150 Amp Wire Size

What gauge wire do you need for a 150 amp circuit? The short answer, the full NEC 310.16 table at all three termination ratings, and how far you can run it before voltage drop forces a bigger conductor.

Short answer

A 150 amp circuit needs 1/0 AWG copper, or 3/0 AWG aluminium, sized from the 75°C column of NEC 310.16.

At 240 V that copper conductor stays inside a 3% voltage drop for roughly 201 ft one-way. Past that, go up a size.

A 150 A breaker may serve a continuous load of no more than 120 A (NEC 210.20(A) and 215.3, the 125% rule).

Minimum conductor by termination rating

Terminations on breakers, lugs and equipment carry a temperature rating. You size the conductor from the lowest-rated component in the circuit, so the same 150 A load can call for different sizes.

Termination rating Copper Aluminium
60°C 3/0 AWG (165 A) 4/0 AWG (150 A)
75°C (applies here) 1/0 AWG (150 A) 3/0 AWG (155 A)
90°C 1/0 AWG (170 A) 2/0 AWG (150 A)

NEC 110.14(C)(1) requires the 60°C column for circuits rated 100 A or less unless every termination is listed for a higher temperature, and the 75°C column above 100 A. Most modern breakers and panels are listed 75°C, which is why the 75°C size is often what actually gets installed. The 90°C column is normally used only as a starting point for derating, not for the final size.

How far can you run it?

Ampacity sets the minimum size; voltage drop sets the maximum distance. These are one-way run lengths at 150 A on a 240 V single-phase circuit, holding drop to 3%.

Copper size Max one-way run at 3% Max one-way run at 5%
1/0 AWG 201 ft 336 ft
2/0 AWG 238 ft 397 ft
3/0 AWG 311 ft 518 ft
4/0 AWG 387 ft 646 ft

3% is the NEC's recommended limit for a branch circuit and 5% for feeder plus branch combined. Both are recommendations in informational notes, not enforceable rules, but most inspectors and specifiers treat 3% as the working target.

What runs on a 150 amp circuit

Typical loads at this rating: dwelling services, large sub-panels, light commercial feeders.

At 150 A the aluminium option becomes economically attractive on long runs, which is why service and feeder conductors at this size are frequently aluminium.

Worked example

A 150 A feeder to a small commercial unit 190 ft from the panel: 1/0 copper meets the 150 A ampacity at the 75°C column and its 3% voltage-drop ceiling at 240 V is about 201 ft, so a 190 ft run clears it with only about 11 ft to spare. Long 150 A feeders are exactly where the aluminium-versus-copper trade-off in the note above actually gets decided, since either metal is working close to its length limit at this distance rather than comfortably inside it.

Check your exact run

These figures assume a standard installation with no derating. For your actual length, voltage, conductor material and temperature, run the numbers:

Ampacities are NEC 310.16 reference values for not more than three current-carrying conductors at 30°C ambient. They do not include ambient-temperature or conductor-bundling derating, and local wiring rules take precedence. Verify against the applicable code before installing.

Frequently Asked Questions

What size wire do I need for a 150 amp breaker?

1/0 AWG copper, or 3/0 AWG aluminium, sized from the 75°C column of NEC 310.16. Where every termination in the circuit is listed for 75°C, 1/0 AWG copper is permitted.

Can I use aluminium wire for a 150 amp circuit?

Yes, provided every terminal is rated for aluminium (marked AL/CU) and the connector maker's instructions on antioxidant compound are followed. Aluminium has lower ampacity for a given size, so you need 3/0 AWG aluminium in place of 1/0 AWG copper. Aluminium is cheaper and lighter on long feeder runs, which is why services are often aluminium.

How far can I run 1/0 AWG at 150 amps?

About 201 ft one-way on a 240 V single-phase circuit before voltage drop reaches 3%. Beyond that, step up one conductor size for every further increment of length.

What is the largest continuous load on a 150 amp circuit?

120 A. A continuous load is one expected to run for three hours or more, and NEC 210.19(A)(1) and 210.20(A) require the conductors and the breaker to be rated at 125% of it (215.2 and 215.3 for feeders). That is why, for example, EV chargers are always on a breaker well above their charging current.

Does this include derating?

No. These are base ampacities for not more than three current-carrying conductors at 30°C ambient. If you have more conductors in a raceway, a hot attic, or conduit in direct sun, apply the NEC 310.15 adjustment and correction factors, which will push the required size up.

Does a 150 A feeder to a sub-panel need GFCI or AFCI protection like a branch circuit does?

No. GFCI and AFCI requirements in NEC 210.8 and 210.12 attach to specific branch circuits (kitchens, bathrooms, dwelling-unit bedrooms and living areas, and similar), not to the feeder that supplies a sub-panel or distribution equipment. Individual branch circuits downstream of the sub-panel get their own protection as their own use requires; the feeder itself does not need it.

Wire size for other amperages

All the breaker sizes side by side are in the wire ampacity chart, and the wire gauge chart gives each size's diameter and area.

Free download

Get the printable wire size charts

NEC 310.16 ampacity for copper and aluminium at 60, 75 and 90 C, how far each size runs before voltage drop bites, standard breaker sizes and AWG to mm2. Three pages, made for the van door.

We store your email with EmailOctopus to send the charts and occasional wiring and calculator tips, nothing else. Unsubscribe any time. Privacy policy.