45 Amp Wire Size
What gauge wire do you need for a 45 amp circuit? The short answer, the full NEC 310.16 table at all three termination ratings, and how far you can run it before voltage drop forces a bigger conductor.
Short answer
A 45 amp circuit needs 6 AWG copper, or 4 AWG aluminium, sized from the 60°C column of NEC 310.16.
At 240 V that copper conductor stays inside a 3% voltage drop for roughly 163 ft one-way. Past that, go up a size.
A 45 A breaker may serve a continuous load of no more than 36 A (NEC 210.20(A) and 215.3, the 125% rule).
Minimum conductor by termination rating
Terminations on breakers, lugs and equipment carry a temperature rating. You size the conductor from the lowest-rated component in the circuit, so the same 45 A load can call for different sizes.
| Termination rating | Copper | Aluminium |
|---|---|---|
| 60°C (applies here) | 6 AWG (55 A) | 4 AWG (55 A) |
| 75°C | 8 AWG (50 A) | 6 AWG (50 A) |
| 90°C | 8 AWG (55 A) | 8 AWG (45 A) |
NEC 110.14(C)(1) requires the 60°C column for circuits rated 100 A or less unless every termination is listed for a higher temperature, and the 75°C column above 100 A. Most modern breakers and panels are listed 75°C, which is why the 75°C size is often what actually gets installed. The 90°C column is normally used only as a starting point for derating, not for the final size.
How far can you run it?
Ampacity sets the minimum size; voltage drop sets the maximum distance. These are one-way run lengths at 45 A on a 240 V single-phase circuit, holding drop to 3%.
| Copper size | Max one-way run at 3% | Max one-way run at 5% |
|---|---|---|
| 6 AWG | 163 ft | 271 ft |
| 4 AWG | 257 ft | 428 ft |
| 3 AWG | 320 ft | 533 ft |
| 2 AWG | 423 ft | 705 ft |
3% is the NEC's recommended limit for a branch circuit and 5% for feeder plus branch combined. Both are recommendations in informational notes, not enforceable rules, but most inspectors and specifiers treat 3% as the working target.
What runs on a 45 amp circuit
Typical loads at this rating: electric ranges and cooktops with a 40 to 45 A nameplate, tankless water heaters, larger heat pump air handlers, 240 V kilns.
At 45 A the termination rating starts to matter. 8 AWG copper carries 50 A at the 75°C column but only 40 A at 60°C, so the same circuit needs 6 AWG with 60°C terminations or NM cable, and can use 8 AWG only when every termination is listed 75°C and the conductor is THHN/THWN or similar in conduit.
Worked example
An 8.5 kW tankless water heater at 240 V draws 35.4 A. Tankless manufacturers size the circuit at 125% of the element current, the continuous-load rule of NEC 210.19, which gives 44.3 A and a 45 A breaker exactly. 6 AWG copper meets 45 A at the 60°C column and stays inside 3% for about 163 ft at 240 V; a tankless heater is almost always within 30 ft of the panel, so ampacity rather than distance sets the size. A 9 kW element would draw 37.5 A, need 46.9 A of circuit and jump to the 50 amp page.
Check your exact run
These figures assume a standard installation with no derating. For your actual length, voltage, conductor material and temperature, run the numbers:
Ampacities are NEC 310.16 reference values for not more than three current-carrying conductors at 30°C ambient. They do not include ambient-temperature or conductor-bundling derating, and local wiring rules take precedence. Verify against the applicable code before installing.
Frequently Asked Questions
What size wire do I need for a 45 amp breaker?
6 AWG copper, or 4 AWG aluminium, sized from the 60°C column of NEC 310.16. Where every termination in the circuit is listed for 75°C, 8 AWG copper is permitted.
Can I use aluminium wire for a 45 amp circuit?
Yes, provided every terminal is rated for aluminium (marked AL/CU) and the connector maker's instructions on antioxidant compound are followed. Aluminium has lower ampacity for a given size, so you need 4 AWG aluminium in place of 6 AWG copper. Aluminium is cheaper and lighter on long feeder runs, which is why services are often aluminium.
How far can I run 6 AWG at 45 amps?
About 163 ft one-way on a 240 V single-phase circuit before voltage drop reaches 3%. Beyond that, step up one conductor size for every further increment of length.
What is the largest continuous load on a 45 amp circuit?
36 A. A continuous load is one expected to run for three hours or more, and NEC 210.19(A)(1) and 210.20(A) require the conductors and the breaker to be rated at 125% of it (215.2 and 215.3 for feeders). That is why, for example, EV chargers are always on a breaker well above their charging current.
Does this include derating?
No. These are base ampacities for not more than three current-carrying conductors at 30°C ambient. If you have more conductors in a raceway, a hot attic, or conduit in direct sun, apply the NEC 310.15 adjustment and correction factors, which will push the required size up.
When can I use the 75°C column instead of 60°C?
NEC 110.14(C)(1)(a) allows the 75°C ampacity for a circuit of 100 A or less only when every termination in the circuit is listed for 75°C and the conductor itself is rated at least 75°C. Modern breakers and panel lugs are almost all marked 60/75°C, and THHN/THWN-2 is a 90°C conductor, so a conduit run usually qualifies. NM cable does not: NEC 334.80 fixes its ampacity at the 60°C column no matter what the terminations say, which is why the 8 AWG answer only works in conduit and 6 AWG is what gets pulled with cable.
Wire size for other amperages
All the breaker sizes side by side are in the wire ampacity chart, and the wire gauge chart gives each size's diameter and area.
Free download
Get the printable wire size charts
NEC 310.16 ampacity for copper and aluminium at 60, 75 and 90 C, how far each size runs before voltage drop bites, standard breaker sizes and AWG to mm2. Three pages, made for the van door.
Related Calculators
Continue with these related electrical tools
Wire Size Calculator
Smallest conductor that meets ampacity and the voltage-drop limit (AWG/mm2)
Ampacity Chart
NEC 310.16 copper and aluminium ampacity at 60, 75 and 90 C, with AWG to mm2
Wire Gauge Chart
AWG sizes 4/0 to 40 with diameter, area, resistance and copper amps
Conduit Fill Chart
How many THHN wires fit in EMT and PVC conduit, from NEC Chapter 9
Voltage Drop Calculator
Voltage drop over a run by length, current and conductor (AWG/mm2, 1ph/3ph/DC)
Breaker / Fuse Sizing Calculator
Next standard breaker or fuse size for a load (NEC 240.6)
Conduit Fill Calculator
NEC conduit fill percentage by conductor size and count