Wire Size for an Electric Dryer
A domestic electric dryer runs on a dedicated 240 V circuit protected at 30 A. The wire size is not the interesting part of this job, because the answer has been the same for decades; the part that catches people out is the four-wire cord and receptacle, which replaced the old three-wire arrangement and is not optional on new work.
Short answer
The 30 A, 240 V circuit for an electric dryer needs 10 AWG copper, or 8 AWG aluminium, sized from the 60°C column of NEC 310.16.
At the 24 A this actually draws, that copper conductor stays inside a 3% voltage drop for roughly 126 ft one-way, so a typical 50 ft run needs no upsizing.
Wiring: four-wire: two hots, a neutral and a separate equipment grounding conductor.
The circuit
A standard vented or condenser dryer draws around 24 A at 240 V, the heating element accounting for almost all of it. The motor and controls take a further amp or so. The circuit is a dedicated 30 A two-pole breaker feeding a single NEMA 14-30 receptacle, and NEC 220.54 lets a dwelling load calculation use 5,000 VA or the nameplate, whichever is larger, for the dryer.
| Supply | 240 V, single-phase |
| Running load | 24 A |
| Continuous load? | No, so the 125% rule does not apply |
| Overcurrent device | 30 A two-pole |
| Conductor sized to | 30 A, from the 30 A circuit rating, with the NEC 240.4(D) cap on 10 AWG copper landing on the same size |
| Copper conductor | 10 AWG (30 A at 60°C) |
| Aluminium conductor | 8 AWG (35 A at 60°C) |
| Typical run length | 50 ft one-way |
A dryer is not a continuous load. It cycles the element on and off against a thermostat and a full cycle is under three hours, so the 125% rule in NEC 210.19 does not apply and the circuit is simply rated above the 24 A draw. 30 A is the standard size that fits, and it has been the domestic dryer circuit for as long as electric dryers have been sold.
Sizes at each termination rating
These are the ampacity minimums at each column. Terminations carry their own temperature rating, and the conductor is sized from the lowest-rated component in the circuit. NM cable is fixed at the 60°C column by NEC 334.80 whatever the terminations are rated, which is why a cable installation often needs a larger conductor than the same circuit in conduit.
| Termination rating | Copper | Aluminium |
|---|---|---|
| 60°C (applies here) | 10 AWG (30 A) | 8 AWG (35 A) |
| 75°C | 10 AWG (35 A) | 8 AWG (40 A) |
| 90°C | 10 AWG (40 A) | 8 AWG (45 A) |
How far can you run it?
Ampacity sets the minimum size; voltage drop sets the maximum distance. These are one-way run lengths at the 24 A this load actually draws on a 240 V single-phase circuit.
| Copper size | Max one-way run at 3% | Max one-way run at 5% |
|---|---|---|
| 10 AWG | 126 ft | 210 ft |
| 8 AWG | 192 ft | 320 ft |
| 6 AWG | 305 ft | 509 ft |
| 4 AWG | 482 ft | 804 ft |
3% is the NEC's recommended limit for a branch circuit and 5% for feeder plus branch combined. Both live in informational notes rather than enforceable rules, but 3% is what most inspectors and specifiers work to.
Three-wire dryer circuits are not permitted on new work
Until 1996 a dryer could be wired with two hots and a neutral, with the frame bonded to that neutral, so the cord had three prongs (NEMA 10-30). NEC 250.140 ended that for new installations: the frame now has to be grounded by a separate equipment grounding conductor, which is why the modern cord and receptacle are four-wire (NEMA 14-30). An existing three-wire circuit in a dwelling may stay in service under the exception in 250.140, but you cannot install a new one, extend one, or reuse the old three-wire cable when you rewire. If you are replacing a dryer and find a three-prong outlet, the cord on the new machine has to match the outlet you actually have, and the bonding strap inside the dryer has to be set accordingly, which is the step most often missed.
The code articles that apply
NEC 250.140
Frames of ranges and clothes dryers must be grounded by an equipment grounding conductor. The exception that allows an existing three-wire circuit to keep using the grounded (neutral) conductor applies only to installations already in place, not to new circuits.
NEC 220.54
A dwelling load calculation uses 5,000 VA or the nameplate rating, whichever is larger, for a household electric clothes dryer. That is the figure that goes into the service calculation, not the 24 A running current.
NEC 210.21(B)
A single receptacle on an individual branch circuit must have an ampere rating not less than the circuit rating, which is why a 30 A circuit takes a 30 A receptacle rather than a smaller one.
NEC 240.4(D)(8)
Caps 10 AWG copper at a 30 A overcurrent device (item (8) in the 2023 edition, (7) in 2020). Here that cap and the circuit rating agree, so 10 AWG is both the minimum and the standard answer.
Check your exact run
These figures assume a standard installation with no derating. For your actual length, voltage, conductor material and termination rating, run the numbers:
Ampacities are NEC 310.16 reference values for not more than three current-carrying conductors at 30°C ambient, with no derating applied. Local wiring rules and the equipment manufacturer's instructions take precedence. Verify against the applicable code before installing.
Free download
Get the printable wire size charts
NEC 310.16 ampacity for copper and aluminium at 60, 75 and 90 C, how far each size runs before voltage drop bites, standard breaker sizes and AWG to mm2. Three pages, made for the van door.
Frequently Asked Questions
Can I use 12 AWG wire for a dryer?
No. NEC 240.4(D) caps 12 AWG copper at a 20 A overcurrent device, and a dryer circuit is protected at 30 A. 10 AWG is the minimum, and the same section caps it at 30 A, which matches the breaker.
Why does my new dryer have four prongs when the outlet has three?
The outlet predates the 1996 change in NEC 250.140 and is a three-wire NEMA 10-30. New dryers ship with no cord fitted precisely because the installer has to match the outlet. You may fit a three-prong cord to the existing three-wire circuit, with the dryer's bonding strap connected, or run a new four-wire circuit and use a four-prong cord with the strap removed. What you must not do is fit a four-prong cord to a three-wire circuit and leave the ground pin unconnected.
Does a gas dryer need the same circuit?
No. A gas dryer heats with gas and only needs power for the motor, controls and igniter, so it plugs into an ordinary 120 V receptacle and draws a few amps. The 240 V, 30 A circuit on this page is for an electric dryer only.
Can the dryer share a circuit with the washer?
No. NEC 210.23 does not permit a fastened-in-place appliance of this size to share a branch circuit, and the laundry receptacle for the washer is required by 210.11(C)(2) to be its own 20 A circuit serving no other outlets. Dryer and washer are two separate circuits.
Is 10/2 or 10/3 cable right for a dryer?
Neither designation on its own: you need 10/3 with ground, which is three insulated conductors (two hots and a neutral) plus a bare or green equipment grounding conductor, four wires in total. 10/2 with ground has only one hot and cannot supply a 240 V dryer with a neutral for the 120 V controls.
Related Calculators
Continue with these related electrical tools
Wire Size Calculator
Smallest conductor that meets ampacity and the voltage-drop limit (AWG/mm2)
Breaker / Fuse Sizing Calculator
Next standard breaker or fuse size for a load (NEC 240.6)
Voltage Drop Calculator
Voltage drop over a run by length, current and conductor (AWG/mm2, 1ph/3ph/DC)
Amps to Watts Calculator
Real power from current, voltage and power factor
Ampacity Chart
NEC 310.16 copper and aluminium ampacity at 60, 75 and 90 C, with AWG to mm2
Conduit Fill Chart
How many THHN wires fit in EMT and PVC conduit, from NEC Chapter 9