30 Amp Wire Size

What gauge wire do you need for a 30 amp circuit? The short answer, the full NEC 310.16 table at all three termination ratings, and how far you can run it before voltage drop forces a bigger conductor.

Short answer

A 30 amp circuit needs 10 AWG copper, or 8 AWG aluminium, sized from the 60°C column of NEC 310.16.

At 240 V that copper conductor stays inside a 3% voltage drop for roughly 100 ft one-way. Past that, go up a size.

A 30 A breaker may serve a continuous load of no more than 24 A (NEC 210.20(A) and 215.3, the 125% rule).

Minimum conductor by termination rating

Terminations on breakers, lugs and equipment carry a temperature rating. You size the conductor from the lowest-rated component in the circuit, so the same 30 A load can call for different sizes.

Termination rating Copper Aluminium
60°C (applies here) 10 AWG (30 A) 8 AWG (35 A)
75°C 10 AWG (35 A) 8 AWG (40 A)
90°C 10 AWG (40 A) 8 AWG (45 A)

NEC 240.4(D) caps 10 AWG copper at a 30 A overcurrent device, below the 35 A its 75°C ampacity would otherwise allow. At 30 A that cap and the conductor land on the same size, so it neither forces an upsize nor leaves headroom for a larger breaker. The cap does not apply to motor circuits (NEC 430) or air-conditioning equipment (NEC 440), which are sized from the nameplate instead under 240.4(G).

NEC 110.14(C)(1) requires the 60°C column for circuits rated 100 A or less unless every termination is listed for a higher temperature, and the 75°C column above 100 A. Most modern breakers and panels are listed 75°C, which is why the 75°C size is often what actually gets installed. The 90°C column is normally used only as a starting point for derating, not for the final size.

How far can you run it?

Ampacity sets the minimum size; voltage drop sets the maximum distance. These are one-way run lengths at 30 A on a 240 V single-phase circuit, holding drop to 3%.

Copper size Max one-way run at 3% Max one-way run at 5%
10 AWG 100 ft 168 ft
8 AWG 153 ft 256 ft
6 AWG 244 ft 407 ft
4 AWG 385 ft 643 ft

3% is the NEC's recommended limit for a branch circuit and 5% for feeder plus branch combined. Both are recommendations in informational notes, not enforceable rules, but most inspectors and specifiers treat 3% as the working target.

What runs on a 30 amp circuit

Typical loads at this rating: electric clothes dryers, small RV hookups, 240 V window air conditioners, well pumps.

NEC 240.4(D) caps 10 AWG copper at 30 A, so 10 AWG copper is the standard answer for a 30 A circuit.

Worked example

A submersible well pump on a 30 A circuit, 150 ft one-way from the panel: 10 AWG copper meets the 30 A ampacity at the 60°C column, but its 3% voltage-drop ceiling at 240 V is only about 100 ft, and a 150 ft run overshoots it by half, enough sag to stress a pump motor under repeated starts. Stepping to 8 AWG raises the ceiling to roughly 153 ft, clearing the run. Well pumps and irrigation feeds are the 30 A use most likely to run this far from the panel; dryers and window units rarely do.

Check your exact run

These figures assume a standard installation with no derating. For your actual length, voltage, conductor material and temperature, run the numbers:

Ampacities are NEC 310.16 reference values for not more than three current-carrying conductors at 30°C ambient. They do not include ambient-temperature or conductor-bundling derating, and local wiring rules take precedence. Verify against the applicable code before installing.

Frequently Asked Questions

What size wire do I need for a 30 amp breaker?

10 AWG copper, or 8 AWG aluminium, sized from the 60°C column of NEC 310.16. Where every termination in the circuit is listed for 75°C, 10 AWG copper is permitted.

Can I use aluminium wire for a 30 amp circuit?

Yes, provided every terminal is rated for aluminium (marked AL/CU) and the connector maker's instructions on antioxidant compound are followed. Aluminium has lower ampacity for a given size, so you need 8 AWG aluminium in place of 10 AWG copper. Aluminium is cheaper and lighter on long feeder runs, which is why services are often aluminium.

How far can I run 10 AWG at 30 amps?

About 100 ft one-way on a 240 V single-phase circuit before voltage drop reaches 3%. Beyond that, step up one conductor size for every further increment of length.

What is the largest continuous load on a 30 amp circuit?

24 A. A continuous load is one expected to run for three hours or more, and NEC 210.19(A)(1) and 210.20(A) require the conductors and the breaker to be rated at 125% of it (215.2 and 215.3 for feeders). That is why, for example, EV chargers are always on a breaker well above their charging current.

Does this include derating?

No. These are base ampacities for not more than three current-carrying conductors at 30°C ambient. If you have more conductors in a raceway, a hot attic, or conduit in direct sun, apply the NEC 310.15 adjustment and correction factors, which will push the required size up.

Does a 30 A dryer or range circuit still use 3 wires, or does it need 4 now?

New work needs 4: two hots, a neutral, and a separate equipment grounding conductor. NEC 250.140 stopped allowing the neutral to double as the ground for ranges and dryers, so the older 3-wire method (shared neutral and ground, no separate ground wire) is only permitted where it already exists in a qualifying existing installation, not for new circuits or rewired branch circuits.

Wire size for other amperages

All the breaker sizes side by side are in the wire ampacity chart, and the wire gauge chart gives each size's diameter and area.

Free download

Get the printable wire size charts

NEC 310.16 ampacity for copper and aluminium at 60, 75 and 90 C, how far each size runs before voltage drop bites, standard breaker sizes and AWG to mm2. Three pages, made for the van door.

We store your email with EmailOctopus to send the charts and occasional wiring and calculator tips, nothing else. Unsubscribe any time. Privacy policy.