Wire Size for a Sub-Panel

A sub-panel feeder carries part of a service to a garage, a workshop, an addition or a second floor. The 100 A feeder on this page is the common size. Two things separate it from a branch circuit: the neutral and the ground must be separated at the sub-panel, and if the sub-panel is in a detached building there are extra grounding requirements at that structure.

Short answer

The 100 A, 240 V feeder for a sub-panel needs 1 AWG copper, or 1/0 AWG aluminium, sized from the 60°C column of NEC 310.16.

At the 80 A this actually draws, that copper conductor stays inside a 3% voltage drop for roughly 301 ft one-way, so a typical 80 ft run needs no upsizing.

Wiring: four-wire: two hots, an insulated neutral and an equipment grounding conductor, with the neutral and ground kept separate at the sub-panel.

The circuit

A 100 A sub-panel feeder is a two-pole 100 A breaker in the main panel feeding four conductors to a panel elsewhere. The 80 A figure used for the run-length table is a realistic calculated load for such a panel rather than its full rating, since a feeder is sized to the calculated load under NEC Article 220 and not to the sum of every breaker fitted to it. Sub-panels are frequently fitted with a 100 A feeder and loaded to a fraction of it, precisely so there is room to grow.

Supply240 V, single-phase
Running load80 A
Continuous load?No, so the 125% rule does not apply
Overcurrent device100 A two-pole
Conductor sized to100 A, from the 100 A feeder rating under NEC 215.2
Copper conductor1 AWG (110 A at 60°C)
Aluminium conductor1/0 AWG (100 A at 60°C)
Typical run length80 ft one-way

A feeder is sized from the calculated load under NEC 215.2 and Article 220, with continuous portions of that load taken at 125%. It is not sized by adding up the breakers in the sub-panel, which would give an absurd answer for any panel with spare ways. The 100 A device here protects the feeder conductors, and the sub-panel's own busbar rating must be at least that.

Sizes at each termination rating

These are the ampacity minimums at each column. Terminations carry their own temperature rating, and the conductor is sized from the lowest-rated component in the circuit. NM cable is fixed at the 60°C column by NEC 334.80 whatever the terminations are rated, which is why a cable installation often needs a larger conductor than the same circuit in conduit.

Termination rating Copper Aluminium
60°C (applies here) 1 AWG (110 A) 1/0 AWG (100 A)
75°C 3 AWG (100 A) 1 AWG (100 A)
90°C 3 AWG (115 A) 2 AWG (100 A)

How far can you run it?

Ampacity sets the minimum size; voltage drop sets the maximum distance. These are one-way run lengths at the 80 A this load actually draws on a 240 V single-phase circuit.

Copper size Max one-way run at 3% Max one-way run at 5%
1 AWG 301 ft 502 ft
1/0 AWG 378 ft 630 ft
2/0 AWG 447 ft 745 ft
3/0 AWG 583 ft 972 ft

3% is the NEC's recommended limit for a branch circuit and 5% for feeder plus branch combined. Both live in informational notes rather than enforceable rules, but 3% is what most inspectors and specifiers work to.

Separate the neutral from the ground, and ground a detached structure locally

In a sub-panel the neutral bar must be isolated from the enclosure and the equipment grounding conductors landed on a separate bonded bar. The bonding screw or strap that ties neutral to enclosure in a main panel has to be removed or left out, because bonding them at both ends puts normal neutral current onto the grounding conductor and the metal parts it connects. Separately, NEC 250.32(A) requires a grounding electrode system at a detached building or structure supplied by a feeder, in addition to the equipment grounding conductor run with that feeder. A detached garage sub-panel therefore needs its own ground rods even though a ground wire already arrives from the house. Since the 2008 code the old practice of grounding a detached structure through the neutral has not been permitted for new work.

The code articles that apply

NEC 250.32(A)

Buildings or structures supplied by a feeder must have a grounding electrode system installed at that structure and connected to the equipment grounding conductor. There is a narrow exception where a structure is supplied by only a single branch circuit.

NEC 250.24(A)(5)

The grounded (neutral) conductor must not be connected to the enclosure or the equipment grounding conductors on the load side of the service disconnect, which is what requires a sub-panel to keep neutral and ground separate.

NEC 215.2(A)(1)

Feeder conductors must have an ampacity not less than the non-continuous load plus 125% of the continuous load, sized from the calculated load rather than from the sum of the downstream overcurrent devices.

NEC 250.122

Sizes the equipment grounding conductor from the rating of the overcurrent device ahead of the feeder. For a 100 A feeder, Table 250.122 gives 8 AWG copper.

Check your exact run

These figures assume a standard installation with no derating. For your actual length, voltage, conductor material and termination rating, run the numbers:

Ampacities are NEC 310.16 reference values for not more than three current-carrying conductors at 30°C ambient, with no derating applied. Local wiring rules and the equipment manufacturer's instructions take precedence. Verify against the applicable code before installing.

Free download

Get the printable wire size charts

NEC 310.16 ampacity for copper and aluminium at 60, 75 and 90 C, how far each size runs before voltage drop bites, standard breaker sizes and AWG to mm2. Three pages, made for the van door.

We store your email with EmailOctopus to send the charts and occasional wiring and calculator tips, nothing else. Unsubscribe any time. Privacy policy.

Frequently Asked Questions

Does a sub-panel need a four-wire feeder?

Yes for new work. Two hots, a neutral and a separate equipment grounding conductor, with neutral and ground separated at the sub-panel. Three-wire feeders to detached structures, where the neutral doubled as the ground, were removed from the code for new installations and are only tolerated where they already exist and no other metallic path runs between the buildings.

Do I need ground rods at a detached garage sub-panel?

Yes. NEC 250.32(A) requires a grounding electrode system at the separate structure, which usually means two ground rods 6 ft apart unless a single rod is shown to have 25 ohms or less resistance. That is in addition to, not instead of, the equipment grounding conductor run with the feeder.

Can the sub-panel breaker be larger than the panel rating?

No. The feeder breaker must not exceed the busbar rating of the sub-panel it supplies. A 100 A feeder needs a panel rated at least 100 A; fitting a 100 A breaker ahead of a 60 A rated panel over-protects the busbar and is a violation even if the actual load is small.

How do I size the feeder if I do not know the load?

Do a load calculation under NEC Article 220 for what the sub-panel will actually supply: lighting and receptacle loads at the code figures, appliances at nameplate with the applicable demand factors, and any continuous load at 125%. Sizing by adding up breaker ratings gives a wildly oversized answer, since a panel full of 20 A ways is never loaded to the sum of them.

Should I run 100 A conductor even for a 60 A sub-panel?

It is a common and sensible choice where the feeder is buried or in finished conduit, because upgrading the panel later is easy and upgrading the feeder is not. The breaker still has to match the conductor and the panel rating, so you would fit the 60 A breaker now and change it, and the panel, when the load grows.

Wire size for other circuits

Or start from the breaker rating instead of the appliance: