Wire Size for a Well Pump
A submersible well pump is the circuit where distance, not current, decides the wire size. The pump itself is small, often 1 hp or less, but the run from the panel to the well head and then down the borehole is long, and a motor that sees low voltage at start draws more current and runs hotter. This page sizes the supply run; the drop cable down the well is sized separately by the pump manufacturer.
Short answer
The 20 A, 240 V circuit for a well pump needs 12 AWG copper, or 10 AWG aluminium, sized from the 60°C column of NEC 310.16. Ampacity alone would allow 14 AWG, but over a typical 150 ft run voltage drop is what sets the size here.
At the 10 A this actually draws, that copper conductor stays inside a 3% voltage drop for roughly 178 ft one-way, so a typical 150 ft run needs no upsizing.
Wiring: two hots and an equipment grounding conductor to the pressure switch, then the submersible drop cable down the well.
The circuit
A typical 1 hp, 240 V submersible pump draws around 10 A running, with a starting surge several times that. The circuit is a dedicated two-pole breaker feeding the pressure switch and control box at the well head, from which the drop cable runs down the casing to the pump. A 20 A circuit suits most half to one horsepower pumps; larger deep-well and constant-pressure pumps need their own calculation from the nameplate.
| Supply | 240 V, single-phase |
| Running load | 10 A |
| Continuous load? | No, so the 125% rule does not apply |
| Overcurrent device | 20 A two-pole |
| Conductor sized to | 12.5 A, from 125% of the motor full-load current under NEC 430.22, not the 20 A device, which is sized for starting inrush under 430.52 |
| Copper conductor | 12 AWG (20 A at 60°C, chosen for voltage drop) |
| Aluminium conductor | 10 AWG (25 A at 60°C) |
| Typical run length | 150 ft one-way |
Motor circuits are protected under NEC Article 430, not by the general rules. The branch-circuit short-circuit and ground-fault device is sized from the table full-load current in 430.248, at up to 250% for an inverse-time breaker, so that starting inrush does not trip it. Overload protection is separate and is provided by the control box or the integral protector in the pump. That is why a 10 A pump sits behind a 20 A breaker and why the breaker is not the thing protecting the motor from overload.
Sizes at each termination rating
These are the ampacity minimums at each column, before the voltage-drop check above pushes the answer up a size. Terminations carry their own temperature rating, and the conductor is sized from the lowest-rated component in the circuit. NM cable is fixed at the 60°C column by NEC 334.80 whatever the terminations are rated, which is why a cable installation often needs a larger conductor than the same circuit in conduit.
| Termination rating | Copper | Aluminium |
|---|---|---|
| 60°C (applies here) | 14 AWG (15 A) | 12 AWG (15 A) |
| 75°C | 14 AWG (20 A) | 12 AWG (20 A) |
| 90°C | 14 AWG (25 A) | 12 AWG (25 A) |
Aluminium smaller than 8 AWG is uncommon in branch circuits today. Where it is used, every terminal an aluminium conductor lands on must be identified for aluminium (NEC 110.14), marked AL/CU on breakers and lugs. The equipment's own instructions decide whether it accepts aluminium at all (NEC 110.3(B)).
How far can you run it?
Ampacity sets the minimum size; voltage drop sets the maximum distance. These are one-way run lengths at the 10 A this load actually draws on a 240 V single-phase circuit.
| Copper size | Max one-way run at 3% | Max one-way run at 5% |
|---|---|---|
| 12 AWG | 178 ft | 298 ft |
| 10 AWG | 302 ft | 504 ft |
| 8 AWG | 461 ft | 768 ft |
| 6 AWG | 733 ft | 1,222 ft |
3% is the NEC's recommended limit for a branch circuit and 5% for feeder plus branch combined. Both live in informational notes rather than enforceable rules, but 3% is what most inspectors and specifiers work to.
Voltage drop, not ampacity, sizes this run
At 10 A the ampacity requirement is trivially met by 12 AWG copper, which carries 20 A. Distance is the constraint: 12 AWG holds a 3% drop for about 178 ft at this load, so a well 150 ft from the panel is inside the limit but a well at 250 ft is not, and would need 10 AWG or larger. Motors are the load least tolerant of low voltage, because a motor draws more current as its terminal voltage falls, which increases the drop further and heats the windings. Pump manufacturers publish drop-cable charts that are noticeably more conservative than a 3% branch-circuit target for exactly this reason, and where the supply run and the borehole depth are both long, both halves have to be added up rather than sized separately.
