400 Amp Wire Size
What gauge wire do you need for a 400 amp circuit? The short answer, the full NEC 310.16 table at all three termination ratings, and how far you can run it before voltage drop forces a bigger conductor.
Short answer
A 400 amp circuit needs 600 kcmil copper, or 900 kcmil aluminium, sized from the 75°C column of NEC 310.16.
At 240 V that copper conductor stays inside a 3% voltage drop for roughly 393 ft one-way. Past that, go up a size.
A 400 A breaker may serve a continuous load of no more than 320 A (NEC 210.20(A) and 215.3, the 125% rule).
Minimum conductor by termination rating
Terminations on breakers, lugs and equipment carry a temperature rating. You size the conductor from the lowest-rated component in the circuit, so the same 400 A load can call for different sizes.
| Termination rating | Copper | Aluminium |
|---|---|---|
| 60°C | 750 kcmil (400 A) | 1250 kcmil (405 A) |
| 75°C (applies here) | 600 kcmil (420 A) | 900 kcmil (425 A) |
| 90°C | 500 kcmil (430 A) | 700 kcmil (425 A) |
NEC 110.14(C)(1) requires the 60°C column for circuits rated 100 A or less unless every termination is listed for a higher temperature, and the 75°C column above 100 A. Most modern breakers and panels are listed 75°C, which is why the 75°C size is often what actually gets installed. The 90°C column is normally used only as a starting point for derating, not for the final size.
How far can you run it?
Ampacity sets the minimum size; voltage drop sets the maximum distance. These are one-way run lengths at 400 A on a 240 V single-phase circuit, holding drop to 3%.
| Copper size | Max one-way run at 3% | Max one-way run at 5% |
|---|---|---|
| 600 kcmil | 393 ft | 656 ft |
| 750 kcmil | 476 ft | 793 ft |
3% is the NEC's recommended limit for a branch circuit and 5% for feeder plus branch combined. Both are recommendations in informational notes, not enforceable rules, but most inspectors and specifiers treat 3% as the working target.
What runs on a 400 amp circuit
Typical loads at this rating: large dwelling services, commercial and industrial feeders, multi-unit buildings.
At 400 A a single conductor per phase becomes large and stiff, so installers commonly run two parallel sets of smaller conductors instead. Parallel runs are permitted by NEC 310.10(G) at 1/0 and larger.
Worked example
A 400 A feeder to a small commercial building, 300 ft from the service: a single 600 kcmil copper conductor per phase meets the 400 A ampacity at the 75°C column, and its 3% voltage-drop ceiling at 240 V is about 393 ft, so a 300 ft run clears it without needing parallel copper runs at all. A single aluminium conductor needs 900 kcmil to carry the full 400 A: it is rated 425 A at the 75°C column. At 385 A and 395 A, 750 and 800 kcmil can sit on a 400 A breaker under NEC 240.4(B) only where the calculated load is no more than the conductor's ampacity. Aluminium conductors this large are hard to pull and to land, so aluminium feeders at this rating are commonly run as two parallel sets of 250 kcmil aluminium per phase instead, 205 A each and 410 A together, which is the parallel-run treatment the note above describes.
Check your exact run
These figures assume a standard installation with no derating. For your actual length, voltage, conductor material and temperature, run the numbers:
Ampacities are NEC 310.16 reference values for not more than three current-carrying conductors at 30°C ambient. They do not include ambient-temperature or conductor-bundling derating, and local wiring rules take precedence. Verify against the applicable code before installing.
Frequently Asked Questions
What size wire do I need for a 400 amp breaker?
600 kcmil copper, or 900 kcmil aluminium, sized from the 75°C column of NEC 310.16. Where every termination in the circuit is listed for 75°C, 600 kcmil copper is permitted.
Can I use aluminium wire for a 400 amp circuit?
Yes, provided every terminal is rated for aluminium (marked AL/CU) and the connector maker's instructions on antioxidant compound are followed. Aluminium has lower ampacity for a given size, so you need 900 kcmil aluminium in place of 600 kcmil copper. Aluminium is cheaper and lighter on long feeder runs, which is why services are often aluminium.
How far can I run 600 kcmil at 400 amps?
About 393 ft one-way on a 240 V single-phase circuit before voltage drop reaches 3%. Beyond that, step up one conductor size for every further increment of length.
What is the largest continuous load on a 400 amp circuit?
320 A. A continuous load is one expected to run for three hours or more, and NEC 210.19(A)(1) and 210.20(A) require the conductors and the breaker to be rated at 125% of it (215.2 and 215.3 for feeders). That is why, for example, EV chargers are always on a breaker well above their charging current.
Does this include derating?
No. These are base ampacities for not more than three current-carrying conductors at 30°C ambient. If you have more conductors in a raceway, a hot attic, or conduit in direct sun, apply the NEC 310.15 adjustment and correction factors, which will push the required size up.
Does a 400 A residential service need one 400 A main disconnect, or are two 200 A panels standard practice?
Both are done, and it is largely a utility-metering and equipment-availability choice rather than a hard NEC limit. NEC 230.71 permits up to six disconnects for a service, which is the rule that lets installers split a 400 A load across two 200 A meter/panel sets instead of sourcing a single 400 A main. It is common where a large dwelling or mixed-use building exceeds a single 200 A service but a true 400 A main disconnect is not readily available or needed.
Wire size for other amperages
All the breaker sizes side by side are in the wire ampacity chart, and the wire gauge chart gives each size's diameter and area.
Free download
Get the printable wire size charts
NEC 310.16 ampacity for copper and aluminium at 60, 75 and 90 C, how far each size runs before voltage drop bites, standard breaker sizes and AWG to mm2. Three pages, made for the van door.
Related Calculators
Continue with these related electrical tools
Wire Size Calculator
Smallest conductor that meets ampacity and the voltage-drop limit (AWG/mm2)
Ampacity Chart
NEC 310.16 copper and aluminium ampacity at 60, 75 and 90 C, with AWG to mm2
Wire Gauge Chart
AWG sizes 4/0 to 40 with diameter, area, resistance and copper amps
Conduit Fill Chart
How many THHN wires fit in EMT and PVC conduit, from NEC Chapter 9
Voltage Drop Calculator
Voltage drop over a run by length, current and conductor (AWG/mm2, 1ph/3ph/DC)
Breaker / Fuse Sizing Calculator
Next standard breaker or fuse size for a load (NEC 240.6)
Conduit Fill Calculator
NEC conduit fill percentage by conductor size and count