Wire Size for an EV Charger

A Level 2 EV charger draws its full current for hours at a time, and NEC 625.42 treats EV charging as a continuous load. The circuit therefore has to be rated at 125% of the charger output, which puts a 48 A charger on a 60 A circuit and pushes the conductor size up with it.

Short answer

The 60 A, 240 V circuit for an EV charger needs 4 AWG copper, or 3 AWG aluminium, sized from the 60°C column of NEC 310.16.

At the 48 A this actually draws, that copper conductor stays inside a 3% voltage drop for roughly 241 ft one-way, so a typical 45 ft run needs no upsizing.

Wiring: two hots and an equipment grounding conductor; a neutral only if the unit needs 120 V for its electronics.

The circuit

The 48 A charger on this page is the largest common residential unit, needing a 60 A circuit. Smaller units are wired to the same rule: a 32 A charger needs 40 A, a 40 A charger needs 50 A. A 48 A unit is normally hardwired. It cannot use the common NEMA 14-50 receptacle: that is rated 50 A, and NEC 210.21(B)(1) does not allow a single receptacle rated below its 60 A circuit, which is why 14-50 plug-in chargers stop at 40 A of charging. The 2023 NEC (625.44) also allows a 60 A NEMA 14-60 receptacle for EV equipment, so a 48 A unit sold with a 14-60 plug can plug in where that edition is adopted.

Supply240 V, single-phase
Running load48 A
Continuous load?Yes, so the circuit is rated at 125% of the load (48 × 1.25 = 60 A)
Overcurrent device60 A two-pole
Conductor sized to60 A, from the 60 A circuit rating, itself 125% of the 48 A charger output under NEC 625.41 and 210.19(A)(1)
Copper conductor4 AWG (70 A at 60°C)
Aluminium conductor3 AWG (65 A at 60°C)
Typical run length45 ft one-way

NEC 625.42 makes EV charging a continuous load, 625.41 requires the overcurrent device to be rated at not less than 125% of the maximum charger output, and 210.19(A)(1) requires the conductors to carry the same 125%. For 48 A that is 60 A exactly, and 60 A is a standard size, so the circuit is 60 A. The charger still draws only 48 A; the extra 12 A of rating is headroom the code requires.

Sizes at each termination rating

These are the ampacity minimums at each column. Terminations carry their own temperature rating, and the conductor is sized from the lowest-rated component in the circuit. NM cable is fixed at the 60°C column by NEC 334.80 whatever the terminations are rated, which is why a cable installation often needs a larger conductor than the same circuit in conduit.

Termination rating Copper Aluminium
60°C (applies here) 4 AWG (70 A) 3 AWG (65 A)
75°C 6 AWG (65 A) 4 AWG (65 A)
90°C 6 AWG (75 A) 4 AWG (75 A)

How far can you run it?

Ampacity sets the minimum size; voltage drop sets the maximum distance. These are one-way run lengths at the 48 A this load actually draws on a 240 V single-phase circuit.

Copper size Max one-way run at 3% Max one-way run at 5%
4 AWG 241 ft 402 ft
3 AWG 300 ft 500 ft
2 AWG 396 ft 661 ft
1 AWG 502 ft 836 ft

3% is the NEC's recommended limit for a branch circuit and 5% for feeder plus branch combined. Both live in informational notes rather than enforceable rules, but 3% is what most inspectors and specifiers work to.

Do not apply the 125% rule twice

The most common error is multiplying by 1.25 a second time. Manufacturers publish a minimum breaker size that already has the continuous-load factor built in, so a unit whose manual says "requires a 60 A circuit" needs a 60 A circuit, not 75 A. Set against that, the opposite error is also common: sizing the circuit to the charger's 48 A output and fitting a 50 A breaker, which can trip during a long charge and is a genuine code violation rather than a nuisance. Read the installation manual, take the breaker size it states, and size the conductor to that device.

The code articles that apply

NEC 625.41

The overcurrent device protecting EV charging equipment must be rated for continuous duty and at not less than 125% of the equipment's maximum load, which is the rule that turns 48 A of charging into a 60 A breaker.