The code articles that apply
NEC 430.6(A)(1)
Conductor and device sizing uses the full-load current values in Tables 430.247 through 430.250, not the motor nameplate current. The nameplate figure is used for the overload protection instead.
NEC 430.52
Sets the maximum rating of the branch-circuit short-circuit and ground-fault protective device, up to 250% of the table full-load current for an inverse-time breaker, so the device rides through starting inrush.
NEC 430.32
Overload protection for a continuous-duty motor is sized at 115% to 125% of the nameplate full-load current, and is separate from the branch-circuit device. In a submersible installation this is normally in the control box or built into the pump.
NEC 300.5
Burial depths for the run out to the well head. Direct-buried cable and conduit have different minimum cover, and the trench often shares its route with the water line.
Check your exact run
These figures assume a standard installation with no derating. For your actual length, voltage, conductor material and termination rating, run the numbers:
Ampacities are NEC 310.16 reference values for not more than three current-carrying conductors at 30°C ambient, with no derating applied. Local wiring rules and the equipment manufacturer's instructions take precedence. Verify against the applicable code before installing.
Free download
Get the printable wire size charts
NEC 310.16 ampacity for copper and aluminium at 60, 75 and 90 C, how far each size runs before voltage drop bites, standard breaker sizes and AWG to mm2. Three pages, made for the van door.
Frequently Asked Questions
What size wire for a well pump 150 feet away?
For a 1 hp, 240 V pump drawing about 10 A, 12 AWG copper holds voltage drop under 3% for about 178 ft, so a 150 ft run is inside the limit. Beyond roughly 178 ft, step up to 10 AWG, which reaches about 302 ft at the same load. Those figures are for the supply run to the well head only, not the drop cable down the borehole.
Is the drop cable down the well the same size as the supply run?
Not necessarily, and it is sized by a different method. The pump manufacturer publishes a drop-cable chart based on motor horsepower, voltage and total cable length, and it is usually more conservative than a 3% branch-circuit target because motor starting at depth is the limiting case. Use their chart for the borehole and this page for the run from the panel to the well head, then check that the two lengths together still keep the total drop acceptable.
Does a well pump circuit need GFCI protection?
The pump circuit itself generally does not, but any receptacle installed at the well head or in the pump house falls under the usual NEC 210.8 requirements for outdoor and accessory-building receptacles. Some jurisdictions require additional protection for pumps in wet locations, so confirm locally.
Why does my pump trip the breaker only in summer?
Usually starting current combined with a marginal supply. Motor starting current is largely fixed, but a longer or hotter conductor has more resistance, so the voltage at the motor sags further at start, the motor draws more, and a breaker that was on the edge finally trips. It can also be the pressure switch cycling more often under heavier summer demand. Check the running voltage at the pressure switch under load before assuming the breaker is faulty.
Can I run the pump circuit in the same trench as the water line?
Commonly yes, and it is normal practice, subject to the burial depths in NEC 300.5 and any local separation requirement between the electrical raceway and the water service. Use a wiring method listed for the conditions, keep the cover depth for the method you choose, and lay warning tape above the run.
Wire size for other circuits
Or start from the breaker rating instead of the appliance:
Related Calculators
Continue with these related electrical tools
Wire Size Calculator
Smallest conductor that meets ampacity and the voltage-drop limit (AWG/mm2)
Voltage Drop Calculator
Voltage drop over a run by length, current and conductor (AWG/mm2, 1ph/3ph/DC)
Motor FLA Calculator
Motor full-load amps from horsepower, voltage and phase
HP to Amps Calculator
Motor running current from horsepower, efficiency and power factor
Ampacity Chart
NEC 310.16 copper and aluminium ampacity at 60, 75 and 90 C, with AWG to mm2
Conduit Fill Chart
How many THHN wires fit in EMT and PVC conduit, from NEC Chapter 9