15 Amp Wire Size
What gauge wire do you need for a 15 amp circuit? The short answer, the full NEC 310.16 table at all three termination ratings, and how far you can run it before voltage drop forces a bigger conductor.
Short answer
A 15 amp circuit needs 14 AWG copper, or 12 AWG aluminium, sized from the 60°C column of NEC 310.16.
At 120 V that copper conductor stays inside a 3% voltage drop for roughly 38 ft one-way. Past that, go up a size.
A 15 A breaker may serve a continuous load of no more than 12 A (NEC 210.20(A) and 215.3, the 125% rule).
Minimum conductor by termination rating
Terminations on breakers, lugs and equipment carry a temperature rating. You size the conductor from the lowest-rated component in the circuit, so the same 15 A load can call for different sizes.
| Termination rating | Copper | Aluminium |
|---|---|---|
| 60°C (applies here) | 14 AWG (15 A) | 12 AWG (15 A) |
| 75°C | 14 AWG (20 A) | 12 AWG (20 A) |
| 90°C | 14 AWG (25 A) | 12 AWG (25 A) |
NEC 240.4(D) caps 14 AWG copper at a 15 A overcurrent device, below the 20 A its 75°C ampacity would otherwise allow. At 15 A that cap and the conductor land on the same size, so it neither forces an upsize nor leaves headroom for a larger breaker. The cap does not apply to motor circuits (NEC 430) or air-conditioning equipment (NEC 440), which are sized from the nameplate instead under 240.4(G).
NEC 110.14(C)(1) requires the 60°C column for circuits rated 100 A or less unless every termination is listed for a higher temperature, and the 75°C column above 100 A. Most modern breakers and panels are listed 75°C, which is why the 75°C size is often what actually gets installed. The 90°C column is normally used only as a starting point for derating, not for the final size.
How far can you run it?
Ampacity sets the minimum size; voltage drop sets the maximum distance. These are one-way run lengths at 15 A on a 120 V single-phase circuit, holding drop to 3%.
| Copper size | Max one-way run at 3% | Max one-way run at 5% |
|---|---|---|
| 14 AWG | 38 ft | 64 ft |
| 12 AWG | 59 ft | 99 ft |
| 10 AWG | 100 ft | 168 ft |
| 8 AWG | 153 ft | 256 ft |
3% is the NEC's recommended limit for a branch circuit and 5% for feeder plus branch combined. Both are recommendations in informational notes, not enforceable rules, but most inspectors and specifiers treat 3% as the working target.
What runs on a 15 amp circuit
Typical loads at this rating: general lighting circuits, bedroom and living-room receptacles, bathroom exhaust fans, smoke detector circuits.
14 AWG copper is the smallest branch-circuit conductor the NEC allows for general use, and 2023 NEC 240.4(D)(4) caps its overcurrent protection at 15 A. That makes 14 AWG the exact fit for a 15 A breaker, with no larger conductor needed for ampacity; the only reason to go up to 12 AWG is distance.
Worked example
A 15 A lighting circuit feeding a detached garage 70 ft from the panel: 14 AWG copper carries 15 A at the 60°C column, but at 120 V its 3% voltage-drop ceiling at full load is only about 38 ft. Real lighting circuits rarely draw the full 15 A, so the sag at 70 ft is smaller than the table implies, but a garage circuit that also feeds a receptacle for a compressor or a shop vac will see the full current in bursts. 12 AWG stretches the ceiling to about 59 ft and 10 AWG to about 100 ft; a 10 AWG run landed on a 15 A breaker is still a 15 A circuit. At 120 V, distance limits a circuit long before the conductor's ampacity does.
Check your exact run
These figures assume a standard installation with no derating. For your actual length, voltage, conductor material and temperature, run the numbers:
Ampacities are NEC 310.16 reference values for not more than three current-carrying conductors at 30°C ambient. They do not include ambient-temperature or conductor-bundling derating, and local wiring rules take precedence. Verify against the applicable code before installing.
Frequently Asked Questions
What size wire do I need for a 15 amp breaker?
14 AWG copper, or 12 AWG aluminium, sized from the 60°C column of NEC 310.16. Where every termination in the circuit is listed for 75°C, 14 AWG copper is permitted.
Can I use aluminium wire for a 15 amp circuit?
Yes. Aluminium has lower ampacity for a given size, so you need 12 AWG aluminium in place of 14 AWG copper. Aluminium this small is uncommon in branch circuits today. Where it is used, every terminal an aluminium conductor lands on must be identified for aluminium (NEC 110.14): AL/CU on breakers and lugs, and CO/ALR on receptacles and switches of 20 A or less that the aluminium connects to directly (NEC 404.14 and 406.3). Follow the connector maker's instructions on antioxidant compound.
How far can I run 14 AWG at 15 amps?
About 38 ft one-way on a 120 V single-phase circuit before voltage drop reaches 3%. Beyond that, step up one conductor size for every further increment of length.
What is the largest continuous load on a 15 amp circuit?
12 A. A continuous load is one expected to run for three hours or more, and NEC 210.19(A)(1) and 210.20(A) require the conductors and the breaker to be rated at 125% of it (215.2 and 215.3 for feeders). That is why, for example, EV chargers are always on a breaker well above their charging current.
Does this include derating?
No. These are base ampacities for not more than three current-carrying conductors at 30°C ambient. If you have more conductors in a raceway, a hot attic, or conduit in direct sun, apply the NEC 310.15 adjustment and correction factors, which will push the required size up.
Can I use 12 AWG wire on a 15 A breaker?
Yes. NEC 240.4(D) sets a maximum overcurrent device for each small conductor (15 A for 14 AWG, 20 A for 12 AWG, 30 A for 10 AWG), not a minimum. A larger conductor on a smaller breaker is always permitted and is the normal way to fix voltage drop on a long 15 A run. What you cannot do is the reverse: 14 AWG on a 20 A breaker is a violation regardless of the 75°C column showing 20 A for it.
Wire size for other amperages
All the breaker sizes side by side are in the wire ampacity chart, and the wire gauge chart gives each size's diameter and area.
Free download
Get the printable wire size charts
NEC 310.16 ampacity for copper and aluminium at 60, 75 and 90 C, how far each size runs before voltage drop bites, standard breaker sizes and AWG to mm2. Three pages, made for the van door.
Related Calculators
Continue with these related electrical tools
Wire Size Calculator
Smallest conductor that meets ampacity and the voltage-drop limit (AWG/mm2)
Ampacity Chart
NEC 310.16 copper and aluminium ampacity at 60, 75 and 90 C, with AWG to mm2
Wire Gauge Chart
AWG sizes 4/0 to 40 with diameter, area, resistance and copper amps
Conduit Fill Chart
How many THHN wires fit in EMT and PVC conduit, from NEC Chapter 9
Voltage Drop Calculator
Voltage drop over a run by length, current and conductor (AWG/mm2, 1ph/3ph/DC)
Breaker / Fuse Sizing Calculator
Next standard breaker or fuse size for a load (NEC 240.6)
Conduit Fill Calculator
NEC conduit fill percentage by conductor size and count