Wire Size for an Air Conditioner
A central air-conditioning condenser or heat pump outdoor unit is the one circuit on this site where you do not size from the breaker at all. The unit's data plate gives two numbers, minimum circuit ampacity and maximum overcurrent protection, and those two numbers replace the usual calculation. Reading them the wrong way round is the most common mistake on this job.
Short answer
The 30 A, 240 V circuit for an air conditioner needs 10 AWG copper or aluminium, sized from the 60°C column of NEC 310.16.
At the 23 A this actually draws, that copper conductor stays inside a 3% voltage drop for roughly 131 ft one-way, so a typical 40 ft run needs no upsizing.
Wiring: two hots and an equipment grounding conductor; no neutral for a straight 240 V condenser.
The circuit
A typical two to three ton residential condenser has a minimum circuit ampacity around 23 A and a maximum overcurrent protective device of 30 to 40 A. The circuit is a dedicated 240 V two-pole breaker running to a fused or non-fused disconnect within sight of the unit, then in liquidtight flexible conduit to the unit's terminals. There is no neutral: the compressor and fan are both 240 V.
| Supply | 240 V, single-phase |
| Running load | 23 A |
| Continuous load? | No, so the 125% rule does not apply |
| Overcurrent device | 30 A two-pole |
| Conductor sized to | 23 A, from the unit's minimum circuit ampacity, which already includes the 125% factor NEC 440.32 requires, not the 30 A device |
| Copper conductor | 10 AWG (30 A at 60°C) |
| Aluminium conductor | 10 AWG (25 A at 60°C) |
| Typical run length | 40 ft one-way |
Motor and air-conditioning circuits are deliberately protected above their conductor ampacity so the breaker rides through the compressor's starting inrush without tripping. That is why the data plate can specify a 30 A or 40 A maximum device on a circuit whose minimum ampacity is 23 A. The conductor is sized to the minimum circuit ampacity; the breaker is sized at or below the maximum overcurrent protection. The two numbers are not meant to match.
Sizes at each termination rating
These are the ampacity minimums at each column. Terminations carry their own temperature rating, and the conductor is sized from the lowest-rated component in the circuit. NM cable is fixed at the 60°C column by NEC 334.80 whatever the terminations are rated, which is why a cable installation often needs a larger conductor than the same circuit in conduit.
| Termination rating | Copper | Aluminium |
|---|---|---|
| 60°C (applies here) | 10 AWG (30 A) | 10 AWG (25 A) |
| 75°C | 12 AWG (25 A) | 10 AWG (30 A) |
| 90°C | 14 AWG (25 A) | 12 AWG (25 A) |
Aluminium smaller than 8 AWG is uncommon in branch circuits today. Where it is used, every terminal an aluminium conductor lands on must be identified for aluminium (NEC 110.14), marked AL/CU on breakers and lugs. The equipment's own instructions decide whether it accepts aluminium at all (NEC 110.3(B)).
How far can you run it?
Ampacity sets the minimum size; voltage drop sets the maximum distance. These are one-way run lengths at the 23 A this load actually draws on a 240 V single-phase circuit.
| Copper size | Max one-way run at 3% | Max one-way run at 5% |
|---|---|---|
| 10 AWG | 131 ft | 219 ft |
| 8 AWG | 200 ft | 334 ft |
| 6 AWG | 318 ft | 531 ft |
| 4 AWG | 503 ft | 839 ft |
3% is the NEC's recommended limit for a branch circuit and 5% for feeder plus branch combined. Both live in informational notes rather than enforceable rules, but 3% is what most inspectors and specifiers work to.
The nameplate overrides the usual small-conductor caps
On a general circuit, NEC 240.4(D) would forbid 10 AWG copper on anything above a 30 A device and 12 AWG above 20 A. Air-conditioning equipment is exempt: NEC 240.4(G) sends Article 440 equipment to its own rules, so a conductor sized to the minimum circuit ampacity may sit behind the larger device the data plate calls for. A unit with a minimum circuit ampacity of 23 A and a maximum overcurrent protection of 40 A can legitimately be wired in 10 AWG copper on a 40 A breaker, which looks wrong against the ordinary table and is correct here. What you cannot do is use the exemption in the other direction: the conductor still has to meet the minimum circuit ampacity, and the device must not exceed the stated maximum.
