Wire Size for an Electric Range

A freestanding electric range or a cooktop and wall oven pair runs on a dedicated 240 V circuit, most often protected at 50 A. Unlike a dryer, ranges vary widely: the nameplate decides the circuit, and a 40 A range and a 50 A range are wired differently. Check the plate on the back or inside the drawer before buying cable.

Short answer

The 50 A, 240 V circuit for an electric range needs 6 AWG copper, or 4 AWG aluminium, sized from the 60°C column of NEC 310.16.

At the 40 A this actually draws, that copper conductor stays inside a 3% voltage drop for roughly 183 ft one-way, so a typical 35 ft run needs no upsizing.

Wiring: four-wire: two hots, a neutral and a separate equipment grounding conductor.

The circuit

A typical freestanding range is rated between 8 kW and 12 kW, which at 240 V is roughly 33 A to 50 A. The 50 A circuit on this page suits the common 40 A nameplate draw with margin, and feeds a single NEMA 14-50 receptacle. Because the elements and the oven never all run flat out at once, NEC 220.55 lets a dwelling load calculation take a single range of 12 kW or less as 8 kW of demand rather than its full rating.

Supply240 V, single-phase
Running load40 A
Continuous load?No, so the 125% rule does not apply
Overcurrent device50 A two-pole
Conductor sized to50 A, from the 50 A circuit rating under NEC 210.19(A)(3)
Copper conductor6 AWG (55 A at 60°C)
Aluminium conductor4 AWG (55 A at 60°C)
Typical run length35 ft one-way

A range is not a continuous load: elements cycle on a thermostat and cooking sessions are short, so the 125% rule does not apply. The breaker is chosen to sit above the nameplate draw at a standard size, which for most freestanding ranges is 50 A. A compact or slide-in unit with a 40 A nameplate belongs on a 40 A circuit instead, with the conductor sized to match that.

Sizes at each termination rating

These are the ampacity minimums at each column. Terminations carry their own temperature rating, and the conductor is sized from the lowest-rated component in the circuit. NM cable is fixed at the 60°C column by NEC 334.80 whatever the terminations are rated, which is why a cable installation often needs a larger conductor than the same circuit in conduit.

Termination rating Copper Aluminium
60°C (applies here) 6 AWG (55 A) 4 AWG (55 A)
75°C 8 AWG (50 A) 6 AWG (50 A)
90°C 8 AWG (55 A) 6 AWG (55 A)

How far can you run it?

Ampacity sets the minimum size; voltage drop sets the maximum distance. These are one-way run lengths at the 40 A this load actually draws on a 240 V single-phase circuit.

Copper size Max one-way run at 3% Max one-way run at 5%
6 AWG 183 ft 305 ft
4 AWG 289 ft 482 ft
3 AWG 360 ft 600 ft
2 AWG 476 ft 793 ft

3% is the NEC's recommended limit for a branch circuit and 5% for feeder plus branch combined. Both live in informational notes rather than enforceable rules, but 3% is what most inspectors and specifiers work to.

The nameplate decides, not the category

Two ranges the same size can call for different circuits. A 9.6 kW model draws 40 A and is specified for a 40 A circuit; a 12 kW double-oven model draws 50 A and needs 50 A. Fitting a 50 A receptacle to a 40 A circuit, or wiring for 40 A because the last range was, is the failure mode here. If you are running the cable before the appliance is chosen, wiring for 50 A costs one size of conductor and covers both cases, since a 40 A range on a 50 A circuit is permitted for a cord-and-plug range under NEC 210.19 while the reverse is not.

The code articles that apply

NEC 220.55

Demand factors for household cooking appliances. A single range rated 12 kW or less is taken as 8 kW of demand in a dwelling load calculation, which is why adding a range does not consume the full nameplate of the service.

NEC 250.140

Range frames are grounded by an equipment grounding conductor. The pre-1996 three-wire method survives only on existing installations, so new work is four-wire with a NEMA 14-50 receptacle.

NEC 210.19(A)(3)

Branch-circuit conductors supplying a range may have an ampacity not less than the rating of the branch circuit, with the neutral of a 50 A range circuit permitted to be smaller than the ungrounded conductors but not smaller than 10 AWG.

NEC 422.33

Where a cord-and-plug connected range is used, the plug and receptacle may serve as the disconnecting means, which is why a receptacle behind the appliance satisfies the disconnect requirement without a separate switch.

Check your exact run

These figures assume a standard installation with no derating. For your actual length, voltage, conductor material and termination rating, run the numbers:

Ampacities are NEC 310.16 reference values for not more than three current-carrying conductors at 30°C ambient, with no derating applied. Local wiring rules and the equipment manufacturer's instructions take precedence. Verify against the applicable code before installing.

Free download

Get the printable wire size charts

NEC 310.16 ampacity for copper and aluminium at 60, 75 and 90 C, how far each size runs before voltage drop bites, standard breaker sizes and AWG to mm2. Three pages, made for the van door.

We store your email with EmailOctopus to send the charts and occasional wiring and calculator tips, nothing else. Unsubscribe any time. Privacy policy.

Frequently Asked Questions

Do I need 6 AWG or 8 AWG for an electric range?

For a 50 A circuit, 6 AWG copper is the answer with 60°C terminations or NM cable, which is the usual case. 8 AWG copper is rated 50 A at the 75°C column and is permitted only when every termination in the circuit is listed 75°C and the conductor is a 75°C or 90°C type in conduit. NM cable is fixed at the 60°C column by NEC 334.80, so a cable installation takes 6 AWG.

Can a cooktop and a wall oven share one circuit?

Often yes. NEC 210.19(A)(3) exception 1 permits the taps to a counter-mounted cooking unit and up to two wall ovens to be supplied from a single branch circuit, provided each tap conductor has an ampacity of at least 20 A and is no longer than necessary. Many installers still run separate circuits because it simplifies the load calculation and future replacement.

Why is the range circuit 50 A when the range only draws 40 A?

The breaker protects the conductor, not the appliance, and it is sized at a standard rating above the load rather than exactly on it. A 40 A draw on a 50 A circuit is normal for a cord-and-plug range. What matters is that the conductor is sized for the 50 A device and the receptacle matches it.

Can I use the old three-wire range cable?

Only if it is already installed and stays as it is. NEC 250.140 allows an existing three-wire range circuit in a dwelling to remain, but new circuits, extensions and rewires all need the four-wire arrangement with a separate equipment grounding conductor.

What about a slide-in range with no receptacle?

Some ranges are hard-wired rather than cord-and-plug. The conductor sizing is identical; what changes is the disconnecting means, since you no longer have the plug and receptacle that NEC 422.33 accepts. A hard-wired range needs the branch-circuit breaker to be capable of being locked in the open position, or a separate disconnect within sight.