What gauge wire do you need for a 30 amp circuit? The short answer, the full NEC 310.16 table at all three termination ratings, and how far you can run it before voltage drop forces a bigger conductor.
A 30 amp circuit needs 10 AWG copper, or 8 AWG aluminium, sized from the 60°C column of NEC 310.16.
At 240 V that copper conductor stays inside a 3% voltage drop for roughly 100 ft one-way. Past that, go up a size.
A 30 A breaker may serve a continuous load of no more than 24 A (NEC 210.19/215.2, the 125% rule).
Terminations on breakers, lugs and equipment carry a temperature rating. You size the conductor from the lowest-rated component in the circuit, so the same 30 A load can call for different sizes.
| Termination rating | Copper | Aluminium |
|---|---|---|
| 60°C (applies here) | 10 AWG (30 A) | 8 AWG (30 A) |
| 75°C | 10 AWG (35 A) | 8 AWG (40 A) |
| 90°C | 12 AWG (30 A) | 8 AWG (45 A) |
NEC 110.14(C)(1) requires the 60°C column for circuits rated 100 A or less unless every termination is listed for a higher temperature, and the 75°C column above 100 A. Most modern breakers and panels are listed 75°C, which is why the 75°C size is often what actually gets installed. The 90°C column is normally used only as a starting point for derating, not for the final size.
Ampacity sets the minimum size; voltage drop sets the maximum distance. These are one-way run lengths at 30 A on a 240 V single-phase circuit, holding drop to 3%.
| Copper size | Max one-way run at 3% | Max one-way run at 5% |
|---|---|---|
| 10 AWG | 100 ft | 168 ft |
| 8 AWG | 153 ft | 256 ft |
| 6 AWG | 244 ft | 407 ft |
| 4 AWG | 385 ft | 643 ft |
3% is the NEC's recommended limit for a branch circuit and 5% for feeder plus branch combined. Both are recommendations in informational notes, not enforceable rules, but most inspectors and specifiers treat 3% as the working target.
Typical loads at this rating: electric clothes dryers, small RV hookups, 240 V window air conditioners, well pumps.
NEC 240.4(D) caps 10 AWG copper at 30 A, so 10 AWG copper is the standard answer for a 30 A circuit.
These figures assume a standard installation with no derating. For your actual length, voltage, conductor material and temperature, run the numbers:
Ampacities are NEC 310.16 reference values for not more than three current-carrying conductors at 30°C ambient. They do not include ambient-temperature or conductor-bundling derating, and local wiring rules take precedence. Verify against the applicable code before installing.
10 AWG copper, or 8 AWG aluminium, sized from the 60°C column of NEC 310.16. Where every termination in the circuit is listed for 75°C, 10 AWG copper is permitted.
Yes, provided the terminations are rated for aluminium (marked AL or CU-AL) and an antioxidant compound is used. Aluminium has lower ampacity for a given size, so you need 8 AWG aluminium in place of 10 AWG copper. It is cheaper and lighter on long feeder runs, which is why services are often aluminium.
About 100 ft one-way on a 240 V single-phase circuit before voltage drop reaches 3%. Beyond that, step up one conductor size for every further increment of length.
24 A. A continuous load is one expected to run for three hours or more, and NEC 210.19 and 215.2 require the circuit to be rated at 125% of it. That is why, for example, EV chargers are always on a breaker well above their charging current.
No. These are base ampacities for not more than three current-carrying conductors at 30°C ambient. If you have more conductors in a raceway, a hot attic, or conduit in direct sun, apply the NEC 310.15 adjustment and correction factors, which will push the required size up.
Continue with these related electrical tools
Smallest conductor that meets ampacity and the voltage-drop limit (AWG/mm2)
Voltage drop over a run by length, current and conductor (AWG/mm2, 1ph/3ph/DC)
Next standard breaker or fuse size for a load (NEC 240.6)
NEC conduit fill percentage by conductor size and count
Fast, free calculators for electricians and engineers
© 2026 Electrical Calculators. All rights reserved.