175 Amp Wire Size

What gauge wire do you need for a 175 amp circuit? The short answer, the full NEC 310.16 table at all three termination ratings, and how far you can run it before voltage drop forces a bigger conductor.

Short answer

A 175 amp circuit needs 2/0 AWG copper, or 4/0 AWG aluminium, sized from the 75°C column of NEC 310.16.

At 240 V that copper conductor stays inside a 3% voltage drop for roughly 204 ft one-way. Past that, go up a size.

A 175 A breaker may serve a continuous load of no more than 140 A (NEC 210.20(A) and 215.3, the 125% rule).

Minimum conductor by termination rating

Terminations on breakers, lugs and equipment carry a temperature rating. You size the conductor from the lowest-rated component in the circuit, so the same 175 A load can call for different sizes.

Termination rating Copper Aluminium
60°C 4/0 AWG (195 A) 300 kcmil (195 A)
75°C (applies here) 2/0 AWG (175 A) 4/0 AWG (180 A)
90°C 2/0 AWG (195 A) 3/0 AWG (175 A)

NEC 110.14(C)(1) requires the 60°C column for circuits rated 100 A or less unless every termination is listed for a higher temperature, and the 75°C column above 100 A. Most modern breakers and panels are listed 75°C, which is why the 75°C size is often what actually gets installed. The 90°C column is normally used only as a starting point for derating, not for the final size.

How far can you run it?

Ampacity sets the minimum size; voltage drop sets the maximum distance. These are one-way run lengths at 175 A on a 240 V single-phase circuit, holding drop to 3%.

Copper size Max one-way run at 3% Max one-way run at 5%
2/0 AWG 204 ft 340 ft
3/0 AWG 266 ft 444 ft
4/0 AWG 332 ft 554 ft
250 kcmil 394 ft 657 ft

3% is the NEC's recommended limit for a branch circuit and 5% for feeder plus branch combined. Both are recommendations in informational notes, not enforceable rules, but most inspectors and specifiers treat 3% as the working target.

What runs on a 175 amp circuit

Typical loads at this rating: dwelling services between the 150 A and 200 A tiers, sub-panels in large homes, small commercial feeders, multi-family unit feeders.

2/0 copper carries exactly 175 A at the 75°C column, so there is no margin in the copper answer; 4/0 aluminium carries 180 A. For a dwelling service, or a feeder carrying a dwelling's whole load, NEC 310.12 allows a smaller conductor than the general table, which is where 175 A services are usually installed.

Worked example

A 175 A feeder to a large detached workshop 180 ft from the service: 2/0 copper carries 175 A at the 75°C column, and its 3% ceiling at 240 V and 175 A is about 204 ft, so the run clears by 24 ft. Aluminium is the usual choice at this size and distance: 4/0 aluminium carries 180 A and its ceiling is also about 204 ft, so both metals clear the run with similar margin. A workshop that regularly draws near its feeder rating, with a welder and a compressor running together, would be worth upsizing to 3/0 copper (about 266 ft) or 250 kcmil aluminium to keep drop well under 3% at full load.

Check your exact run

These figures assume a standard installation with no derating. For your actual length, voltage, conductor material and temperature, run the numbers:

Ampacities are NEC 310.16 reference values for not more than three current-carrying conductors at 30°C ambient. They do not include ambient-temperature or conductor-bundling derating, and local wiring rules take precedence. Verify against the applicable code before installing.

Frequently Asked Questions

What size wire do I need for a 175 amp breaker?

2/0 AWG copper, or 4/0 AWG aluminium, sized from the 75°C column of NEC 310.16. Where every termination in the circuit is listed for 75°C, 2/0 AWG copper is permitted.

Can I use aluminium wire for a 175 amp circuit?

Yes, provided every terminal is rated for aluminium (marked AL/CU) and the connector maker's instructions on antioxidant compound are followed. Aluminium has lower ampacity for a given size, so you need 4/0 AWG aluminium in place of 2/0 AWG copper. Aluminium is cheaper and lighter on long feeder runs, which is why services are often aluminium.

How far can I run 2/0 AWG at 175 amps?

About 204 ft one-way on a 240 V single-phase circuit before voltage drop reaches 3%. Beyond that, step up one conductor size for every further increment of length.

What is the largest continuous load on a 175 amp circuit?

140 A. A continuous load is one expected to run for three hours or more, and NEC 210.19(A)(1) and 210.20(A) require the conductors and the breaker to be rated at 125% of it (215.2 and 215.3 for feeders). That is why, for example, EV chargers are always on a breaker well above their charging current.

Does this include derating?

No. These are base ampacities for not more than three current-carrying conductors at 30°C ambient. If you have more conductors in a raceway, a hot attic, or conduit in direct sun, apply the NEC 310.15 adjustment and correction factors, which will push the required size up.

The utility installed my 175 A service with 1/0 copper. Is that allowed?

For a dwelling, yes. NEC 310.12 provides a separate ampacity table for single-phase dwelling services and for feeders that carry the entire dwelling load, on the basis that a whole house rarely draws its full rating. That table permits 1/0 copper or 3/0 aluminium for a 175 A dwelling service, one size below the 2/0 copper and 4/0 aluminium the general 310.16 table gives on this page. The reduced sizes apply only to dwelling units; a 175 A commercial feeder, or a sub-panel that carries part of a home's load, uses the general table.

Wire size for other amperages

All the breaker sizes side by side are in the wire ampacity chart, and the wire gauge chart gives each size's diameter and area.

Free download

Get the printable wire size charts

NEC 310.16 ampacity for copper and aluminium at 60, 75 and 90 C, how far each size runs before voltage drop bites, standard breaker sizes and AWG to mm2. Three pages, made for the van door.

We store your email with EmailOctopus to send the charts and occasional wiring and calculator tips, nothing else. Unsubscribe any time. Privacy policy.