125 Amp Wire Size
What gauge wire do you need for a 125 amp circuit? The short answer, the full NEC 310.16 table at all three termination ratings, and how far you can run it before voltage drop forces a bigger conductor.
Short answer
A 125 amp circuit needs 1 AWG copper, or 2/0 AWG aluminium, sized from the 75°C column of NEC 310.16.
At 240 V that copper conductor stays inside a 3% voltage drop for roughly 192 ft one-way. Past that, go up a size.
A 125 A breaker may serve a continuous load of no more than 100 A (NEC 210.20(A) and 215.3, the 125% rule).
Minimum conductor by termination rating
Terminations on breakers, lugs and equipment carry a temperature rating. You size the conductor from the lowest-rated component in the circuit, so the same 125 A load can call for different sizes.
| Termination rating | Copper | Aluminium |
|---|---|---|
| 60°C | 1/0 AWG (125 A) | 3/0 AWG (130 A) |
| 75°C (applies here) | 1 AWG (130 A) | 2/0 AWG (135 A) |
| 90°C | 2 AWG (130 A) | 1/0 AWG (135 A) |
NEC 110.14(C)(1) requires the 60°C column for circuits rated 100 A or less unless every termination is listed for a higher temperature, and the 75°C column above 100 A. Most modern breakers and panels are listed 75°C, which is why the 75°C size is often what actually gets installed. The 90°C column is normally used only as a starting point for derating, not for the final size.
How far can you run it?
Ampacity sets the minimum size; voltage drop sets the maximum distance. These are one-way run lengths at 125 A on a 240 V single-phase circuit, holding drop to 3%.
| Copper size | Max one-way run at 3% | Max one-way run at 5% |
|---|---|---|
| 1 AWG | 192 ft | 321 ft |
| 1/0 AWG | 242 ft | 403 ft |
| 2/0 AWG | 286 ft | 477 ft |
| 3/0 AWG | 373 ft | 622 ft |
3% is the NEC's recommended limit for a branch circuit and 5% for feeder plus branch combined. Both are recommendations in informational notes, not enforceable rules, but most inspectors and specifiers treat 3% as the working target.
What runs on a 125 amp circuit
Typical loads at this rating: larger sub-panels, small commercial services, feeders to accessory dwelling units.
125 A is a standard NEC 240.6 breaker size and a common panel rating, sitting between the 100 A and 150 A feeder tiers.
Worked example
A 125 A feeder to a detached accessory dwelling unit 175 ft from the main panel: 1 AWG copper meets the 125 A ampacity at the 75°C column (the column that applies above 100 A) and its 3% voltage-drop ceiling at 240 V is about 192 ft, so a 175 ft run clears it, but with less margin than the shorter feeders elsewhere in this cluster, typical for ADU feeders since a detached unit is rarely close to the main panel.
Check your exact run
These figures assume a standard installation with no derating. For your actual length, voltage, conductor material and temperature, run the numbers:
Ampacities are NEC 310.16 reference values for not more than three current-carrying conductors at 30°C ambient. They do not include ambient-temperature or conductor-bundling derating, and local wiring rules take precedence. Verify against the applicable code before installing.
Frequently Asked Questions
What size wire do I need for a 125 amp breaker?
1 AWG copper, or 2/0 AWG aluminium, sized from the 75°C column of NEC 310.16. Where every termination in the circuit is listed for 75°C, 1 AWG copper is permitted.
Can I use aluminium wire for a 125 amp circuit?
Yes, provided every terminal is rated for aluminium (marked AL/CU) and the connector maker's instructions on antioxidant compound are followed. Aluminium has lower ampacity for a given size, so you need 2/0 AWG aluminium in place of 1 AWG copper. Aluminium is cheaper and lighter on long feeder runs, which is why services are often aluminium.
How far can I run 1 AWG at 125 amps?
About 192 ft one-way on a 240 V single-phase circuit before voltage drop reaches 3%. Beyond that, step up one conductor size for every further increment of length.
What is the largest continuous load on a 125 amp circuit?
100 A. A continuous load is one expected to run for three hours or more, and NEC 210.19(A)(1) and 210.20(A) require the conductors and the breaker to be rated at 125% of it (215.2 and 215.3 for feeders). That is why, for example, EV chargers are always on a breaker well above their charging current.
Does this include derating?
No. These are base ampacities for not more than three current-carrying conductors at 30°C ambient. If you have more conductors in a raceway, a hot attic, or conduit in direct sun, apply the NEC 310.15 adjustment and correction factors, which will push the required size up.
Does 125 A automatically cover an ADU's total electrical load, or could it fall short?
That is a load-calculation question, not a wire-gauge one. This page only answers what conductor 125 A itself needs. Whether 125 A is actually enough for a given ADU's connected load (heating, an EV charger, appliances, and so on) is worked out under NEC Article 220's load-calculation rules, and depends entirely on what is installed in the unit.
Wire size for other amperages
All the breaker sizes side by side are in the wire ampacity chart, and the wire gauge chart gives each size's diameter and area.
Free download
Get the printable wire size charts
NEC 310.16 ampacity for copper and aluminium at 60, 75 and 90 C, how far each size runs before voltage drop bites, standard breaker sizes and AWG to mm2. Three pages, made for the van door.
Related Calculators
Continue with these related electrical tools
Wire Size Calculator
Smallest conductor that meets ampacity and the voltage-drop limit (AWG/mm2)
Ampacity Chart
NEC 310.16 copper and aluminium ampacity at 60, 75 and 90 C, with AWG to mm2
Wire Gauge Chart
AWG sizes 4/0 to 40 with diameter, area, resistance and copper amps
Conduit Fill Chart
How many THHN wires fit in EMT and PVC conduit, from NEC Chapter 9
Voltage Drop Calculator
Voltage drop over a run by length, current and conductor (AWG/mm2, 1ph/3ph/DC)
Breaker / Fuse Sizing Calculator
Next standard breaker or fuse size for a load (NEC 240.6)
Conduit Fill Calculator
NEC conduit fill percentage by conductor size and count