storage water heater of 120 gallons or less as a continuous load, so the circuit is sized at 125%: 23.4 A, which lands on a 25 A breaker. 10 AWG copper meets the 25 A requirement at the 60°C column; 12 AWG carries 25 A at 75°C but NEC 240.4(D) caps it at 20 A, so it is out. At 240 V and 25 A the 10 AWG run stays inside 3% for about 121 ft, far beyond any water heater run, so ampacity rather than distance sets the size here.
Check your exact run
These figures assume a standard installation with no derating. For your actual length, voltage, conductor material and temperature, run the numbers:
Ampacities are NEC 310.16 reference values for not more than three current-carrying conductors at 30°C ambient. They do not include ambient-temperature or conductor-bundling derating, and local wiring rules take precedence. Verify against the applicable code before installing.
Frequently Asked Questions
What size wire do I need for a 25 amp breaker?
10 AWG copper or aluminium, sized from the 60°C column of NEC 310.16. Where every termination in the circuit is listed for 75°C, 10 AWG copper is permitted.
Can I use aluminium wire for a 25 amp circuit?
Yes. Aluminium has lower ampacity for a given size, but at 25 A both metals land on 10 AWG: 10 AWG aluminium carries 25 A at the 60°C column, against 30 A for copper. Aluminium this small is uncommon in branch circuits today. Where it is used, every terminal an aluminium conductor lands on must be identified for aluminium (NEC 110.14): AL/CU on breakers and lugs, and CO/ALR on receptacles and switches of 20 A or less that the aluminium connects to directly (NEC 404.14 and 406.3). Follow the connector maker's instructions on antioxidant compound.
How far can I run 10 AWG at 25 amps?
About 121 ft one-way on a 240 V single-phase circuit before voltage drop reaches 3%. Beyond that, step up one conductor size for every further increment of length.
What is the largest continuous load on a 25 amp circuit?
20 A. A continuous load is one expected to run for three hours or more, and NEC 210.19(A)(1) and 210.20(A) require the conductors and the breaker to be rated at 125% of it (215.2 and 215.3 for feeders). That is why, for example, EV chargers are always on a breaker well above their charging current.
Does this include derating?
No. These are base ampacities for not more than three current-carrying conductors at 30°C ambient. If you have more conductors in a raceway, a hot attic, or conduit in direct sun, apply the NEC 310.15 adjustment and correction factors, which will push the required size up.
The AC condenser nameplate says minimum circuit ampacity 19.3 A and maximum breaker 25 A. Can I run 12 AWG on the 25 A breaker?
Yes, for that equipment. NEC 240.4(G) exempts air-conditioning and refrigeration circuits (Article 440) and motor circuits (Article 430) from the small-conductor caps in 240.4(D). The conductor only has to carry the nameplate minimum circuit ampacity, and 12 AWG copper carries 20 A at 60°C, so it is compliant on the 25 A device the nameplate calls for. The 10 AWG answer at the top of this page is for a general-purpose 25 A circuit, where the exemption does not apply.
Wire size for other amperages
All the breaker sizes side by side are in the wire ampacity chart, and the wire gauge chart gives each size's diameter and area.
Free download
Get the printable wire size charts
NEC 310.16 ampacity for copper and aluminium at 60, 75 and 90 C, how far each size runs before voltage drop bites, standard breaker sizes and AWG to mm2. Three pages, made for the van door.
Related Calculators
Continue with these related electrical tools
Wire Size Calculator
Smallest conductor that meets ampacity and the voltage-drop limit (AWG/mm2)
Ampacity Chart
NEC 310.16 copper and aluminium ampacity at 60, 75 and 90 C, with AWG to mm2
Wire Gauge Chart
AWG sizes 4/0 to 40 with diameter, area, resistance and copper amps
Conduit Fill Chart
How many THHN wires fit in EMT and PVC conduit, from NEC Chapter 9
Voltage Drop Calculator
Voltage drop over a run by length, current and conductor (AWG/mm2, 1ph/3ph/DC)
Breaker / Fuse Sizing Calculator
Next standard breaker or fuse size for a load (NEC 240.6)
Conduit Fill Calculator
NEC conduit fill percentage by conductor size and count