The code articles that apply
NEC 440.32
Branch-circuit conductors supplying a single motor-compressor must have an ampacity not less than 125% of the rated-load current or the branch-circuit selection current, whichever is greater. The manufacturer has already done this arithmetic and printed the result as the minimum circuit ampacity.
NEC 440.22
Sets the maximum rating of the branch-circuit short-circuit and ground-fault protective device, which is the figure printed on the plate as maximum overcurrent protection. The installed device must not exceed it.
NEC 240.4(G)
Exempts air-conditioning and refrigeration equipment conductors from the small-conductor caps in 240.4(D), sending them to Article 440 instead.
NEC 440.14
A disconnecting means must be located within sight from and readily accessible from the air-conditioning equipment, which is the service disconnect box on the wall beside the condenser.
Check your exact run
These figures assume a standard installation with no derating. For your actual length, voltage, conductor material and termination rating, run the numbers:
Ampacities are NEC 310.16 reference values for not more than three current-carrying conductors at 30°C ambient, with no derating applied. Local wiring rules and the equipment manufacturer's instructions take precedence. Verify against the applicable code before installing.
Free download
Get the printable wire size charts
NEC 310.16 ampacity for copper and aluminium at 60, 75 and 90 C, how far each size runs before voltage drop bites, standard breaker sizes and AWG to mm2. Three pages, made for the van door.
Frequently Asked Questions
What do MCA and MOCP mean on the data plate?
MCA is the minimum circuit ampacity: the smallest conductor ampacity the circuit may have, already including the 125% factor from NEC 440.32. MOCP is the maximum overcurrent protection: the largest breaker or fuse permitted ahead of it. Size the wire to the MCA and the breaker at or below the MOCP. They are two different jobs and the numbers are meant to differ.
Can I fit a smaller breaker than the MOCP?
You may fit a smaller standard device provided it still allows the unit to start and run without nuisance tripping, and provided it is not below what the equipment needs. In practice manufacturers specify a value that works, and going lower is the usual cause of a compressor that trips the breaker on a hot afternoon when starting current is highest.
Does an air conditioner need a fused disconnect?
NEC 440.14 requires a disconnecting means within sight of the unit; whether it is fused depends on the equipment. Where the data plate specifies maximum fuse size rather than maximum breaker, or where the branch device is further from the unit than the code allows, a fused pull-out disconnect is used. A non-fused disconnect is common where the breaker in the panel provides the protection.
Can a window air conditioner use an ordinary outlet?
A 120 V window unit plugs into a standard receptacle, but NEC 440.62 limits a cord-and-plug room air conditioner to 80% of the branch circuit rating where other loads share the circuit, or 50% where the circuit also supplies lighting. A large 240 V window unit needs its own circuit and the sizing on this page.
Why is my heat pump on a bigger circuit than the AC it replaced?
A heat pump runs in winter as well as summer and often includes auxiliary electric strip heat, which is a genuinely continuous load and is added to the data plate figures. That is what pushes the minimum circuit ampacity up, sometimes into a completely different conductor size, even though the cooling capacity is unchanged.
Related Calculators
Continue with these related electrical tools
Wire Size Calculator
Smallest conductor that meets ampacity and the voltage-drop limit (AWG/mm2)
Motor FLA Calculator
Motor full-load amps from horsepower, voltage and phase
Breaker / Fuse Sizing Calculator
Next standard breaker or fuse size for a load (NEC 240.6)
Amps to kW Calculator
Kilowatts from a current reading, single or three-phase
Ampacity Chart
NEC 310.16 copper and aluminium ampacity at 60, 75 and 90 C, with AWG to mm2
Conduit Fill Chart
How many THHN wires fit in EMT and PVC conduit, from NEC Chapter 9