300 Amp Wire Size
What gauge wire do you need for a 300 amp circuit? The short answer, the full NEC 310.16 table at all three termination ratings, and how far you can run it before voltage drop forces a bigger conductor.
Short answer
A 300 amp circuit needs 350 kcmil copper, or 500 kcmil aluminium, sized from the 75°C column of NEC 310.16.
At 240 V that copper conductor stays inside a 3% voltage drop for roughly 314 ft one-way. Past that, go up a size.
A 300 A breaker may serve a continuous load of no more than 240 A (NEC 210.20(A) and 215.3, the 125% rule).
Minimum conductor by termination rating
Terminations on breakers, lugs and equipment carry a temperature rating. You size the conductor from the lowest-rated component in the circuit, so the same 300 A load can call for different sizes.
| Termination rating | Copper | Aluminium |
|---|---|---|
| 60°C | 500 kcmil (320 A) | 700 kcmil (315 A) |
| 75°C (applies here) | 350 kcmil (310 A) | 500 kcmil (310 A) |
| 90°C | 300 kcmil (320 A) | 400 kcmil (305 A) |
NEC 110.14(C)(1) requires the 60°C column for circuits rated 100 A or less unless every termination is listed for a higher temperature, and the 75°C column above 100 A. Most modern breakers and panels are listed 75°C, which is why the 75°C size is often what actually gets installed. The 90°C column is normally used only as a starting point for derating, not for the final size.
How far can you run it?
Ampacity sets the minimum size; voltage drop sets the maximum distance. These are one-way run lengths at 300 A on a 240 V single-phase circuit, holding drop to 3%.
| Copper size | Max one-way run at 3% | Max one-way run at 5% |
|---|---|---|
| 350 kcmil | 314 ft | 524 ft |
| 400 kcmil | 364 ft | 607 ft |
| 500 kcmil | 442 ft | 737 ft |
| 600 kcmil | 524 ft | 874 ft |
3% is the NEC's recommended limit for a branch circuit and 5% for feeder plus branch combined. Both are recommendations in informational notes, not enforceable rules, but most inspectors and specifiers treat 3% as the working target.
What runs on a 300 amp circuit
Typical loads at this rating: large dwelling services, commercial building feeders, three-phase distribution to industrial equipment, generator and transformer secondaries.
350 kcmil copper carries 310 A at the 75°C column and 500 kcmil aluminium carries 310 A. Both are heavy, stiff conductors, and at 300 A many installers instead run two parallel sets of smaller conductors per phase, which NEC 310.10(G) permits for 1/0 AWG and larger.
Worked example
A 300 A three-phase feeder from a transformer secondary 250 ft away: a single 350 kcmil copper per phase carries 310 A at 75°C, and its 3% ceiling at 240 V single-phase and 300 A is about 314 ft, so the run clears. The alternative is two parallel sets of 1/0 copper per phase, since 1/0 copper carries 150 A at 75°C and two sets give 300 A; two 1/0 conductors are far easier to pull and terminate than one 350 kcmil, and each set can be in its own raceway. In aluminium the single-conductor answer is 500 kcmil (310 A) with a ceiling of about 279 ft, or two parallel sets of 3/0 aluminium (155 A each).
Check your exact run
These figures assume a standard installation with no derating. For your actual length, voltage, conductor material and temperature, run the numbers:
Ampacities are NEC 310.16 reference values for not more than three current-carrying conductors at 30°C ambient. They do not include ambient-temperature or conductor-bundling derating, and local wiring rules take precedence. Verify against the applicable code before installing.
Frequently Asked Questions
What size wire do I need for a 300 amp breaker?
350 kcmil copper, or 500 kcmil aluminium, sized from the 75°C column of NEC 310.16. Where every termination in the circuit is listed for 75°C, 350 kcmil copper is permitted.
Can I use aluminium wire for a 300 amp circuit?
Yes, provided every terminal is rated for aluminium (marked AL/CU) and the connector maker's instructions on antioxidant compound are followed. Aluminium has lower ampacity for a given size, so you need 500 kcmil aluminium in place of 350 kcmil copper. Aluminium is cheaper and lighter on long feeder runs, which is why services are often aluminium.
How far can I run 350 kcmil at 300 amps?
About 314 ft one-way on a 240 V single-phase circuit before voltage drop reaches 3%. Beyond that, step up one conductor size for every further increment of length.
What is the largest continuous load on a 300 amp circuit?
240 A. A continuous load is one expected to run for three hours or more, and NEC 210.19(A)(1) and 210.20(A) require the conductors and the breaker to be rated at 125% of it (215.2 and 215.3 for feeders). That is why, for example, EV chargers are always on a breaker well above their charging current.
Does this include derating?
No. These are base ampacities for not more than three current-carrying conductors at 30°C ambient. If you have more conductors in a raceway, a hot attic, or conduit in direct sun, apply the NEC 310.15 adjustment and correction factors, which will push the required size up.
What are the rules for running parallel conductors at 300 A?
NEC 310.10(G) allows conductors 1/0 AWG and larger to be connected in parallel, provided each set is the same length, the same material, the same size in circular mils, the same insulation type and terminated the same way, so that the current divides equally. Where the sets run in separate raceways, each raceway needs a full-size equipment grounding conductor sized to the 300 A overcurrent device under 250.122(F), which Table 250.122 puts at 4 AWG copper, and each raceway must contain all phases of a set so the raceway does not heat inductively. Ampacity adjustment still applies: two sets in one raceway means six current-carrying conductors on a three-phase feeder, which derates each to 80% under 310.15(C).
Wire size for other amperages
All the breaker sizes side by side are in the wire ampacity chart, and the wire gauge chart gives each size's diameter and area.
Free download
Get the printable wire size charts
NEC 310.16 ampacity for copper and aluminium at 60, 75 and 90 C, how far each size runs before voltage drop bites, standard breaker sizes and AWG to mm2. Three pages, made for the van door.
Related Calculators
Continue with these related electrical tools
Wire Size Calculator
Smallest conductor that meets ampacity and the voltage-drop limit (AWG/mm2)
Ampacity Chart
NEC 310.16 copper and aluminium ampacity at 60, 75 and 90 C, with AWG to mm2
Wire Gauge Chart
AWG sizes 4/0 to 40 with diameter, area, resistance and copper amps
Conduit Fill Chart
How many THHN wires fit in EMT and PVC conduit, from NEC Chapter 9
Voltage Drop Calculator
Voltage drop over a run by length, current and conductor (AWG/mm2, 1ph/3ph/DC)
Breaker / Fuse Sizing Calculator
Next standard breaker or fuse size for a load (NEC 240.6)
Conduit Fill Calculator
NEC conduit fill percentage by conductor size and count