20 Amp Wire Size

What gauge wire do you need for a 20 amp circuit? The short answer, the full NEC 310.16 table at all three termination ratings, and how far you can run it before voltage drop forces a bigger conductor.

Short answer

A 20 amp circuit needs 12 AWG copper, or 8 AWG aluminium, sized from the 60°C column of NEC 310.16.

At 120 V that copper conductor stays inside a 3% voltage drop for roughly 44 ft one-way. Past that, go up a size.

A 20 A breaker may serve a continuous load of no more than 16 A (NEC 210.19/215.2, the 125% rule).

Minimum conductor by termination rating

Terminations on breakers, lugs and equipment carry a temperature rating. You size the conductor from the lowest-rated component in the circuit, so the same 20 A load can call for different sizes.

Termination rating Copper Aluminium
60°C (applies here) 12 AWG (20 A) 8 AWG (30 A)
75°C 14 AWG (20 A) 8 AWG (40 A)
90°C 14 AWG (25 A) 8 AWG (45 A)

NEC 110.14(C)(1) requires the 60°C column for circuits rated 100 A or less unless every termination is listed for a higher temperature, and the 75°C column above 100 A. Most modern breakers and panels are listed 75°C, which is why the 75°C size is often what actually gets installed. The 90°C column is normally used only as a starting point for derating, not for the final size.

How far can you run it?

Ampacity sets the minimum size; voltage drop sets the maximum distance. These are one-way run lengths at 20 A on a 120 V single-phase circuit, holding drop to 3%.

Copper size Max one-way run at 3% Max one-way run at 5%
12 AWG 44 ft 74 ft
10 AWG 75 ft 126 ft
8 AWG 115 ft 192 ft
6 AWG 183 ft 305 ft

3% is the NEC's recommended limit for a branch circuit and 5% for feeder plus branch combined. Both are recommendations in informational notes, not enforceable rules, but most inspectors and specifiers treat 3% as the working target.

What runs on a 20 amp circuit

Typical loads at this rating: kitchen and bathroom small-appliance circuits, general-purpose 120 V receptacle circuits, garage outlets.

NEC 240.4(D) caps 12 AWG copper at 20 A regardless of its 75 C ampacity, so 12 AWG is both the minimum and the practical answer.

Check your exact run

These figures assume a standard installation with no derating. For your actual length, voltage, conductor material and temperature, run the numbers:

Ampacities are NEC 310.16 reference values for not more than three current-carrying conductors at 30°C ambient. They do not include ambient-temperature or conductor-bundling derating, and local wiring rules take precedence. Verify against the applicable code before installing.

Frequently Asked Questions

What size wire do I need for a 20 amp breaker?

12 AWG copper, or 8 AWG aluminium, sized from the 60°C column of NEC 310.16. Where every termination in the circuit is listed for 75°C, 14 AWG copper is permitted.

Can I use aluminium wire for a 20 amp circuit?

Yes, provided the terminations are rated for aluminium (marked AL or CU-AL) and an antioxidant compound is used. Aluminium has lower ampacity for a given size, so you need 8 AWG aluminium in place of 12 AWG copper. It is cheaper and lighter on long feeder runs, which is why services are often aluminium.

How far can I run 12 AWG at 20 amps?

About 44 ft one-way on a 120 V single-phase circuit before voltage drop reaches 3%. Beyond that, step up one conductor size for every further increment of length.

What is the largest continuous load on a 20 amp circuit?

16 A. A continuous load is one expected to run for three hours or more, and NEC 210.19 and 215.2 require the circuit to be rated at 125% of it. That is why, for example, EV chargers are always on a breaker well above their charging current.

Does this include derating?

No. These are base ampacities for not more than three current-carrying conductors at 30°C ambient. If you have more conductors in a raceway, a hot attic, or conduit in direct sun, apply the NEC 310.15 adjustment and correction factors, which will push the required size up.