NEC 625.42

EV charging loads are continuous loads. Where the equipment has an adjustable output and access to the adjustment is restricted (a tool-only cover, a locked door or password-protected software), the circuit is sized from the adjusted setting on its rating label, at 125%, so dialling a charger down at commissioning is a legitimate way to fit a larger unit onto an existing smaller circuit.

NEC 210.8(A)

Ground-fault protection requirements for receptacles in garages and outdoors apply to a receptacle-connected charger, and 625.54 requires GFCI on every receptacle installed for EV charging. A hardwired charger on a 60 A circuit is not a receptacle and relies on the protection in the listed equipment; under the 2023 NEC, a hardwired unit at a dwelling on a circuit of 50 A or less needs GFCI under 210.8(F) if it is outdoors, in a garage with its floor at or below grade, or in an accessory building.

NEC 220.57

The load calculation for a service or feeder uses 7,200 VA or the nameplate of the EV supply equipment, whichever is larger. Where an energy management system set up under 750.30 limits the load, 220.70 lets the calculation use its setpoint instead.

Full guide: EV charger wire and breaker size

The long-form walkthrough, with the sizes for 16 A, 32 A, 40 A and 48 A units side by side.

Check your exact run

These figures assume a standard installation with no derating. For your actual length, voltage, conductor material and termination rating, run the numbers:

Ampacities are NEC 310.16 reference values for not more than three current-carrying conductors at 30°C ambient, with no derating applied. Local wiring rules and the equipment manufacturer's instructions take precedence. Verify against the applicable code before installing.

Free download

Get the printable wire size charts

NEC 310.16 ampacity for copper and aluminium at 60, 75 and 90 C, how far each size runs before voltage drop bites, standard breaker sizes and AWG to mm2. Three pages, made for the van door.

We store your email with EmailOctopus to send the charts and occasional wiring and calculator tips, nothing else. Unsubscribe any time. Privacy policy.

Frequently Asked Questions

What size wire for a 48 amp EV charger?

A 48 A charger needs a 60 A circuit under the 125% continuous-load rule in NEC 625.41. Copper 4 AWG carries 70 A at the 60°C column, enough for the 60 A circuit, and is the answer for NM cable or 60°C terminations; 6 AWG copper is rated 65 A at the 75°C column and is permitted where every termination is listed 75°C and the conductor is a 75°C or 90°C type in conduit, which is the usual hardwired installation.

Why is the breaker bigger than the charger current?

Because charging is continuous. NEC 625.41 requires the circuit to be rated at 125% of the charger output so the conductors and the breaker are not run at their limit for hours. The charger still draws only its rated current; the extra capacity is margin.

Can I plug a Level 2 charger into a dryer outlet?

Not sensibly. A dryer circuit is 30 A and not rated as continuous, so the most a charger could draw from it is 24 A, and the NEMA 14-30 outlet does not match the NEMA 14-50 plug most portable units use. Adapters that bridge the two exist and are a common cause of overheated receptacles. If you want to charge from an existing circuit, set the charger's output down to 24 A rather than adapting the plug.

Do I need to upgrade my service for an EV charger?

Often not. A load calculation under NEC Article 220 decides it, using 7,200 VA or the nameplate for the charger under 220.57. Where the calculation comes out over the service rating, an energy management system under 750.30 that sheds or limits charging when other loads are running is frequently cheaper than a service upgrade and is explicitly recognised by the code.

Should I hardwire or use a receptacle?

A 48 A charger is normally hardwired. It cannot use a NEMA 14-50 receptacle: that is rated 50 A, and NEC 210.21(B)(1) does not allow a single receptacle rated below its 60 A circuit, so 14-50 plug-in chargers stop at 40 A of charging. The 2023 NEC (625.44) also allows a 60 A NEMA 14-60 receptacle, so a 48 A unit sold with that plug can plug in where the 2023 code is adopted. A charger of 40 A or less can be hardwired or plugged into a 14-50: hardwiring generally runs cooler and removes the plug and receptacle as a failure point, while a receptacle makes the unit easy to swap. A receptacle installed for EV charging also needs GFCI protection under NEC 625.54.